|
r r N
<br /> CROWN CASTLE USA INC. SITE ACTIVITY REQUIREMENTS: GENERAL NOTES: ELECTRICAL INSTALLATION NOTES:
<br /> 1. FOR THE PURPOSE OF CONSTRUCTION DRAWING, THE FOLLOWING DEFINITIONS SHALL APPLY:
<br /> 1. NOTICE TO PROCEED- NO WORK SHALL COMMENCE PRIOR TO CROWN CASTLE USA INC. WRITTEN NOTICE TO PROCEED CONTRACTOR: GENERAL CONTRACTOR RESPONSIBLE FOR CONSTRUCTION 1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, NEC AND ALL
<br /> (NTP)AND THE • U ISSUANCE OF A PURCHASE ORDER. PRIOR TO ACCESSING/ENTERING THE SITE YOU MUST CONTACT CARRIER: T-MOBILE APPLICABLE FEDERAL, STATE.AND LOCAL CODES/ORDINANCES. Mobile THE CROWN CASTLE USA INC. NOC AT 800-788-7011 &THE CROWN CASTLE USA INC. CONSTRUCTION MANAGER. TOWER OWNER: CROWN CASTLE USA INC. 2. CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT IS
<br /> 2. "LOOK UP" - CROWN CASTLE USA INC. SAFETY CUMB REQUIREMENT: 2. THESE DRAWINGS HAVE BEEN PREPARED USING STANDARDS OF PROFESSIONAL CARE AND COMPLETENESS NORMALLY NOT BLOCKED AND TRIP HAZARDS ARE ELIMINATED.
<br /> THE INTEGRITY OF THE SAFETY CLIMB AND ALL COMPONENTS OF THE CUMBING FACILITY SHALL BE CONSIDERED EXERCISED UNDER SIMILAR CIRCUMSTANCES BY REPUTABLE ENGINEERS IN THIS OR SIMILAR LOCALITIES. IT IS 3. WIRING. RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC. 12920 SE 38TH STREET
<br /> DURING ALL STAGES OF DESIGN. INSTALLATION.AND INSPECTION. TOWER MODIFICATION. MOUNT REINFORCEMENTS, ASSUMED THAT THE WORK DEPICTED WILL BE PERFORMED BY AN EXPERIENCED CONTRACTOR AND/OR WORKPEOPLE 4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC.
<br /> AND/OR EQUIPMENT INSTALLATIONS SHALL NOT COMPROMISE THE INTEGRITY OR FUNCTIONAL USE OF THE SAFETY WHO HAVE A WORKING KNOWLEDGE OF THE APPLICABLE CODE STANDARDS AND REQUIREMENTS AND OF INDUSTRY 4.1. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF APPROVAL, AND SHALL CONFORM TO BELLEVUE,WA 98006
<br /> CLIMB OR ANY COMPONENTS OF THE CLIMBING FACILITY ON THE STRUCTURE. THIS SHALL INCLUDE. BUT NOT BE ACCEPTED STANDARD GOOD PRACTICE. AS NOT EVERY CONDITION OR ELEMENT IS (OR CAN BE) EXPLICITLY SHOWN REQUIREMENT OF THE NATIONAL ELECTRICAL CODE.
<br /> LIMITED TO: PINCHING OF THE WIRE ROPE, BENDING OF THE WIRE ROPE FROM ITS SUPPORTS, DIRECT CONTACT OR ON THESE DRAWINGS, THE CONTRACTOR SHALL.USE INDUSTRY ACCEPTED STANDARD GOOD PRACTICE FOR 4.2. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN
<br /> CLOSE PROXIMITY TO THE WIRE ROPE WHICH MAY CAUSE FRICTIONAL WEAR, IMPACT TO THE ANCHORAGE POINTS IN MISCELLANEOUS WORK NOT EXPLICITLY SHOWN. THE SHORT CIRCUIT CURRENT TO WHICH THEY ARE SUBJECTED, 20,000 AIC MINIMUM. VERYIFY AVAILABLE SHORT
<br /> ANY WAY, OR TO IMPEDE/BLOCK ITS INTENDED USE. ANY COMPROMISED SAFETY CLIMB, INCLUDING EXISTING 3. THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE MEANS OR METHODS OF CIRCUIT CURRENT DOES NOT EXCEED THE RATING OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE
<br /> CONDITIONS MUST BE TAGGED OUT AND REPORTED TO YOUR CROWN CASTLE USA INC. POC OR CALL THE NOC TO CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS, 110.24 NEC OR THE MOST CURRENT ADOPTED CODE PRE THE GOVERNING JURISDICTION.
<br /> GENERATE A SAFETY CLIMB MAINTENANCE AND CONTRACTOR NOTICE TICKET. TECHNIQUES. SEQUENCES, AND PROCEDURES. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY FOR 5. EACH END OF EVERY POWER PHASE CONDUCTOR, GROUNDING CONDUCTOR,AND TELCO CONDUCTOR OR CABLE CROWN
<br /> PROTECTION OF LIFE AND PROPERTY DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE UMITED SHALL BE LABELED WITH COLOR-CODED INSULATION OR ELECTRICAL TAPE (3M BRAND, 1/2"PLASTIC ELECTRICAL
<br /> 3. PRIOR TO THE START OF CONSTRUCTION,ALL REQUIRED JURISDICTIONAL PERMITS SHALL BE OBTAINED. THIS INCLUDES. TO, BRACING, FORMWORK, SHORING, ETC. SITE VISITS BY THE ENGINEER OR HIS REPRESENTATIVE WILL NOT INCLUDE TAPE WITH UV PROTECTION, OR EQUAL).THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA. Cill:
<br /> BUT IS NOT LIMITED TO, BUILDING. ELECTRICAL, MECHANICAL, FIRE. FLOOD ZONE, ENVIRONMENTAL,AND ZONING. AFTER INSPECTION OF THESE ITEMS AND IS FOR STRUCTURAL OBSERVATION OF THE FINISHED STRUCTURE ONLY. 6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE, CASTLE
<br /> ONSITE ACTIVITIES AND CONSTRUCTION ARE COMPLETED. ALL REQUIRED PERMITS SHALL BE SATISFIED AND CLOSED 4. NOTES AND DETAILS IN THE CONSTRUCTION DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL PHASE CONFIGURATION. WIRE CONFIGURATION, POWER OR AMPACITY RATING AND BRANCH CIRCUIT ID NUMBERS i.e.
<br /> OUT ACCORDING TO LOCAL JURISDICTIONAL REQUIREMENTS. DETAILS. WHERE NO DETAILS ARE SHOWN. CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT,
<br /> 4. ALL CONSTRUCTION MEANS AND METHODS; INCLUDING BUT NOT LIMITED TO, ERECTION PLANS, RIGGING PLANS, AND/OR AS PROVIDED FOR IN THE CONTRACT DOCUMENTS. WHERE DISCREPANCIES OCCUR BETWEEN PLANS. DETAILS, PANEL BOARD AND CIRCUITU ID'S). 1505 WESTLAICE AVENUE NORTH,SUITE 800
<br /> CLIMBING PLANS, AND RESCUE PLANS SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR RESPONSIBLE GENERAL NOTES, AND SPECIFICATIONS, THE GREATER, MORE STRICT REQUIREMENTS, SHALL GOVERN. IF FURTHER 7. ALL TIEL BOARDSWRP SHALLD NUMBERS) SHALL BE CLEARLY VEDECUTED WITH PLASTICO LABELS.
<br /> FOR THE EXECUTION OF THE WORK CONTAINED HEREIN,AND SHALL MEET ANSI/ASSE A10.48 (LATEST EDITION); CLARIFICATION IS REQUIRED CONTACT THE ENGINEER OF RECORD. 8. ALL WRAPS BE CUT FLUSH WITH APPROVED CUTTING TOOL TO REMOVE SHARP EDGES. SEATTLE,WA 98109
<br /> FEDERAL. STATE,AND LOCAL REGULATIONS; AND ANY APPLICABLE INDUSTRY CONSENSUS STANDARDS RELATED TO THE 5. SUBSTANTIAL EFFORT HAS BEEN MADE TO PROVIDE ACCURATE DIMENSIONS AND MEASUREMENTS ON THE DRAWINGS TO 9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR (#14
<br /> CONSTRUCTION ACTMTIES BEING PERFORMED. ALL RIGGING PLANS SHALL ADHERE TO ANSI/ASSE A10.48 (LATEST ASSIST IN THE FABRICATION AND/OR PLACEMENT OF CONSTRUCTION ELEMENTS BUT IT IS THE SOLE RESPONSIBILITY OR LARGER) WITH TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THAW-2, RHW, OR RHW-2 INSULATION ! ., ---
<br /> EDITION)AND CROWN CASTLE USA INC. STANDARD CED-STD-10253, INCLUDING THE REQUIRED INVOLVEMENT OF A OF THE CONTRACTOR TO FIELD VERIFY THE DIMENSIONS, MEASUREMENTS,AND/OR CLEARANCES SHOWN IN THE UNLESS O SPECIFIED.
<br /> QUALIFIED ENGINEER FOR CLASS IV CONSTRUCTION, TO CERTIFY THE SUPPORTING STRUCTURE(S) IN ACCORDANCE WITH CONSTRUCTION DRAWINGS PRIOR TO FABRICATION OR CUTTING OF ANY NEW OR EXISTING CONSTRUCTION ELEMENTS. 10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOR (#6 OR
<br /> ANSI/TIA-322 (LATEST EDITION). IF IT IS DETERMINED THAT THERE ARE DISCREPANCIES AND/OR CONFUCTS WITH THE CONSTRUCTION DRAWINGS THE LARGER) WITH TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS r7
<br /> 5. ALL SITE WORK TO COMPLY WITH OAS-STD-10068 "INSTALLATION STANDARDS FOR CONSTRUCTION ACTMTIES ON ENGINEER OF RECORD IS TO BE NOTIFIED AS SOON AS POSSIBLE. OTHERWISE SPECIFIED. SQUAR ��
<br /> CROWN CASTLE USA INC. TOWER SITE"AND LATEST VERSION OF ANSI/TIA-1019-A-2012 "STANDARD FOR 6. PRIOR TO THE SUBMISSION OF BIDS, THE BIDDING CONTRACTOR SHALL VISIT THE CELL SITE TO FAMILIARIZE WITH THE 11. POWER AND CONTROL WIRING IN FLEXIBLE CORD SHALL BE MULTI-CONDUCTOR,TYPE SOON CORD (#14 OR
<br /> INSTALLATION,ALTERATION,AND MAINTENANCE OF ANTENNA SUPPORTING STRUCTURES AND ANTENNAS." EXISTING CONDITIONS AND TO CONFIRM THAT THE WORK CAN BE ACCOMPUSHED AS SHOWN ON THE CONSTRUCTION LARGER) UNLESS OTHERWISE SPECIFIED. WIRELESS
<br /> DRAWINGS. ANY DISCREPANCY FOUND SHALL BE BROUGHT TO THE ATTENTION OF CROWN CASTLE. 12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL BE MULTI-CONDUCTOR, TYPE TC CABLE (#14 OR
<br /> 6. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS,THE CONTRACTOR SHALL 7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES. LARGER), WITH TYPE THHW,THWN, THWN-2. XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS 1 3 8 7 C A l L E A V A N Z A D O
<br /> PROPOSE AN ALTERNATIVE INSTALLATION FOR APPROVAL BY CROWN CASTLE USA INC. PRIOR TO PROCEEDING WITH REGULATIONS AND ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS, OTHERWISE SPECIFIED. SAN CLEMENTE CA 92673(949)391.6824
<br /> ANY SUCH CHANGE OF INSTALLATION. ORDINANCES, RULES. REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE PERFORMANCE 13. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP-STYLE, COMPRESSION WIRE LUGS AND WIRE NUTS BY
<br /> 7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES, OF THE WORK.ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY THOMAS AND BETTS (OR EQUAL). LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION NOT LESS THAN 75' C
<br /> REGULATIONS AND ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS, SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES AND APPLICABLE REGULATIONS. (90' C IF AVAILABLE).
<br /> ORDINANCES. RULES, REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE PERFORMANCE B. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT,APPURTENANCES AND 14. RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL,
<br /> OF THE WORK.ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THE DRAWINGS. ANSI/IEEE AND NEC.
<br /> SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES AND APPUCABLE REGULATIONS. 9. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S 15. ELECTRICAL METALLIC TUBING (EMT), INTERMEDIATE METAL CONDUIT(AMC), OR RIGID METAL CONDUIT(RMC) SHALL
<br /> 8. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE. BE USED FOR EXPOSED INDOOR LOCATIONS.
<br /> RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE. 10. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL 16. ELECTRICAL METALLIC TUBING (EMT) OR METAL-CLAD CABLE (MC) SHALL BE USED FOR CONCEALED INDOOR
<br /> 9. THE CONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF CONSTRUCTION. PROPOSE AN ALTERNATIVE INSTALLATION FOR APPROVAL BY THE CARRIER AND CROWN CASTLE PRIOR TO PROCEEDING LOCATIONS. T-MOBILE SITE NUMBER:
<br /> 10. ALL EXISTING ACTIVE SEWER. WATER, GAS, ELECTRIC AND OTHER UTILITIES WHERE ENCOUNTERED IN THE WORK, SHALL WITH ANY SUCH CHANGE OF INSTALLATION. 17. SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL ELBOWS/90s AND ALL
<br /> BE PROTECTED AT ALL TIMES AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE WORK, SHALL BE 11. CONTRACTOR IS TO PERFORM A SITE INVESTIGATION AND IS TO DETERMINE THE BEST ROUTING OF ALL CONDUITS FOR APPROVED ABOVE GRADE PVC CONDUIT. SE01685B
<br /> RELOCATED AS DIRECTED BY CONTRACTOR. EXTREME CAUTION SHOULD BE USED BY THE CONTRACTOR WHEN DPOWER,RAWINGS.
<br /> TELCO AND FOR GROUNDING CABLES AS SHOWN IN THE POWER.TELCO,AND GROUNDING PLAN 18. LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT (LIQUID-ILIA FLEX) SHALL BE USED INDOORS AND OUTDOORS, WHERE
<br /> EXCAVATING OR DRILLING PIERS AROUND OR NEAR UTILITIES. CONTRACTOR SHALL PROVIDE SAFETY TRAINING FOR THE 12. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS. LANDSCAPING AND STRUCTURES. ANY VIBRATION OCCURS OR FLEXIBIUTY IS NEEDED.
<br /> WORKING CREW. THIS WILL INCLUDE BUT NOT BE UNITED TO A) FALL PROTECTION B)CONFINED SPACE C) 19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION-TYPE AND APPROVED FOR THE LOCATION
<br /> ELECTRICAL SAFETY D) TRENCHING AND EXCAVATION E) CONSTRUCTION SAFETY PROCEDURES. DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION OF CROWN CASTLE USA INC. USED. SET SCREW FITTINGS ARE NOT ACCEPTABLE. BU#:825709
<br /> 11. ALL SITE WORK SHALL BE AS INDICATED ON THE STAMPED CONSTRUCTION DRAWINGS AND PROJECT SPECIFICATIONS, 13. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL CABLES AND 20. CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL,
<br /> LATEST APPROVED REVISION. OTHER ITEMS REMOVED FROM THE EXISTING FACILITY.ANTENNAS REMOVED SHALL BE RETURNED TO THE OWNER'S ANSI/IEEE AND THE NEC. MASONIC CENTER
<br /> DESIGNATED LOCATION.
<br /> 12. CONTRACTOR SHALL KEEP THE SITE FREE FROM ACCUMULATING WASTE MATERIAL, DEBRIS, AND TRASH AT THE 14, CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED FROM SITE ON 21. WIREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER, DESIGNED TO SWING OPEN
<br /> COMPLETION OF THE WORK. IF NECESSARY, RUBBISH, STUMPS, DEBRIS. STICKS. STONES AND OTHER REFUSE SHALL A DAILY BASIS. DOWNWARDS (WIREMOLD SPECMATE WIREWAY).
<br /> BE REMOVED FROM THE SITE AND DISPOSED OF LEGALLY. 22. SLOTTED WIRING DUCT SHALL BE PVC AND INCLUDE COVER (PANDUIT TYPE E OR EQUAL). 220 OLYMPIC BLVD
<br /> 13. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTIUTIES, WHICH INTERFERE WITH THE EXECUTION 23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON-PERFORATED STRAPS AND HANGERS.
<br /> OF THE WORK, SHALL BE REMOVED AND/OR CAPPED, PLUGGED OR OTHERWISE DISCONTINUED AT POINTS WHICH WILL f EXPLOSIVE DEVICES (i.e. POWDER-ACTUATED) FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED. EVEi i'T' WA 98203
<br /> NOT INTERFERE WITH THE EXECUTION OF HE WORK, SUBJECT TO THE APPROVAL OF CONTRACTOR,TOWER OWNER, 1 CLOSELY FOLLOW THE UNES OF THE STRUCTURE, MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP
<br /> CROWN CASTLE USA INC.,AND/OR LOCAL UTILITIES. CONDUITS IN TIGHT ENVELOPES. CHANGES IN DIRECTION TO ROUTE AROUND OBSTACLES SHALL BE MADE WITH
<br /> 14. THE CONTRACTOR SHALL PROVIDE SITE SIGNAGE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATION FOR SITE CONDUIT OUTLET BODIES. CONDUIT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. PARALLEL AND
<br /> SIGNAGE REQUIRED BY LOCAL JURISDICTION AND SIGNAGE REQUIRED ON INDIVIDUAL PIECES OF EQUIPMENT, ROOMS, CONCRETE, FOUNDATIONS. AND REINFORCING STEEL: PERPENDICULAR TO STRUCTURE WALL AND CEILING UNES. ALL CONDUIT SHALL BE FISHED TO CLEAR EXISTING 761-0t1 MONOPOI,F
<br /> AND SHELTERS. OBSTRUCTIONS. ENDS OF CONDUITS SHALL BE TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO PREVENT
<br /> 15. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE CARRIER'S EQUIPMENT AND TOWER CONCRETE, PLASTER OR DIRT FROM ENTERING. CONDUITS SHALL BE RIGIDLY CLAMPED TO BOXES BY GALVANIZED
<br /> H
<br /> AREAS. 1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITHE ACI 301, ACI 318,ACI 336,ASTM A184, ASTM A185 AND MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED MALLEABLE IRON LOCKNUT ON OUTSIDE AND INSIDE.
<br /> 16. THE SUB GRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE PRIOR TO FINISHED SURFACE THE DESIGN AND CONSTRUCTION SPECIFICATION FOR CAST-IN-PLACE CONCRETE. 24. EQUIPMENT CABINETS, TERMINAL BOXES,JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR
<br /> APPLICATION. 2. UNLESS NOTED OTHERWISE, SOIL BEARING PRESSURE USED FOR DESIGN OF SLABS AND FOUNDATIONS IS ASSUMED EPDXY-COATED SHEET STEEL SHALL MEET OR EXCEED UL 50 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR
<br /> TO BE 1000 psf. LOCATIONS AND NEMA 3R (OR BETTER) FOR EXTERIOR LOCATIONS.
<br /> 17. THE AREAS OF THE OWNERS PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE TOWER. EQUIPMENT OR 3. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (f'c) OF 3000 psi AT 28 DAYS, UNLESS NOTED 25. METAL RECEPTACLE, SWITCH AND DEVICE BOXES SHALL BE GALVANIZED, EPDXY-COATED OR NON-CORRODING;
<br /> DRIVEWAY. SHALL BE GRADED TO A UNIFORM SLOPE,AND STABIUZED TO PREVENT EROSION AS SPECIFIED ON THE OTHERWISE. NO MORE THAN 90 MINUTES SHALL ELAPSE FROM BATCH TIME TO TIME OF PLACEMENT UNLESS SHALL MEET OR EXCEED UL 514A AND NEMA OS 1 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS ISSUED FOR:
<br /> CONSTRUCTION DRAWINGS AND/OR PROJECT SPECIFICATIONS. APPROVED BY THE ENGINEER OF RECORD. TEMPERATURE OF CONCRETE SHALL NOT EXCEED 901 AT TIME OF
<br /> 18. CONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. EROSION CONTROL MEASURES. PLACEMENT. AND WEATHER PROTECTED (W OR BETTER) FOR EXTERIOR LOCATIONS.
<br /> IF REQUIRED DURING CONSTRUCTION, SHALL BE IN CONFORMANCE WITH THE LOCAL GUIDELINES FOR EROSION AND 4. CONCRETE EXPOSED TO FREEZE-THW CYCLES SHALL CONTAIN AIR ENTRAINING ADMIXTURES. AMOUNT OF AIR 26. NONMETALLIC RECEPTACLE, SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2 (NEWEST REVISION) REV DATE DAWN DESCRIPTION DES./QA
<br /> SEDIMENT CONTROL ENTRAINMENT TO BE BASED ON SIZE OF AGGREGATE AND F3 CLASS EXPOSURE (VERY SEVERE). CEMENT USED TO BE AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR BETTER) FOR A 06/21/2019 OF 90%FOR REVIEW JAC
<br /> 19. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS. PAVEMENTS. CURBS, LANDSCAPING AND STRUCTURES.ANY TYPE II PORTLAND CEMENT WITH A MAXIMUM WATER-TO-CEMENT RATIO (W/C) OF 0.45. EXTERIOR LOCATIONS.
<br /> DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION OF OWNER. 5. ALL STEEL REINFORCING SHALL CONFORM TO ASTM A615.ALL WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM 27. THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR CROWN 0 08/20/2019 TB 100%FOR SUBMITTAL JAC
<br /> 20. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL CABLES AND A185. ALL SPLICES SHALL BE CLASS "B"TENSION SPLICES, UNLESS NOTED OTHERWISE.ALL HOOKS SHALL BE CASTLE USA INC. SHABEFLL
<br /> LE COMMENCINGECWORK THE ONAC PH BREAKERS,R DISTRIBUTION AN PANELS.
<br /> OTHER ITEMS REMOVED FROM THE EXISTING FACILITY.ANTENNAS REMOVED SHALL BE RETURNED TO THE OWNER'S STANDARD 90 DEGREE HOOKS, UNLESS NOTED OTHERWISE.YIELD STRENGTH (Fy) OF STANDARD DEFORMED BARS ARE 28. THE ACCORDANCECOAN WITHTOR SHALL PROVIDE NECESSARY TAGGING STANDARDS THE ARLIFEFES AND DISTRIBUTIONPE PANELS IN
<br /> THE APPLICABLE CODES AND TO SAFEGUARD AND PROPERTY.
<br /> DESIGNATED LOCATION. AS FOLLOWS: 29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW "T-MOBILE". - -
<br /> 21. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED FROM SITE ON #4 BARS AND SMALLER 40 ksi 30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED.
<br /> A DAILY BASIS. #5 BARS AND LARGER .60 ksi
<br /> 22. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN MATERIALS. SNOW OR ICE 6. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE
<br /> SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT. ON DRAWINGS: CONDUCTOR COLOR CODE
<br /> CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3" SYSTEM CONDUCTOR COLOR
<br /> CONCRETE EXPOSED TO EARTH OR WEATHER,
<br /> #6 BARS AND LARGER 2" A PHASE BLACK
<br /> #5 BARS AND SMALLER 1-1/2" B PHASE RED
<br /> CONCRETE NOT EXPOSED TO EARTH OR WEATHER: 120/240V, 10
<br /> SLAB AND WALLS .3/4" NEUTRAL WHITE
<br /> BEAMS AND COLUMNS 1-1/2" GROUND GREEN
<br /> 7. A TOOLED EDGE OR A 3/4" CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE. UNLESS NOTED A PHASE BLACK
<br /> OTHERWISE, IN ACCORDANCE WITH ACI 301 SECTION 4.2.4. B PHASE RED �� A. 104
<br /> al
<br /> 120/208V, 30 C PHASE BLUE yP W �T
<br /> GREENFIELD GROUNDING NOTES: NEUTRAL WHITE �O OF IASy/y/O1-
<br /> GROUND GREEN A,
<br /> A PHASE BROWN Q" ,r.. O
<br /> I. ALL GROUND ELECTRODE SYSTEMS (INCLUDING TELECOMMUNICATION, RADIO, LIGHTNING PROTECTION AND AC POWER GES'S) SHALL BE BONDED TOGETHER AT OR BELOW GRADE, BY TWO OR MORE COPPER BONDING CONDUCTORS IN - .....-
<br /> ACCORDANCE WITH THE NEC. ORANGE OR Z
<br /> 2. THE CONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTAL RESISTANCE TO EARTH TESTING (PER IEEE 1100 AND 81) FOR GROUND ELECTRODE SYSTEMS,THE CONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTAL GROUND B PHASE PURPLE /I ell
<br /> ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5 OHMS OR LESS. 277/480V, •� ?s-1 • I
<br /> 30 C PHASE YELLOW
<br /> 3. E CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND R N CONDUIT INSTALLATION TI N ASTOGROUNDINGT E G OU D CO D S ALLA 0 PREVENT ANY LOSS OF CONTINUITY IN THE SYSTEM OR DAMAGE TO THE CONDUIT AND PROVIDE
<br /> TESTING RESULTS. NEUTRAL GREY AA Nj" 1 L9 ,,. '
<br /> 4. METAL CONDUIT AND TRAY SHALL BE
<br /> D
<br /> D
<br /> E
<br /> TED
<br /> G
<br /> 5. THEMETAL POWE
<br /> R E RATS SHALL
<br /> T NOT BE O BTS EQUIPMENT.DASTHE E NECN REQUIRED ELECTRICALLY
<br /> EQUPPMENT GROUND CONDUCTOR. TRANDEDNCOP ER FITTINGS
<br /> ONDUCTORS WITH GREEN INSULATION,ACROSS THE TI SIZED IN ACCORDANCE TY WITH #6 PWT H THE E UNEC, SHAL LL ERFFURNIS FURNISHED DOUNDING TYPE C INSTALLED ONDUIT CLAMPS.
<br /> ITTH DC VOLTAGE POS (+) RED.. / �s`S/ONALR G '
<br /> 6. EACH CABINET FRAME SHALL BE DIRECTLY CONNECTED TO THE MASTER GROUND BAR WITH GREEN INSULATED SUPPLEMENTAL EQUIPMENT GROUND WIRES, #6 STRANDED COPPER OR LARGER FOR INDOOR BTS; #2 BARE SOUD TINNED NEG (-) BLACK.. V
<br /> COPPER FOR OUTDOOR BTS. " SEE NEC 210.5(C)(1)AND (2)
<br /> 7. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED BACK TO BACK CONNECTIONS ON OPPOSITE SIDE OF THE GROUND BUS ARE PERMITTED. "" POLARITY MARKED AT TERMINATION DATE SIGNED:08/20/19
<br /> 8. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND BARS AND THE GROUND RING SHALL BE #2 SOLID TINNED COPPER UNLESS OTHERWISE INDICATED.
<br /> 9. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING CONNECTIONS.
<br /> 10. USE OF 90' BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED WHEN 45' BENDS CAN BE ADEQUATELY SUPPORTED. > Lo1z8 A.Wharton,P.E
<br /> 11. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE. QTY QUANTITY Professional Engin<a License:#51509
<br /> 12. ALL GROUND CONNECTIONS ABOVE GRADE (INTERIOR AND EXTERIOR) SHALL BE FORMED USING HIGH PRESS CRIMPS. ABBREVIATIONS: RECT RECTIFIERANTY Expiration EnginDate e.
<br /> 20
<br /> 13. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS. RBS RADIO BASE STATION
<br /> 14. ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED OR BOLTED TO THE BRIDGE AND THE TOWER GROUND BAR. ANT ANTENNA RET REMOTE ELECTRIC TILT
<br /> 15. APPROVED ANTIOXIDANT COATINGS (i.e. CONDUCTIVE GEL OR PASTE) SHALL BE USED ON ALL COMPRESSION AND BOLTED GROUND CONNECTIONS. (E) EXISTING IT ISAVIOLATION OF LAW FOR ANY PERSON,
<br /> 16. ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL. FIF FACILITY INTERFACE FRAME REDS RADIO FREQUENCY DATA SHEET UNLESS THEY ARE ACTING UNDER THE DIRECTION
<br /> 17. MISCELLANEOUS ELECTRICAL AND NON-ELECTRICAL METAL BOXES, FRAMES AND SUPPORTS SHALL BE BONDED TO THE GROUND RING, IN ACCORDANCE WITH THE NEC. GEN GENERATOR RRH REMOTE RADIO HEAD OF LICENSED PROFESSIONAL ENGINEER,
<br /> RRU REMOTE RADIO UNIT
<br /> #2 BARE SOLID TINNED COPPER GROUND CONDUCTOR. GPS GLOBAL POSITIONING SYSTEM SIAD SMART INTEGRATED DEVICE TO ALTER THIS DOCUMENT.18. BOND ALL METALLIC OBJECTS WITHIN 6 ft OF MAIN GROUND RING (1)WITH
<br /> 19. GROUND CONDUCTORS USED FOR THE FACILITY GROUNDING AND LIGHTNING PROTECTION SYSTEMS SHALL NOT BE ROUTED THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR, SUCH AS METALLIC CONDUITS, METAL GSM GLOBAL SYSTEM FOR MOBILE TMA TOWER MOUNTED AMPLIFIER • •
<br /> SUPPORT CUPS OR SLEEVES THROUGH WALLS OR FLOORS. WHEN IT IS REQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL CONDITIONS. NON-METALLIC MATERIAL SUCH AS PVC CONDUIT SHALL BE USED. LTE LONG TERM EVOLUTION TYP TYPICAL
<br /> WHERE USE OF METAL CONDUIT IS UNAVOIDABLE (i.e., NONMETALLIC CONDUIT PROHIBITED BY LOCAL CODE)THE GROUND CONDUCTOR SHALL BE BONDED TO EACH END OF THE METAL CONDUIT. MGB MASTER GROUND BAR UMTS UNIVERSAL MOBILE TELECOMMUNICATIONS SYSTEM SHEET NUMBER: REVISION:
<br /> 20. ALL GROUNDS THAT TRANSITION FROM BELOW GRADE TO ABOVE GRADE MUST BE #2 BARE SOLID TINNED COPPER IN 3/4"NON-METALLIC, FLEXIBLE CONDUIT FROM 24" BELOW GRADE TO WITHIN 3"TO 6" OF CAD-WELD TERMINATION MW MICROWAVE W.P. WORK POINT
<br /> POINT. THE EXPOSED END OF THE CONDUIT MUST BE SEALED WITH SIUCONE CAULK. (ADD TRANSITIONING GROUND STANDARD DETAIL AS WELL). (N) NEWT-20
<br /> 21. BUILDINGS WHERE THE MAIN GROUNDING CONDUCTORS ARE REQUIRED TO BE ROUTED TO GRADE,THE CONTRACTOR SHALL ROUTE TWO GROUNDING CONDUCTORS FROM THE ROOFTOP. TOWERS.AND WATER TOWERS GROUNDING RING, TO THE NEC NATIONAL ELECTRIC CODE
<br /> EXISTING GROUNDING SYSTEM, THE GROUNDING CONDUCTORS SHALL NOT BE SMALLER THAN 2/0 COPPER. ROOFTOP GROUNDING RING SHALL BE BONDED TO THE EXISTING GROUNDING SYSTEM. THE BUILDING STEEL COLUMNS, UGHTNING (P) PROPOSED
<br /> ` PROTECTION SYSTEM, AND BUILDING MAIN WATER UNE (FERROUS OR NONFERROUS METAL PIPING ONLY). PP POWER PLANT
<br /> a
<br /> 2-I11
<br />
|