<br /> KITS
<br /> KEY NOTES' COAXIAL H2 HOLE COMPRESSIION LUGS
<br /> O EXISTING MONOPOLE TOWER (TYP.)
<br /> LONG BARREL COMPRESSION LUGS
<br /> O EXISTING ANTENNA T-ARM WITH(2)5/16"BOLTS AND LOCK WIT
<br /> H TH#2 AWG INSULATED O
<br /> O NEW ANTENNA STRANDED JUMPER.SUPPLY AND
<br /> INSTALLED BY CONTRACTOR.
<br /> 4O X
<br /> EXISTING MASTER GROUND BAR AT BASE OF 4"BAR
<br /> 12"GALVANIZED#:BB-4 STEEL(PASTEEL BUSS N
<br /> TOWER,NEAR EXIT PORT.FINAL GROUND LEAD TO BY ATC)RT B-412-HDG-VZW,MFR
<br /> EXISTING TOWER GROUND RING. M�
<br /> 0 /ro
<br /> EXISTING COLLECTION GROUND BAR AT EACH
<br /> SECTOR,FILED VERIFY AND REPLACE WITH N., 0 0 0 0 0 0 0 O O 0 0 0 ' 3/8"0 TYP.
<br /> LARGER GROUND BAR AS REQUIRED IF r1
<br /> O INSUFFICIENT GROUND CONNECTION HOLES. 0 - ®O O O O O O O O O O O O- 3/8"0 X 3/4"SLOT TYP.
<br /> FINAL GROUND LEAD,#2AWGSTRANDEDGREEN )4[3[�4 Bnw
<br /> Re
<br /> INSULATED COPPER CONDUCTOR TO EXISTING .-�4 G ,. .
<br /> MASTER GROUND BAR 'I ` ` aldmili
<br /> ANTENNA GROUNDING,#2 AWG STRANDED GREEN 0 ` O O
<br /> INSULATED COPPER CONDUCTOR CADWELD TO / ° . Jr 10" NUNIVERSALBUSSBARMOUNTING
<br /> COLLECTION GROUND BAR © T KIT(PART#:BB-HKU,MFR BY ATC)
<br /> �j/ *. / • I #2/0 AWG INSULATED STRANDED
<br /> EQUIPMENT GROUNDING,#2 AWG GREEN N""f� �,0 !, �_ COPPER CONDUCTOR DOWNLEAD AGE
<br /> INSULATED STRANDED COPPER CONDUCTOR FROM
<br /> O RRU AND OVP WITH MECHANICAL CONNECTION TO '+/ •� \\ 5 3 professional services
<br /> EXISTING COLLECTION GROUND BAR TO MASTER GROUND BAR OR
<br /> e✓ �, OTHER FINAL GROUNDING POINT
<br /> 0 ♦+ 3 COLLECTION GROUND BAR
<br /> GENERAL NOTES /� N 4. • '- •
<br /> • �/ .` a NOT TO SCALE WAVE
<br /> 1. ALL CADWELD CONNECTIONS ON GALVANIZED ArA - /.`\ "` ARCHITECTURE
<br /> SURFACES SHALL BE CLEANED THOROUGHLY AND L ,--i %I •-_. I V`L��\ �' '� �.
<br /> COVERED WITH TWO(2)COATS OF SHERWIN WILLIAMS ._
<br /> GALVANITE PAINT 8350W3 OR EQUAL. I '^ \
<br /> � 1133 164TH STREET SW
<br /> 2. ALL ELECTRICAL CADWELD AND MECHANICAL GROUND � A ' i- `\ 02
<br /> LYNNwooDSUITE?WA98087
<br /> CONNECTIONS WILL HAVE NON-OXIDATION COMPOUND \ OFFICE:(425)7798087
<br /> APPLIED TO CONNECTION. O / Q
<br /> 3. ANY METAL OBJECTS WITHIN 6 FEET OF THE EXTERNAL JAVI�NEWuVAVEARCH.COM
<br /> GROUND RING SHALL BE GROUNDED. / \
<br /> 4. ALL GROUNDING MATERIALS AND CADWELD MOLDS, _, DATE. 5-18-21
<br /> SHOTS,ETC.,SHALL BE FURNISHED AND INSTALLED BY .. �.�� �.,�. ,�i•••• PREPARED BY. YML
<br /> CONTRACTOR,UNLESS OTHERWISE NOTED. / / --
<br /> 5. THE ELECTRICAL CONTRACTOR SHALL FOLLOW --- �iri�IM.. ' �''.•I APPROVED BY. JYS
<br /> la-al ail
<br /> GROUNDING SYSTEM INSTALLED AND TESTING dale
<br /> PROCEDURES AS DESCRIBED IN THE GENERAL '.1� NIPELECTRICAL PROVISIONS. - SUBMITTALS
<br /> NO DATE DESORPTION
<br /> LEGEND
<br /> ITEM DESCRIPTION
<br /> - - NEW MECHANICAL CONNECTION
<br /> --0-- EXISTING MECHANICAL CONNECTION
<br /> -- -- NEW EXOTHERMIC CADWELD CONNECTION
<br /> --IE-- EXISTING EXOTHERMIC CADWELD CONNECTION
<br /> 5-18-21 FINAL PERMIT
<br /> 5-17-21 PRELIMINARY PERMIT
<br /> 1 GROUNDING PLAN AND NOTES NORTH 4 NOT USED
<br /> SCALE' 3/4' • 1'-0' (22x34), 3/8' - 1'-0' (11x17) REGISTEERCETD
<br /> Ilk
<br /> 1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE DESIGN AND 13.CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED. STRANDED CU WIRE WITH 11. US 5-18-?'�
<br /> GREEN,UL I ON. A/THWN 1
<br /> CONSTRUCTION SPECIFICATIONS AND ALL APPLICABLE LOCAL CODES. BACK TO BACK CONNECTIONS ON OPPOSITE SIDES OF THE GROUND BUS ARE INSULATION.SIZE AS 11111 AY Y.?0
<br /> 2. ALL GROUNDING SHALL CONFORM TO THE CURRENT VERIZON WIRELESS STANDARDS. PERMITTED. SPECIFIED 44.,.,, I I STA-- OF WASHNGTON
<br /> 3. CONDUIT ROUTINGS ARE SCHEMATIC.CONTRACTOR SHALL INSTALL CONDUITS SO THAT 14.USE OF 90°BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE PANT SCHEME SPECIFICATIONS:
<br /> ACCESS TO EQUIPMENT IS NOT BLOCKED. AVOIDED WHEN 45°BENDS CAN BE ADEQUATELY SUPPORTED.
<br /> 4. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND 15.GROUND RING SHALL BE LOCATED A MINIMUM OF 24"BELOW GRADE OR 6"MINIMUM PRODUCER(P)
<br /> UNDERGROUND CONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN BELOW THE FROST LINE. TWO-HOLE LUG,BOLTED TO CONNECTS TO WIRELESS EQUIPMENT CABINETS,CABLE ENTRANCE
<br /> THE GROUNDING SYSTEM OR DAMAGE TO THE CONDUIT. 16.INSTALL GROUND CONDUCTORS AND GROUND ROD MINIMUM OF 1-0"FROM GROUND BAR USING 3/8"-16 GROUND BAR(CEGB),MAIN DISTRIBUTION FRAME GROUND BAR SITE
<br /> 5. PREFABRICATED SHELTER WILL BE PROVIDED WITH INTERNAL WRING AND EQUIPMENT EQUIPMENT CONCRETE PAD,SPREAD FOOTING,OR FENCE. x 1 1/4"STAINLESS STEEL (MDFB),AND STANDBY ENGINE-GENERATOR SET FRAME AND OTHER
<br /> INSTALLED.FOR COMPLETE INTERNAL WRING AND ARRANGEMENT REFER TO DRAWINGS 17.EXOTHERMIC WELD GROUND CONNECTION TO FENCE POST:TREAT WITH A COLD HEX HEAD BOLTS AND HARDWARE. " " II
<br /> PRODUCING EQUIPMENT
<br /> PROVIDED BY SHELTER MANUFACTURER. GALVANIZED SPRAY.
<br /> 6. FOR INTERIOR EQUIPMENT LAYOUT AND LOCATION,SEE SHELTER MANUFACTURER'S 18.OBSERVE N.E.C.AND LOCAL UTILITY REQUIREMENTS FOR ELECTRICAL SERVICE ABSORBER(A)
<br /> DRAWINGS AND SPECIFICATION.IN CASE OF CONFLICT THE DRAWINGS GOVERN. GROUNDING 1 CONNECTS TO THE EARTH ELECTRODE SYSTEM INCLUDING CENTRAL SEA-HWY 526
<br /> 7. ALL GROUND CONNECTIONS BELOW GRADE SHALL BE EXOTHERMIC(CADWELD). 19.GROUNDING ATTACHMENT TO TOWER SHALL BE AS PER MANUFACTURER'S P I
<br /> GROUND BAR ON WALL, /� 11 OFFICE GROUND GRID,BUILDING STRUCTURAL GROUND,METALLIC (MOD.SITE _50 L-SU88 1
<br /> 8. ALL GROUND CONNECTIONS ABOVE GRADE(INTERIOR&EXTERIOR)SHALL BE FORMED RECOMMENDATIONS OR AT GROUNDING POINTS PROVIDED(2 MINIMUM) :./O O O O O
<br /> FLOOR OR ON ANTENNA III WATER PIPE SYSTEM,ANTENNA SUPPORTING STRUCTURE GROUND
<br /> USING TWO(2)HIGH PRESS CRIMPS. 20.MAXIMUM RESISTANCE OF THE COMPLETED GROUND SYSTEM SHALL NOT EXCEED 5 TOWER /l-O © SYSTEM,AND ELECTRICAL SERVICE ENTRANCE GROUND
<br /> 9. ALL EXOTHERMIC CONNECTIONS TO THE GROUND RODS SHALL START AT THE TOP& OHMS. O - I 9810 19TH AVE SE
<br /> HAVE A VERTICAL SEPARATION OF 6"FOR EVERY ADDITIONAL CONNECTION. 21.MINIMUM BENDING RADIUS FOR GROUNDING CONDUCTORS IS 8"WHEN BENDING IS 0 • O • �, NON-ISOLATED(N) EVERETT, WA 98208
<br /> 10.ALL GROUNDING CONNECTORS TO BE CLEAN AND FREE OF PAINT AT THEIR MATING NECESSARY.GROUND CONDUCTORS ARE TO BE AS STRAIGHT AS POSSIBLE. CAD WELD WITH#2/0 AWG CONNECTS TO EQUIPMENT NOT IN AN ISOLATED GROUND ZONE(IGZ)
<br /> SURFACES AND INSTALL PER MANUFACTURER'S RECOMMENDATIONS.ALL EXTERIOR 22.NO SPLICES PERMITTED IN GROUND CONDUCTORS.
<br /> GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL. 23.ENSURE ALL MECHANICAL CONNECTORS ARE TORQUED TO THE MANUFACTURER'S SOLID TINNED BARE CU SUCH AS CBN EQUIPMENT FRAME GROUNDS AND DC GROUND
<br /> 11.ALL EXTERIOR GROUND CONDUCTORS SHALL BE#2 AWG TIN PLATED COPPER UNLESS SPECIFIED VALUES. WIRE OR STRANDED CU CONDUCTORS FOR DC POWER SYSTEMS THAT SERVE CBN OR BOTH
<br /> OTHERWISE INDICATED, 24.GROUND BARS SHALL NOT BE FIELD MODIFIED. WIRE WITH GREEN,600V, ' CBN AND IBN EQUIPMENT
<br /> 12.GROUND RODS SHALL BE STAINLESS STEEL OR COPPER CLAD 25.ALL HORIZONTAL FENCE SECTIONS TO BE GROUNDED WITH 8"SINGLE BARREL TO N/TEN N INSULATION SHEET TITLE
<br /> STEEL 5/8"0 10-FT.LONG,AND SHALL BE DRIVEN VERTICALLY WITH THEIR GROUND STRAPS. TO ANTENNA STRUCTURE, I
<br /> ISOLATED(I)
<br /> • TOPS 18"BELOW FINAL GRADE OR 6"BELOW FROST LINE FOR MAXIMUM DEPTH. 26.USE PANT SCHEME FOR LOADING ON MGB AS DISCUSSED IN NSTD 119,33&36. BUILDING,RING GROUND 'GROUND BARS AT BOTTOM OF CONNECTS TO THE SINGLE POINT CONNECTION BAR(SPCB),FOR IBN GROUNDING PLAN,
<br /> OR MGB TOWERS OR MONOPOLES SHALL EQUIPMENT
<br /> USE EXOTHERMIC CONNECTION. DETAILS
<br /> AND NOTES
<br /> SHEET NUMBER
<br /> 2 GENERAL NOTES 5 GROUND BAR CONNECTION DETAIL AND NOTES E-1
<br /> NOT TO SCALE