Laserfiche WebLink
VERETT <br />0 <br />Permit Inspections <br />City of Everett <br />- Rough gas piping ok. <br />4/28/2023 <br />4/28/2023 <br />GAS 03-FINAL <br />JASON <br />APPROVAL <br />eTRAKiT Inspection Request <br />MORRISSEY <br />Notes: <br />4/27/2023 7:27 AM Roger Hascall <br />Morning if possible <br />Contact Name: Roger Ryan Hascall <br />Site Address: 1242 State Ave PMB 200 <br />Phone:4253613488 <br />e-Mail: hascallroger97@gmail.com <br />4/28/2023 <br />4/28/2023 <br />PLUMB 08-FINAL <br />JASON <br />CORRECTION <br />see notes <br />MORRISSEY <br />REQUIRED <br />Notes: <br />4/27/2023 7:26 AM Roger Hascall <br />Morning inspection if possible <br />Contact Name: Roger Ryan Hascall <br />Site Address: 1242 State Ave PMB 200 <br />Phone:4253613488 <br />e-Mail: hascallroger97@gmail.com <br />- Install mixing valve that complies with ASSE 1071 for emergency eyewash per the UPC 416.2 Water Supply Emergency Equipment.- Remove unprimed <br />trap for eyewash, cap trap arm and run drain tailpiece to the floor.- Recess floor drain next to eyewash so strainer is flush or below finished floor.**** <br />Install grab bars for ADA toilet stalls. <br />5/5/2023 <br />5/5/2023 <br />PLUMB 08 FINAL <br />JASON <br />APPRVD-PERMIT <br />eTRAKiT Inspection Request <br />MORRISSEY <br />FINAL <br />Notes: <br />5/4/2023 10:14 AM Roger Hascall <br />Contact Name: Roger Ryan Hascall <br />Site Address: 1242 State Ave PMB 200 <br />Phone:4253613488 <br />e-Mail: hascallroger97@gmail.com <br />I <br />Printed: Monday, 08 May, 2023 2 of 2 rk <br />SUPERION <br />