Laserfiche WebLink
SC-4 <br />SC-4 <br />Date: 11/22/22 <br />Designed By: SDT <br />Project: SVDP HVAC UH-1, UH-2, ERV-1, and ERV-2 <br />Description: Sesimic Load of Non -Structural Component <br />Fp = 0 4aR�DSI,roW,ro (1 + 2 nl (ASCE 13.3-1) <br />hP) <br />0.3SDSIpWp <_ Fp <_ 1.6SDSIpWp (13.3-2 & 13.3-3) <br />Sd, = <br />1.038 <br />�V�RSTCASE1OAD1J\U <br />Component Weight, Wp = <br />120 <br />Ibs <br />Importance Factor, Ip = <br />1.0 <br />(Section 13.1.3) <br />Amplification Factor, ap = <br />2.5 <br />(Table 13.5-1 or 13.6-1) <br />Response Modification Factor, RP = <br />6.0 <br />Component Height in Structure, z = <br />17 <br />ft <br />Average Roof Height, h = <br />17 <br />ft <br />z/h = <br />1 <br />(need not exceed 1.0) <br />Fp = <br />62 <br />Ibs (13.3-1) <br />Fp >_ <br />37 <br />Ibs (13.3-2) <br />Fp <_ <br />199 <br />Ibs (13.3-3) <br />Design Force, Fp = 62 Ibs (LRFD) <br />Design Vertical Force, FPV = ± 25 Ibs (LRFD) <br />