Laserfiche WebLink
t <br /> 0 • <br /> Comment Notice <br /> Permit Application#B2205-018 <br /> Building Review(Reviewer Drew Martin By: dmartin@everettwa.gov) <br /> Intake Review Comments: <br /> General: <br /> • The submitted drawings appear to include prior unpermitted work, including but not limited to the rear <br /> addition, garage conversion to habitable space, adding carport and porch roofs, and additional <br /> modifications to the interior of the building. The existing conditions shown in the drawings are not <br /> consistent with the available City of Everett and Snohomish County records. A copy of the old SnoCo <br /> Field Assessor record is attached; note that the SnoCo records only provide a record of the building <br /> condition for the purpose of assessing taxes and do not substantiate a permitted condition. The drawings <br /> are also not consistent with photography available on Google Earth and the real-estate website <br /> Redfin.com. The drawings should be revised to show all previous unpermitted work as new work; all <br /> new work is required to comply with the current code requirements. Alternatively, the drawings should <br /> show the removal of unpermitted work and restoration of the building to its previous legally permitted <br /> condition. See IRC Sections R102.7.1, R105.1, and R113.1. <br /> Response:See revised plans for the additions. <br /> • The project includes an addition that was partially constructed under Permit No. C0802-003. The work <br /> was not completed, and therefore the addition is not a legal addition. The construction drawing are <br /> required to show the addition as new construction. The addition must comply with the current code <br /> requirements for new construction. <br /> Response:See revised plans for the additions. <br /> A chitectural: <br /> • Landings should be specified outside all exterior doors. See IRC Section R311.3. <br /> Response:Plans revised to show landings. <br /> • The carport is within the 5-foot fire-separation distance and required fire-rated construction. See 1RC <br /> Table R302.1(1). <br /> V Response:Existingcarport will be demolished. <br /> p <br /> • The minimum opening dimensions and area,and maximum bottom sill opening height of the floor,should <br /> be specified. See IRC Section R310. <br /> /Response:Plans show minimum openings and area, and max sill height of the floor for new and existing <br /> windows. <br />