PS-DA and PS -SA <br />Conventional Pull -Stations <br />Engineering Specification <br />Manual Fire Alarm Stations shall be non -code, with a key -operated reset lock in order that they may be tested, <br />and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a <br />key. An operated station shall automatically condition itself so as to be visually detected as activated. Manual <br />stations shall be constructed of red colored LEXAN® (or polycarbonate equivalent) with clearly visible operating <br />instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 <br />inches (25.4 mm) or larger.* Stations shall be suitable for surface mounting on matching back -box SB-10; or <br />semi -flush mounting on a standard single -gang, double -gang, or 4" (10.16 cm) square electrical box, and shall <br />be installed within the limits defined by the Americans with Disabilities Act (ADA) or per national/local require- <br />ments. Manual Stations shall be Underwriters Laboratories listed. <br />*NOTE: The words "FIRE/FUEGO" on the PS-DASP shall appear on the front of the station in white letters, <br />approximately 3/4" high. <br />PS -SA Front View <br />o CD <br />PS-DA Front View PS -SA Rear View PS-DA Rear View <br />SILENT This document is not intended to be used for installation purposes. We try to <br />KNIGHT keep our product information up-to-date and accurate. We cannot cover all <br />specific applications or anticipate all requirements. All specifications are sub- <br />ject to change without notice. For more information, contact Silent Knight 12 <br />by Honeywell Clintonville Road Northford, CT 06472-1610 Phone: (800) 328-0103, <br />Fax: (203) 484-7118. www.silentknight.com <br />MADE IN AMERICA <br />P/N 350241 Rev. D <br />© 2011 Honeywell International Inc. <br />