C. Sales and Service
<br />Project: City of Everett Public Works, 1 000kW
<br />Quotation: Q-154012-20230131-0959
<br />January 31, 2023
<br />Prepared by
<br />Zach Schulte
<br />(206)794-9801
<br />zach.t.schulte@cummins.com
<br />We are pleased to provide you this quotation based on your inquiry.
<br />Item Description
<br />1 DQFAD, Commercial Diesel Generator Set, 1000kW Standby 60Hz
<br />U.S. EPA, Stationary Emergency Application
<br />1 000DQFAD, Diesel Genset, 60Hz, 1 000kW
<br />Duty Rating -Standby Power (ESP)
<br />Emission Certification, EPA, Tier 2, NSPS Cl Stationary Emergency
<br />Listing -UL 2200
<br />Cert-Seismic, IBC2000, IBC2003, IBC2006, IBC2009, IBC2011
<br />Voltage -277/480, 3 Phase, Wye, 4 Wire
<br />Alternator -60Hz, 3 Phase, Wye, Extended Range, 125/105C
<br />Steel Sound Attenuated Level 2 Enclosure, with Exhaust System
<br />Enclosure Color -Green, Steel
<br />Vibration Isolators -Earthquake Certified
<br />Cooling Air Outlet -Horizontal, Sound Attenuated
<br />Fuel Tank -Sub Base, 1500 Gallon, UL 142 Compliant
<br />Compliance -Fuel Tank, Michigan
<br />Listing, ULC -S601 -07
<br />Alarm -High Fuel Level, External
<br />Fuel Water Separator
<br />Spill/Fill Box -Fuel with OFPV
<br />Vent Extensions -Fuel Tank, 6 Inch Diameter
<br />Fuel Tank Connection -Dual Stub Up
<br />Control Mounting -Left Facing
<br />' PowerCommand 3.3 Controller, Paralleling Capable
<br />LCD Control Display
<br />Relays -Genset Status, User Configured
<br />Alarm -Audible, Engine Shutdown
<br />Stop Switch -Emergency, Externally Mounted
<br />Signals -Auxiliary, 8 lnputs/8 Outputs
<br />Relay -Alarm Shutdown
<br />Control Display Language -English
<br />Circuit Breaker or Entrance Box or Terminal Box -Right Only
<br />Terminal Box-Low Voltage, Left-None
<br />Circuit Breaker -1600A, Right, 3P, UL 600, I EC 415, UL Service Entrance 100%
<br />Load Connections-None
<br />Bottom Entry, Right
<br />Indication -Ground Fault, Terminal Box (or) Circuit Breaker Box -Right
<br />Circuit Breaker Accessory, 24 Volts DC Trip, Aux and Trip Contacts, Right Side
<br />Circuit Breaker Lugs -Mechanical, Right Side
<br />Engine Air Cleaner -Normal Duty
<br />External Battery Charger -12 Amp, Regulated
<br />Engine Cooling -Radiator, Enhanced High Ambient Air Temperature, Ship Fitted
<br />Shutdown -Low Coolant Level
<br />Sight Glass -Coolant Level
<br />Coolant Heater -208/240/480 Volts AC, 40F Minimum Ambient Temperature
<br />Genset Warranty - 2 Years Base
<br />Literature -English
<br />Packinq -None, Base Mounted Housinq
<br />2 Vibration Isolator, Seismic-3400Ibs, 1.1 0" Deflection, 31 00lbs/in Spring Rate
<br />3 Annunciator-panel mount with enclosure (RS485)
<br />Quotation: Q-154012-20230131-0959
<br />Qty
<br />1
<br />10
<br />1
|