• <br /> Architectural <br /> 1. See Site Plan Proposal on Sheet A.100. It appears that the structure is within 5 feet of the property <br /> line. The exterior walls on the North side of the building should have fire-rated construction per <br /> IRC Table R302.1(1). <br /> See Sheet A.103—Proposal Floor Plan updated with new wall key&Sheet i4.301 Detail Wall <br /> Detail for typical 1 hr Fire Proof Wall Construction. <br /> 2. Continuing with the previous comment,the South walls located in the laundry room do not appear to <br /> have the required fire separation distance to the existing dwelling and should have fire-rated <br /> construction per IRC Table R302.1(1). <br /> See Sheet A.103—Proposal FloorPlan updated with new wall key&Sheet .301 Detail Wall <br /> Detail for typical l hr Fire Proof Wall Construction. <br /> 3. See Site Plan Proposal on Sheet A.100.The roof eaves project approximately 2 feet from the property <br /> line on the North side of the structure per the site plan. In this location,one-hour construction is <br /> required on the underside of the eaves(see alternatives and exceptions provided). In most solutions, <br /> the soffit venting will not be permitted in the eaves in these locations and the roof venting should be <br /> relocated to an approved location.Table R302.1(1) <br /> See Sheet A.103—Proposal RoofPlan updated with new detail/key&Sheet A.301 Detail 51 Detail <br /> for typical 1 hr Fire ProofEave Construction. <br /> 4. The plans should specify the heating equipment type, location,and the minimum equipment <br /> efficiency per the project energy credits. WA State Energy Code Table R406.2 <br /> See Sheet A.103—Proposal FloorPlan updated with new Mini Split location.And Check addendum to <br /> WA Energy code Prescriptive points <br /> 5. See Wall Section 3 on Sheet A.301. It appears that the floor joists and rim board rest on the masonry <br /> exterior foundation wall and framing members are less than 8 inches from the exposed ground. Plans <br /> should include a note to specify preservative-treated wood or naturally durable framing where required <br /> per Section R317.1 (2). <br /> See Sheet A.301— Updated Detail 3 Wall Section <br /> 6. Continuing with the previous comment,fasteners for preservative-treated wood should be specified as <br /> hot-dipped,zinc-coated galvanized steel,stainless steel, silicon bronze or copper.R317.3.1 <br /> See Sheet A.301— Updated Detail 3 Wall Section <br /> 7. See Wall section 3 on Sheet A.301. R-38 ceiling insulation is specified on the plans. Plans should be <br /> updated to show R-49 insulation per WSEC Table R402.1.1. Note that R-38 is allowed for single rafter or <br /> joist-vaulted ceilings if the full insulation depth extends over the top plate of the exterior wall. <br /> See Sheet A.301— Updated Detail Wall Section <br /> 8. Continuing with the previous comment,floor insulation should be specified as R-38 per selected energy <br /> credits. <br /> See Sheet A.301— Updated Detail 3 Wall Section <br />