My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
5732 EAST DR 2023-06-29
>
Address Records
>
EAST DR
>
5732
>
5732 EAST DR 2023-06-29
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
6/29/2023 11:10:04 AM
Creation date
6/29/2023 6:16:06 AM
Metadata
Fields
Template:
Address Document
Street Name
EAST DR
Street Number
5732
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
14
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Step 4 - Refrigerant Piping <br /> Table 6- Piping and Refrigerant Information <br /> SIZE 12K 9K 12 18K 24K 30K 38K <br /> (115V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V (208/230V) <br /> Min.Piping Length Ft(m) 10(3) 10(3) 10(3) 10(3) 10(3) 10(3) 10(3) <br /> Standard Ft(m) 25(7.5) 25(7.5) 25(7.5) 25(7.5) 25(7.5) 25(7.5) 25(7.5) <br /> Piping Length <br /> Max.Outdoor indoor Ft(m) 32(10) 32(10) 32(10) 65(20) 65(20) 82(25) 82(25) <br /> height difference <br /> Max.Piping Length <br /> with no additional Ft(m) 26(8) 26(8) 26(8) 26(8) 26(8) 26(8) 26(8) <br /> refrigerant charge <br /> Max.Piping Length Ft(m) 82(25) 82(25) 82(25) 98(30) 164(50) 164(50) 164(50) <br /> Piping <br /> Additional refrigerant charge <br /> (between Standard-Max Oz/ft(g/m) 0.16(15) 0.16(15) 0.16(15) 0.16(15) 0.32(30) 0.32(30) 0.32(30) <br /> piping length) <br /> in 1/2 3/8 1/2 1/2 5/8 5/8 5/8 <br /> Gas Pipe <br /> (mm) 12.7 9.52 12.7 12.7 16 16 16 <br /> in 1/4 1/4 1/4 1/4 3/8 3/8 3/8 <br /> Liquid Pipe <br /> (mm) 6.35 6.35 6.35 6.35 9.52 9.52 9.52 <br /> Refrigerant Type - R41 OA R41 OA R41 OA R41 OA R41 OA R41 OA R41 OA <br /> Refrigerant <br /> Charge Amount (kg) 2.76(125) 3.31(1.5) 3.31(1.5) 4.30(l.95) 5.73(2.60) 6.06(2.75) 7.50(3.40) <br /> IMPORTANT: Both refrigerant lines must be insulated <br /> separately.Use refrigeration grade tubing ONLY.No other <br /> type of tubing may be used.Use of other types of tubing • <br /> will void the manufacturer's warranty. <br /> • The minimum refrigerant line length between the indoor and All field piping must be completed by a licensed technician and <br /> outdoor unit is 10 ft.(3m), must comply with the local and national regulations. <br /> • When paired with Ductless indoor units,size the line sets based on When the system is installed in a small room,measures must be <br /> the connection size of the indoor unit unless specified. taken to prevent the refrigerant concentration in the room from <br /> • When paired with conventional or multi-family fan coils,size the exceeding the safety limit in the event of refrigerant leakage.If the <br /> line sets based on the liquid and gas connection size of the outdoor refrigerant leaks and its concentration exceeds its proper limit, <br /> unit;a field supplied reducer may be required. hazards due to lack of oxygen may result. <br /> • All outdoor units have an electronic expansion valve to manage the When installing the refrigeration system,ensure that air,dust, <br /> refrigerant flow of the fan coil connected. moisture or foreign substances do not enter the refrigerant circuit. <br /> • Do not open the service valves or remove the protective caps from Contamination in the system may cause poor operating capacity, <br /> the tubing ends until all connections are made. <br /> • Bend the tubing with bending tools to avoid kinks and flat spots. high pressure in the refrigeration cycle,explosion or injury. <br /> Ventilate the area immediately if there is refrigerant leakage <br /> • Keep the tubing free of dirt,sand,moisture,and other during the installation. <br /> contaminants to avoid damaging the refrigerant system. Leaked refrigerant gas is hazardous.Ensure there is no refrigerant <br /> • Avoid sags in the suction line to prevent the formation of oil traps. leakage after completing the installation work. <br /> • Insulate each tube with a minimum 3/8-in.(10 mm)wall thermal <br /> pipe insulation.Inserting the tubing into the insulation before <br /> making the connections will save time and improve installation , <br /> quality. <br /> DO NOT install the connecting pipe until both the indoor and <br /> outdoor units have been installed. <br /> Insulate both the gas and liquid piping to prevent condensation. <br /> 10 Specifications subject to change without notice. 38MAR-04SI <br />
The URL can be used to link to this page
Your browser does not support the video tag.