Laserfiche WebLink
SC-1 <br />SC-1 <br />Date: 12/1/2022 <br />DIC�G Made By: SDT <br />Project: SVDP HVAC <br />Description: Design Criteria <br />Design Criteria <br />Code: <br />Seismic: <br />Latitude = 47.9394022 North <br />Longitude =-122.1998505 West <br />Spectral Response Acceleration, Ss & S1 = <br />Spectral Response Acceleration, Sds & Sd1 = <br />Soil Site Class, Fa & Fv = <br />Seismic Design Category, SDC <br />Amplification Factor, a = <br />Response Modification Factor, R = <br />Wind: <br />Exposure = B <br />Basic Wind Speed = 110 mph <br />Topographical Terrain = Flat <br />Kzt = 1.00 <br />Dead Loads: <br />HVAC = 120lbs (Max) <br />HP = 220lbs (Max) <br />Soils: <br />2018 International Building Code <br />1.298 <br />1.038 <br />1.2 <br />D <br />2.5 <br />6.0 <br />& 0.459 <br />Foundation Design Parameters Per Geotechnnical Report No. 21-0499 By Geotest Dated June 10, 2021 <br />Soil Bearing = 3, 000 psf <br />Active Soil Pressure = 35 pcf <br />Passive Soil Pressure = 350 pcf <br />IBC Soil Site Classification = C <br />Frost Depth = 18 inches <br />