GENERAL NOTES CONTRACTOR <br /> SITE NOTES GROUNDING NOTES INTERCONNECTION NOTES <br /> 2.1.1 A LADDER WILL BE IN PLACE FOR INSPECTION IN ACCORDANCE 2.5.1 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR 2.7.1 LOAD SIDE INTERCONNECTION SHALL BE IN <br /> WITH OSHA REGULATIONS. THEIR PURPOSE, AND GROUNDING DEVICES EXPOSED TO THE ACCORDANCE WITH NEC 705.12. <br /> 2.1.2 THE PV MODULES ARE CONSIDERED NON-COMMUSTIBLE AND THIS ELEMENTS SHALL BE RATED FOR SUCH USE. 2.7.2 THE SUM OF THE UTILITY OCPD AND INVERTER ELECTRICAL SYSTEMS <br /> SYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGE 2.5.2 PV EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE CONTINUOUS OUTPUT MAY NOT EXCEED 120 PERCENT OF SOLUTIONS INC <br /> BATTERIES. WITH NEC 690.43 AND NEC TABLE 250.122. BUSBAR RATING PER NEC 705.12. <br /> 2.1.3 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY 2.5.3 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND 2.7.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) PO BOX 16452, SEATTLE, <br /> PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. ENCLOSURES CONSIDERED GROUNDED IN ACCORDANCE WITH OUTPUT CIRCUIT CURRENT AND THE RATING OF THE WASHINGTON, 98116 <br /> 2.1.4 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING NEC 250.134 AND 250.136(A). OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL PHONE -(206)963-2999 <br /> AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED IN 2.5.4 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED IN NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE LIC. NO. - EC ELECTSS902JN <br /> ACCORDANCE WITH SECTION NEC 110.26. ACCORDANCE WITH NEC 690.45 AND INVERTER BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE <br /> 2.1.5 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MANUFACTURER'S INSTALLATION PRACTICES LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY <br /> MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED 2.5.5 EACH MODULE WILL BE GROUNDED AS SHOWN IN SOURCE OCPD IN ACCORDANCE WITH NEC 705.12. <br /> MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. 2.7.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT <br /> SERVES TO PROTECT THE BUILDING OR STRUCTURE. 2.5.6 THE GROUNDING CONNECTION TO A MODULE SHALL BE COMBINER PANEL, TOTAL RATING OF ALL OVERCURRENT <br /> ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT PROTECTION DEVICES SHALL NOT EXCEED AMPACITY OF <br /> EQUIPMENT LOCATIONS INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. BUSBAR. HOWEVER, THE MAIN OVERCURRENT PROTECTION <br /> 2.2.1 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS IN 2.5.7 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, DEVICE MAY BE EXCLUDED IN ACCORDANCE WITH NEC <br /> ACCORDANCE WITH NEC 110.26. SHALL BE COLORED GREEN OR MARKED GREEN IF#4 AWG OR 705.12. <br /> 2.2.2 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE LARGER PER NEC 250.119 2.7.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) IN <br /> RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY 2.5.8 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC ACCORDANCE WITH NEC 705.12. <br /> NEC 690.31 (A),(C)AND NEC TABLES 310.15 (13)(2)(A)AND 310.15 (B)(3)(C). 690.47 AND NEC 250.50 THROUGH 250.106. IF EXISTING SYSTEM IS 2.7.6 SUPPLY SIDE TAP INTERCONNECTION IN ACCORDANCE <br /> 2.2.3 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE WITH TO NEC 705.12 WITH SERVICE ENTRANCE <br /> MODULES IN ACCORDANCE WITH NEC 690.34. SYSTEM PROVIDED IN ACCORDANCE WITH NEC 250, NEC 690.47 CONDUCTORS IN ACCORDANCE WITH NEC 230.42. PROJECT NAME &ADDRESS <br /> 2.2.4 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE AND THE AHJ. 2.7.7 BACKFEEDING BREAKER FOR ELECTRIC POWER ELIZABETH CALSYN <br /> INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 2.5.9 GROUND-FAULT DETECTION SHALL COMPLY WITH NEC SOURCES OUTPUT IS EXEMPT FROM ADDITIONAL <br /> 2.2.5 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED 690.41(13)(1)AND (2)TO REDUCE FIRE HAZARDS FASTENING PER NEC 705.12. 216 MADISON ST, <br /> PERSONNEL IN ACCORDANCE WITH NEC APPLICABLE CODES. EVERETT, WA 98203 <br /> 2.2.6 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED DISCONNECTION AND OVERCURRENT PROTECTION NOTES APN #: 00392000000109 <br /> FOR OUTDOOR USAGE WHEN APPROPRIATE. 2.6.1 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT <br /> WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING AHJ: CITY OF EVERETT <br /> STRUCTURAL NOTES ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED "LINE UTILITY: PUD <br /> 2.3.1 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED IN SIDE" (TYPICALLY THE UPPER TERMINALS). <br /> ACCORDANCE WITH THE CODE-COMPLIANT INSTALLATION MANUAL. 2.6.2 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY SYSTEM DETAILS <br /> TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH DC SIZE:7.665 KW DC-(STC) <br /> RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER 2.6.3 PV SYSTEM CIRCUITS INSTALLED ON OR IN HABITABLE AC SIZE:6.090 KW <br /> (21)URECO FBM40OM0MFG-BB <br /> EDGE OF THE ARRAY/SUBARRAY, IN ACCORDANCE WITH RAIL BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION TO (21)ENPHASE IQ8PLUS-72-2-US[240V] <br /> MANUFACTURER'S INSTALLATION PRACTICES. REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN <br /> 2.3.2 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S ACCORDANCE WITH 690.12 <br /> SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & 2.6.4 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO REVISIONS <br /> SEALED PER LOCAL REQUIREMENTS. NEC 690.8, 690.9, AND 240. REV DESCRIPTION DATE <br /> 2.3.3 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED 2.6.5 INVERTER ON-GRID BRANCHES SHALL BE CONNECTED TO A <br /> AND SEALED W/APPROVED CHEMICAL SEALANT PER CODE BY A SINGLE BREAKER OR GROUPED FUSE DISCONNECT(S) IN <br /> LICENSED CONTRACTOR. ACCORDANCE WITH NEC 110.3(B). <br /> 2.3.4 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO 2.6.6 IF REQUIRED BY THE AHJ, SYSTEM WILL INCLUDE <br /> GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING ARC-FAULT CIRCUIT PROTECTION IN ACCORDANCE WITH NEC <br /> MANUFACTURER OR PROFESSIONAL ENGINEERING GUIDANCE. 690.11 AND UL1699B. <br /> 2.3.5 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL <br /> BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. SHEET TITLE <br /> WIRING & CONDUIT NOTES NOTES <br /> 2.4.1 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR <br /> THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON <br /> MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT DRAWN DATE 4/15/2023 <br /> UP-SIZING. DRAWN BY PCAD <br /> 2.4.2 CONDUCTORS SIZED IN ACCORDANCE WITH THE NEC <br /> 2.4.3 AC CONDUCTORS TO BE COLORED OR MARKED PER NEC SHEET NUMBER <br /> 2.4.4 LISTED OR LABELED EQUIPMENT SHALL BE INSTALLED AND USED <br /> IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING PV-05 <br /> OR LABELING PER NEC <br />