Laserfiche WebLink
TABLE II—ELECTRICAL DATA—MODEL 542E—SIZES 024 THRU 042 <br /> MODEL 542E <br /> SIZE 024 030 036 042 <br /> SERIES A A A A — <br /> Unit Volts-Phase 601-14 208-230-1 208-230-1 208-230-1 208/230-3 230-1 208/230-3 <br /> Operating Voltage Range 197-253 197-253 197-253 187-253 207-253 187-253 <br /> Total Unit Amps 16.7 22.7 23.9 14.8 28.7 21.0 <br /> Max Branch Circuit Fuse Size Amps 30 45 45 25 50 40 <br /> Unit Ampacity for Wire Sizing 20.2 27.5 29.2 17.8 34.9 25.2 <br /> Minimum Wire Size(AWG)* 10 10 10 12 8 10 <br /> Maximum Wire Length(Ft)* 115 85 80 95 112 1 107 <br /> TABLE III—ELECTRICAL DATA—MODELS 542EO48, 542DO60, & 542EO60 <br /> MODEL 542E 542E 542D&542E <br /> SIZE 048 060 060 <br /> SERIES A A A <br /> Unit Volts—Phase 601-14 230-1 208/230-3 460-3 230-1 208/230-3 460-3 <br /> Operating Voltage Range 207-253 187-253 1 414-506 207-253 187-253 414-506 <br /> Total Unit Amps 31.9 22.4 10.9 40.9 26.1 13.7 <br /> Max Branch Circuit Fuse Size Amps 60 45 20 60 50 25 <br /> Unit Ampacity for Wire Sizing 38.9 27.1 13.2 49.8 31.3 16.4 <br /> Minimum Wire Size(AWG)* 8 10 14 6 8 12 <br /> Maximum Wire Length(Ft)* 101 100 181 1 123 137 1 229 <br /> *Only use copper wire for field connections to unit.Wire size is based on 60 or 75°C copper conductor at 86°F(30°C)ambient tempera- <br /> ture and ampacity shown in table.If other than 60 or 75°C copper conductor is used,if ambient temperature is above 86°F,or if voltage <br /> drop of wire exceeds 2%of unit rated voltage,determine wire size from ampacity shown and the National Electrical Code.Wire lengths <br /> shown are measured one way along the wire path between unit and service panel for minimum voltage drop. <br /> USE SPREADER BARS TO PROTECT UNIT <br /> SPREADER BARS: <br /> (2) 2x4x82 WITH 1-1/2 DEEP USE SPREADER BARS TO PROTECT UNIT <br /> 90°NOTCHES EACH END <br /> (2)2 x 4 x 40 WITH 1-1/2 DEEP CHAIN SPREADER BARS: <br /> 90°NOTCHES EACH END (2)2 x 4 x A WITH 1-1/2 DEEP <br /> 90*NOTCHES EACH END <br /> PACKAGED UNIT (2) 2 x 4 x B WITH 1-1/2 DEEP CHAIN <br /> / 90°NOTCHES EACHHEEND <br /> SIZES A B / PACKAGED UNIT <br /> / 024,030 8 036 / -- <br /> 042,048 B 060 8282 40 0 <br /> I / <br /> I <br /> I � <br /> I I I <br /> I l 1 1 <br /> PLENUM <br /> DO NOT LIFT LOCATE CHAIN <br /> AT PLENUM CHAIN RETAINER THRU CHANNEL <br /> (PART OF UNIT) <br /> LOCATE CHAIN UNDER UNIT AND LOCATE CHAIN AGAINST LOCATE CHAINS <br /> ONE INCH FROM PLENUM FOR CHAIN RETAINER FOR A79147 THRU CHANNELS A79148 <br /> PROPER FIT ON CURB AND PLATFORM PROPER BALANCE <br /> Figure 7-542DO60 Suggested Rigging Figure 8-542E Suggested Rigging <br /> Prime the trap with water and check the condensate line for openings on the side of the unit. See Figure 3 for connection <br /> leaks. sizes and locations.See Figures 10 and 11 for illustrations of <br /> CAUTION-- Do not undersize the condensate drain line. typical installations. <br /> Flanges are provided on the 542D supply- and return-air <br /> During the heating defrost cycle, defrost water from the <br /> openings on the bottom of the unit.See Figure 4 for connec- <br /> melting ice on the outdoor coil flows through the slots in the <br /> heat pump base directly below the outdoor coil.If a field- <br /> sup-plied drain pan is to be used to catch the defrost water,this NOTE: The minimum installation requirements of the duct <br /> pan should be at least 2 inches high and extend at least 2 in- system must be in accordance with the standards of the Na- <br /> ches beyond the width and length of the unit. tional Fire Protection Association for installation of air con- <br /> If the installation requires draining the condensate and/or ditioning and ventilating systems of other than residence <br /> defrost away from the unit, connect a minimum of 7/8-inch type,NFPA No.90;or residence type,NFPA No.9013;and/or <br /> OD copper tubing, 3/4-inch galvanized pipe, or 7/8-inch local codes and ordinances. <br /> plastic pipe.The drainage lines should pitch downward at a CAUTION:When the duct system fastening holes are being <br /> slope of at least 1 inch in every 10 feet of horizontal run. drilled into the 542E side instead of the unit duct flanges <br /> Both condensate and defrost water can be drained directly provided, use care to avoid puncturing the coil tubes. <br /> onto the roof in rooftop installations where permitted or The following criteria must be followed when selecting, siz- <br /> onto a gravel apron in ground-level installations. When a ing, and installing ductwork: <br /> gravel apron is being used, it should extend at least 24 in- 1. When electric heater is installed,a minimum clearance <br /> ches around the mounting pad to ensure proper drainage. of one inch to combustible materials must be main- <br /> III. DUCT CONNECTIONS tained for the first 36 inches of duct. <br /> Flanges are provided on the 542E supply- and return-air 2. It is recommended that flexible connectors be used be- <br /> -A— <br />