Laserfiche WebLink
Permit Inspections <br /> p <br /> VERETT City of Everett <br /> WASHINGTON <br /> BLDG 09-FIRE CORRECTION <br /> 12/14/2020 12/14/2020 CAULKING/BLOCKIN KURT KECK REQUIRED L 5 Corridor electrical boxes <br /> G <br /> Notes: <br /> Have spoken with contractor regarding the electrical boxes on level 5 in the 1 hour corridor. <br /> All electrical boxes in these corridors need to be rated or protected for 1 hour rating.See 2015 IBC 714.4.1.Please complete and recall for inspection. <br /> 12/15/2020 12/15/2020 BLDG 08-FRAMING KURT KECK PARTIAL L6 elevator front <br /> APPROVAL <br /> Notes: <br /> BLDG 09-FIRE CORRECTION <br /> 12/28/2020 12/29/2020 CAULKING/BLOCKIN KURT KECK REQUIRED not ready <br /> G <br /> Notes: <br /> Inspection called for fire caulking of North stair well and L4,5,6,corridor lid. <br /> BLDG 09-FIRE PARTIAL <br /> 1/5/2021 1/5/2021 STOPPING/BLOCKIN KURT KECK APPROVAL L4,5,6 corridor lid,north stairwell <br /> G <br /> Notes: <br /> BLDG 12- PARTIAL <br /> 1/8/2021 1/8/2021 INSULATION KURT KECK APPROVAL north stairwell as noted <br /> Notes: <br /> 1/6/2021 11:11 AM Craig Sanderson <br /> Please inspect north stairway insulation <br /> Contact Name:Craig Sanderson <br /> Site Address:2721 WETMORE AVE <br /> Phone:4255080413 <br /> e-Mail:craig.sanderson@skotdal.com <br /> (1/8/2021 3:06 PM KMK) <br /> Recall for framing/fire rated assembly-south wall <br /> BLDG 09-FIRE CORRECTION <br /> 1/12/2021 1/12/2021 STOPPING/BLOCKIN KURT KECK REQUIRED L2 soffits Fire caulking not complete <br /> G <br /> Notes: <br /> 1/11/2021 8:26 AM Craig Sanderson <br /> 2nd floor soffits <br /> Contact Name:Craig Sanderson <br /> Site Address:2721 WETMORE AVE <br /> Phone:4255080413 <br /> e-Mail:craig.sanderson@skotdal.com <br /> (1/12/2021 3:18 PM KMK) <br /> For electrical see(12/14/2020 4:28 PM SKB) <br /> Soffits in units. <br /> •. k <br /> Printed:Tuesday, 13 June,2023 4 of 12) '4' <br /> SUPERION <br />