<br /> MECHANICAL COMPLIANCE SUMMARY
<br /> 2018 WSEC Compliance Forms for Commercial Buildings including Group R2,R3&R4 over 3 stories and all RI Admiuistemd by:C 2022 NEEA,All rights reserved
<br /> Project Title American Red Cross Everett-2018 WSEC IF.,Building Department Use: I Date: Nov 17,2022
<br /> 1010 SE Everett Mall Way
<br /> Project Address Suite 202
<br /> Project&Applicant Everett,WA 98028
<br /> Information Applicant Name GUNNAR LEHNERTZ
<br /> Applicant Phone 206-364-3343
<br /> Applicant Email glehnertz@robiam engineering.com
<br /> For questions about this report,contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
<br /> General Occupancy All Commercial General Building Use Type Office,Professional Ifundiding Cond.Floor Area 3,600
<br /> New Building Project Cand.Floor Area 3,600
<br /> Alteration
<br /> General Project Types Alteration or Addition Single Zone Systema&Equipment Floors Above Grade I
<br /> M.1mulcal Scope Mechanical Scope Compliance Method Compliance Method 1-General
<br /> Mechanical Project Description REPLACE EXISTING HOT WATER CHILLED WATER FAN COILS WITH NEW.PROVIDE DUCTWORK AND ASSOCIATED GRO'S FOR TENANT IMPROVEMENT. N
<br /> Economizer Equipment Efficiency L
<br /> Project DOAS Ventilation Higher Equipment N
<br /> Mechanical Scope Exception(s) Compliance
<br /> Mechanical Compliance Type Provided? ERciency Option Applied?
<br /> Scope and Method Applied? Verification
<br /> Alteration Single Zone Systems& Yes No NA COMPLIES -ttEquipmentLU tt
<br /> Additional Efficiency U)
<br /> Credits Included(AEC) N
<br /> Does building include occupancy classscations requiring Yes Does project include DOAS equipment? No I ICU Q
<br /> DOAS? TSPR? �/� 00 N
<br /> Based on project scope do TSPR requirements apply? No D.all systems comply with Appendix D standard reference design or qualify for an exception to No ( ll 0') (V
<br /> _ CD
<br /> Scope&Space Conditioning IkLTE 'Hon O Q N
<br /> V � � N
<br /> Single Zone Air Systems Category-Heat pump,applied(water or ground loop,groundwater) �e �
<br /> Air Systems Summary Information Q) O
<br /> Quantity Supply AirBow Ventilation CFM Ventilation Energy Recovery
<br /> SysteMEquip ID of Rema Control Vemilati.n Standard (Total if Multiple Items) All Source Paired with DOAS Ventilation energy recovery Mcieney(%) LU LU
<br /> W SHP-3 Constant volume ASHRAE Standard 62.1 410 Other System LU
<br /> WSHP-2 Constant volume ASHRAE Standard 62.1 410 Other System U)
<br /> W SHP-1 I Constant volume ASHRAE Standard 62.1 410 Other System 0
<br /> WSHP4 Constant volume ASHRAE Standard 62.1 410 Other System I V
<br /> Am Systems&Equipment-Cooling
<br /> system/ Cooling Capacity AEC Efficiency been.Exception Combined Efficiency Proposed Cooling CE Proposed Part PL Efficiency Compliance •L
<br /> Equip Cooling SystaWEgmip Type specific Type per item(BtWh) Multiplier Multiplier(FL th PL) Multiplier(AEC&Econo) Ef tiency Units I Load Efficiency Units Verification
<br /> WSHP-3 Heat pump,water loop Water to air 46,700 1 1.0 I 13.1 EER COMPETES
<br /> WSHP-2 Heat pump,water loop Weter to air 33,300 I 1.0 1 13.7 EER COMPLIES
<br /> WSHP-1 Heat pump,water loop Water to air 41,200 1 1.0 1 13.0 EER COMPLIES
<br /> WSHP-4 Heat pump,water loop Water to air 33,300 1 1.it 1 13.7 EER COMPLIES
<br /> Av Systems&Equipment-Heating
<br /> Heat Pump Heating Proposed Low
<br /> System AECEffrricney Prop.sed Heat Pump HPH LWTH Efficiency Complianm
<br /> /Equip ID Heating System/Equip Type Specific Type Capacity per Unit Cooling Capacity(Btu/h) Multiplier Heating Efficiency Units Water Temp Units verification
<br /> (Broth) Efficiency
<br /> https://waenergycodes.com/print_project_summary_form.php?k=Y29tYm9fdGZ2X3BOPW 11Y79odmFjX3N5c196b25pbmdfc2luZ2xIJTdDcGRfYWxOZXJhdGlvbiZOZnY9bW VjX2h2YW Nfe31zX3pvbmluZl... 112
<br /> 11/17/22,2:05 PM https:llwaenergycodes.comlprint_project_summary_fonn.php?k=Y29tYm9fdGZ2X3BOPW11Y19odmFjX3N5cl96b25pbmdfc2luZ2xIJTdDcGRfYWxOZXJhdGlvbiZOZnY9bwVjX2h2Y...
<br /> WSHP-1 Heat pump,water loop,heating Water to air 50,300 41,200 I 4.5 COP COMPLIES
<br /> WSHP-4 Heat pump,water loop,heating Water to av 41,400 33,300 l 4.7 COP COMPLIES
<br /> WSHP-3 Heat pump,water loop,heating Water to air 57,700 48,700 1 4.7 COP COMPLIES
<br /> WSHP-2 Heat pump,water loop,heating Water to air 1 41,400 1 33,300 I 1 4.7 1 COP COMPLIES
<br /> Air Systems&Equipment Details
<br /> System/Equip ID I Area(s)Served Location In Project Documents-Plan/Detail N
<br /> WSHP-3 Office MO.1,M2.1 07/28/2022
<br /> Sysono/Equip to for a single or multiple items?:Single item
<br /> Heating Section/Auxilimy Heating Type:Other source Economizer Compliance Method:Applying air-side economizer exception
<br /> Airside economzer iexception applied:Exp 1-DOAS paired with cooling system(Note equip location limitations)WSEC Equip Efficiency Reference Table-Cooling:Table C403.3.2(2)-Unitary and Applied Heat Pumps CONSTRUCTION
<br /> WSEC Equip Efficiency Reference Table-Heating:Table C403.3.2(2)-Unitary and Applied Heat Pumps DOCUMENTS I
<br /> WSHP-2 Office 7 MOA,M2.1 J
<br /> Sy-o,fEquip ID for a single or multiple items?:Single it..
<br /> Heating Section/Auxiliary Heating Type:Other sourceEconomizer Compliance Method:Applying air-side economizer exception
<br /> economizer Air-side exception applied:Exp 1-DOAS paired with cooling system(Note equip location limitations)WSEC Equip Efficiency Reference Table-Cooling:Table C403.3.2(2)-Unitary and Applied Heat Pumps
<br /> WSEC Equip Efficiency Reference Table-Heating:Table C403.3.2(2)-Unitary and Applied He.Pumps
<br /> W SHP-1 Office MO.1,M2.1
<br /> Systene/Equip ID fr a single or multiple items?:Single it.. Revisions
<br /> Heating Section/Auxiliary Heating Type:Other source Economizer Compliance Method:Applying airside economizer exception No. Description Date
<br /> Air-side economizer exception applied:Exp 1-DOAS paired with cooling system(Note equip location limitations)WSEC Equip Efficiency Reference Table-Cooling:Table C403.3.2(2)-Unitary and Applied Heat Pumps 0 100%SUBMITTAL 7/28/22ate
<br /> WSEC Equip Efficiency Reference Table-Heating:Table C403.3.2(2)-Unitary and Applied Heat Pumps 2 REVISIONS 11/17/22
<br /> WSHP4 Ofce MO.1,M2.1
<br /> System/Equip to for a single or multiple items?:Single item
<br /> Heating SectimlAuxiEary Heating Type:Electric resistance(or None) Economizer Compliance Method:Applying.imide economizer exception
<br /> Air_de economizer exception applied:Exp I-DOAS paired with cooling system(Note equip location limitations)WSEC Equip Efficiency Reference Table-Cooling:Table C403.3.2(2)-Unitary and Applied Heat Pumps
<br /> W SEC Equip Efficiency Reference Table-Heating:Table C403.3.2(2)-Unitary and Applied Heat Pumps
<br /> American Red
<br /> Cross: Everett,WA
<br /> Owner
<br /> 1010 SE Everett Mall Way
<br /> https://waenergycodes.com/print_project_summary_form.php?k=Y29tYm9fdGZ2X3BOPW11Y19odmFjX3N5cl96b25pbmdfc2luZ2xIJTdDcGRfYWxOZXJhdGlvbiZOZnY9bWvjX2h2YWNfc3lzX3pvbmluZl... 2/2 Suite 202
<br /> 2 Everett,WA 98028
<br /> Project Number
<br /> 22001 D
<br /> Date
<br /> 11/17/2022
<br /> ENERGY
<br /> FORMS
<br /> M0.3
<br /> This drawing is the property of LIVE design group pc,and is not to be reproduced,copied,or altered in whole or in part or used for any purpose without the approval of LIVE design group pc,and is to be returned upon request. 331 p205.870.30901 f205.870.30931 www.LIVEdesigngroup.00m 7/26/20224:30:20 PM