Permit Insp ections <br /> VERETT p City of Everett <br /> WASHINGTON <br /> BLDG 09-FIRE CORRECTION <br /> 2/19/2021 2/19/2021 STOPPING/BLOCKIN KURT KECK REQUIRED Rooms 101 and 102 See notes <br /> G <br /> Notes: <br /> 2/18/2021 4:03 PM Craig Sanderson <br /> 101&102 high fire block and insulation <br /> Lobby high. <br /> Contact Name:Craig Sanderson <br /> Site Address:2721 WETMORE AVE <br /> Phone:4255080413 <br /> e-Mail:craig.sanderson@skotdal.com <br /> (2/19/2021 2:06 PM KMK) <br /> 1.Call for electrical inspections above grid ceiling <br /> 2.Room 102:Fire caulk 2 hour through penetrations above grid on north wall bathroom.(Adjacent to corridor). <br /> 3.Room 101 and 102: Finish fire caulking all 1 hour wall assemblies above grid. <br /> Recall for inspection <br /> BLDG 09-FIRE CORRECTION <br /> 2/25/2021 2/25/2021 STOPPING/BLOCKIN KURT KECK REQUIRED room 101,102 <br /> G <br /> Notes: <br /> 2/23/2021 3:23 PM Craig Sanderson <br /> Units 101&102 <br /> Contact Name:Craig Sanderson <br /> Site Address:2721 WETMORE AVE <br /> Phone:4255080413 <br /> e-Mail:craig.sanderson@skotdal.com <br /> (2/25/2021 1:17 PM KMK) <br /> Fire taping does not work around pipe penetrations.Remove tape and use fire caulking at these locations in room 101 and 102 above grid.Fire taping at <br /> seams is OK but not at through penetrations. <br /> BLDG 09-FIRE PARTIAL <br /> 3/3/2021 3/3/2021 STOPPING/BLOCKIN KURT KECK APPROVAL 101,102 <br /> G <br /> Notes: <br /> 3/2/2021 7:50 AM Craig Sanderson <br /> Fire caulk 101,102 <br /> Contact Name:Craig Sanderson <br /> Site Address:2721 WETMORE AVE <br /> Phone:4255080413 <br /> e-Mail:craig.sanderson@skotdal.com <br /> Printed:Tuesday, 13 June,2023 6 of 12 SUPERION <br />