Laserfiche WebLink
City of Everett 26 05 73.19 -2 <br /> Inductive Charging Infrastructure for Everett Transit <br /> B. Study Submittals: <br /> 1. Submit the following after approval of system protective devices submittals. <br /> Submittals must be in digital form: <br /> a. Arc-flash study input data, including completed computer program input <br /> data sheets. <br /> b. Submit study report for action prior to receiving final approval of distribution <br /> equipment submittals. If formal completion of studies will cause delay in <br /> equipment manufacturing, obtain approval from Architect for preliminary <br /> submittal of sufficient study data to ensure that selection of devices and <br /> associated characteristics is satisfactory. <br /> c. Revised one-line diagram, reflecting field investigation results and results <br /> of arc-flash study. <br /> 1.4 INFORMATIONAL SUBMITTALS <br /> A. Product Certificates: For arc-flash hazard analysis software, certifying compliance with <br /> IEEE 1584 and NFPA 70E. <br /> 1.5 QUALITY ASSURANCE <br /> A. Study must be performed using commercially developed and distributed software <br /> designed specifically for power system analysis. <br /> B. Software algorithms must comply with requirements of standards and guides specified <br /> in this Section. <br /> C. Manual calculations are unacceptable. <br /> 1.6 REGULATORY AGENCY APPROVALS <br /> A. Submittals for arc-flash hazard analysis requiring approval by authorities having <br /> jurisdiction must be signed and sealed by qualified electrical professional engineer <br /> responsible for their preparation. <br /> B. Submittals for arc-flash hazard analysis require action by Architect prior to submitting <br /> for approval by authorities having jurisdiction. <br /> PART 2 - PRODUCTS <br /> 2.1 COMPUTER SOFTWARE <br /> A. Comply with IEEE 1584 and NFPA 70E. <br /> B. Analytical features of device coordination study computer software program must have <br /> capability to calculate "mandatory," "very desirable," and "desirable" features as listed <br /> in IEEE 399. <br /> 26 05 73.19 - 2 ARC-FLASH HA <br /> ZARD ANALYSIS <br />