SCOPE OF WORK GOVERNING CODES SYSTEM RATING Lumio TO INSTALL A ROOF MOUNTED SOLAR PHOTOVOLTAIC SYSTEM AT THE OWNER RESIDENCE
<br /> LOCATED AT 710 91ST PL SE, EVERETT, WA 98208, USA. 2018 INTERNATIONAL FIRE CODE 6.000 kWDC
<br /> THE POWER GENERATED BY THE PV SYSTEM WILL BE INTERCONNECTED WITH THE UTILITY 2018 INTERNATIONAL BUILDING CODE 4.500 kWAC SMART ENERGY TODAY
<br /> GRID THROUGH THE EXISTING ELECTRICAL SERVICE EQUIPMENT. 2018 INTERNATIONAL RESIDENTIAL CODE (SET)
<br /> THE PV SYSTEM DOES NOT INCLUDE STORAGE BATTERIES. 2020 NATIONAL ELECTRICAL CODE SHEET INDEX 1550 DIGITAL DR,LEHI,UT
<br /> WASHINGTON ADMINISTRATIVE CODE (WAC) 84043,USA
<br /> EQUIPMENT SUMMARY WIRING AND CONDUIT NOTES PV1 COVER PAGE
<br /> 15 Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES • ALL CONDUIT SIZES AND TYPES SHALL BE LISTED FOR ITS PURPOSE AND PV2 SITE PLAN
<br /> APPROVAL FOR THE SITE APPLICATIONS PV3 ROOF PLAN
<br /> 15 ENPHASE IQ8PLUS-72-2-US (240V) MICROINVERTERS • ALL PV CABLES AND HOMERUN WIRES BE#10AWG*USE-2, PV WIRE, OR
<br /> GENERAL NOTES PROPRIETARY SOLAR CABLING SPECIFIED BY MFR, OR EQUIVALENT; ROUTED TO PV4 STRING LAYOUT& BOM
<br /> • THESE CONSTRUCTION DOCUMENTS HAVE BEEN BASED ON FIELD INSPECTIONS AND SOURCE CIRCUIT COMBINER BOXES AS REQUIRED PV5-PV6 ATTACHMENT DETAILS
<br /> OTHER INFORMATION AVAILABLE AT THE TIME. ACTUAL FIELD CONDITIONS MAY REQUIRE • ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE PV7 ELECTRICAL LINE &CALCS. SYSTEM INFO
<br /> MODIFICATIONS IN CONSTRUCTION DETAILS. DERATED ACCORDING TO AS PER LATEST NEC CODE. (15)Q CELLS
<br /> PV8 SPECIFICATIONS& NOTES Q.PEAK DUO BILK ML-G10+
<br /> • ARCHITECT HAS NOT BEEN RETAINED TO SUPERVISE ANY CONSTRUCTION OR • EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 90°C RATED, WET AND UV (40OW)
<br /> INSTALLATION OF ANY EQUIPMENT AT SITE. RESISTANT,AND UL LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE PV9-PV10 SIGNAGE (15)ENPHASE
<br /> • CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, EQUIPMENT, TOOLS, OBTAINS ALL USED TO PROTECT WIRE FROM SHARP EDGES PV11 JOB SAFETY PLAN IQ8PLUS-72-2-US(240V)
<br /> PERMITS, LICENSES AND PAY ALL REQUIRED FEES AND COMPLETE INSTALLATION. • PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 PV12-PV21 EQUIPMENT SPECIFICATIONS DC SYSTEM SIZE:6.000 kWDC
<br /> • CONTRACTOR HAS THE FULL RESPONSIBILITY TO CHECK AND VERIFY ALL DIMENSIONS INSULATED, 90°C RATED, WET AND UV RESISTANT, RATED FOR 1000V PER NEC AC SYSTEM SIZE:4.500 kWAC
<br /> AND EXISTING CONDITIONS. ANY DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER 2017
<br /> BEFORE PROCEEDING WITH THE WORK. ANY WORK STARTED BEFORE CONSULTATION AND • 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER PROJECTSITE
<br /> ACCEPTANCE BY THE ENGINEER SHALL BE THE SOLE RESPONSIBILITY OF THE VOLTAGE TO GROUND MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE
<br /> CONTRACTOR AND SHALL BE SUBJECT TO CORRECTION BY THEM WITHOUT ADDITIONAL MEANS REVISIONS
<br /> COMPENSATION. • ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION , DESCRIPTION DATE I REV
<br /> • DAMAGE CAUSED TO THE EXISTING STRUCTURE, PIPES, DUCTS, WINDOWS, WALL, FLOORS, y `
<br /> ETC. SHALL BE REPAIRED TO THE ORIGINAL CONDITION OR REPLACED BY THE VOLTAGE DROP LIMITED TO 2% • 1
<br /> CONTRACTOR AT NO ADDITIONAL COST. • AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1- BLACK, 1 .
<br /> • THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE PROPER INSTALLATION AND PHASE B OR L2- RED, PHASE C OR L3- BLUE, NEUTRAL-WHITE/GRAY
<br /> COMPLETION OF THE WORK WITH APPROVED MATERIALS. • VOLTAGE DROP LIMITED TO 2% t'
<br /> • NO CHANGES ARE TO BE MADE WITHOUT THE CONSULTATION AND APPROVAL OF THE • AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE AOR L1-BLACK, 1" `� PROJECT NAME&ADDRESS
<br /> ARCHITECT. PHASE B OR L2- RED, PHASE C OR L3- BLUE, NEUTRAL-WHITE/GRAY
<br /> • CONTRACTOR SHALL OBTAIN BULDING PERMIT. NO WORK TO START UNLESS BUILDING
<br /> PERMIT IS PROPERLY DISPLAYED. Q
<br /> • ALL WORKMANSHIP AND MATERIALS SHALL BE OF FIRST QUALITY AND IN COMPLIANCE �-�� U)
<br /> WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, THE DEPARTMENT OF ,.;.
<br /> ENVIRONMENTAL PROTECTION AND ALL PERTINENT AGENCIES. 00
<br /> • IT 1 S ESSENTIAL THAT ALL WORK PROCEED WITH THE MAXIMUM COOPERATION OF ALL CN
<br /> PARTIES AND WITH MINIMUM INTERFERENCE TO THE OCCUPANTS WITHIN THE BUILDING. 00
<br /> THE OWNER'S DIRECTIONS IN THIS REGARD SHALL BE FULLY COMPLIED WITH. • Q p
<br /> • ALL EXPOSED PLUMBING, HVAC, ELECTRICAL DUCTWORK, PIPING AND CONDUITS ARE TO J o
<br /> Lu
<br /> BE PAINTED BY GENERAL CONTRACTOR. IE Luo
<br /> ,.; ()
<br /> • THE CONTRACTOR SHALL PERFORM THE WORK IN STRICT CONFORMANCE WITH THE I '; =_ _ -a ;•Terrra of'Jae P.eoort = 'rz: err, C) z w m
<br /> LOCAL LAWS, REGULATIONS AND THE NATIONAL ELECTRIC CODE. U) W LO
<br /> • THE CONTRACTOR SHALL OBTAIN ALL PERMITS, APPROVALS, AFFIDAVITS, CERTIFICATIONS, HOUSE PHOTO SCALE:NTS LLI 0 W
<br /> co
<br /> ETC.AND PAY ALL FEES AS REQUIRED BY THE LOCAL AUTHORITIES. PROJECT SITE a: W W o
<br /> • CONTRACTORS SHALL OBTAIN FIRE CERTIF. UPON COMPLETION OF WORK.
<br /> G z
<br /> SIP J _
<br /> ELECTRICAL NOTES Fred Meyer a �
<br /> • ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. -
<br /> • ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET -- Q
<br /> S26
<br /> ENVIRONMENT. _,
<br /> • WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY
<br /> TO,AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.
<br /> • WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL ?
<br /> COMPLY WITH NEC 110.26. b CASCADE VIEU'!
<br /> • WHERE SIZES OF JUNCTION BOXES, RACEWAYS,AND CONDUITS ARE NOT SPECIFIED, THE DATE:9/7/2022
<br /> CONTRACTOR SHALL SIZE THEM ACCORDINGLY. _
<br /> SHEET NAME
<br /> • ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE.
<br /> • MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE WinCo Foods COVER PAGE
<br /> SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURERS INSTRUCTION.
<br /> • MODULE SUPPORT RAIL SHALL BE BONDED TO THE MODULE
<br /> COStCO Wholesale� SHEET SIZE
<br /> ANSI B
<br /> Go ale 11" X 17"
<br /> %a0 Data Terms of Ilse . Report a map error
<br /> SHEET NUMBER
<br /> VICINITY MAP SCALE:NTS
<br /> PV-1