City of Everett 26 05 33.13 -4 <br /> Inductive Charging Infrastructure for Everett Transit <br /> minimum radii requirements. Provide only equipment specifically designed <br /> for material and size involved. <br /> e. Conceal conduit within finished walls, ceilings, and floors unless otherwise <br /> indicated. Install conduits parallel or perpendicular to building lines. <br /> f. Support conduit within 12 inches of enclosures to which attached. <br /> g. Install duct sealing fittings at accessible locations in accordance with <br /> NFPA 70 and fill them with listed sealing compound. For concealed duct <br /> raceways, install fitting in flush steel box with blank cover plate having <br /> finish similar to that of adjacent plates or surfaces. Install duct sealing <br /> fittings in accordance with NFPA 70. <br /> h. Do not install duct raceways or electrical items on "explosion-relief' walls or <br /> rotating equipment. <br /> i. Cut conduit perpendicular to the length. For conduits metric designator 53 <br /> (trade size 2) and larger, use roll cutter or a guide to make cut straight and <br /> perpendicular to the length. Ream inside of conduit to remove burrs. <br /> j. Install pull wires in empty duct raceways. Provide polypropylene or <br /> monofilament plastic line with not less than 200 lbs. tensile strength. Leave <br /> at least 12 inches of slack at both ends of pull wire. Cap underground duct <br /> raceways designated as spare above grade alongside duct raceways in <br /> use. <br /> k. Install duct raceways square to the enclosure and terminate at enclosures <br /> without hubs with locknuts on both sides of enclosure wall. Install locknuts <br /> hand tight, plus one-quarter turn more. <br /> 1) Termination fittings with shoulders do not require two locknuts. <br /> I. Terminate threaded conduits into threaded hubs or with locknuts on inside <br /> and outside of boxes or cabinets. Install bushings on conduits up to metric <br /> designator 35 (trade size 1-1/4) and insulated throat metal bushings on <br /> metric designator 41 (trade size 1-1/2) and larger conduits terminated with <br /> locknuts. <br /> 3.3 PROTECTION <br /> A. Protect coatings, finishes, and cabinets from damage and deterioration. <br /> 1. Repair damage to galvanized finishes with zinc-rich paint recommended by <br /> manufacturer. <br /> 2. Repair damage to PVC coatings or paint finishes with matching touchup coating <br /> recommended by manufacturer. <br /> END OF SECTION 260533.13 <br /> 26 05 33.13 -4 CONDUITS FOR ELECTRICAL SYSTEMS <br />