Laserfiche WebLink
CONCRETE FOUNDATIONS AND REINFORCING STEEL: <br />1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301, ACI 318, ACI 336, ASTM A184, ASTM A185 AND THE DESIGN <br />AND CONSTRUCTION SPECIFICATION FOR CAST -IN -PLACE CONCRETE. <br />2. UNLESS NOTED OTHERWISE, SOIL BEARING PRESSURE USED FOR DESIGN OF SLABS AND FOUNDATIONS IS ASSUMED TO BE 1000 <br />psf. <br />3. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (f'c) OF 3000 psi AT 28 DAYS, UNLESS NOTED OTHERWISE. NO <br />MORE THAN 90 MINUTES SHALL ELAPSE FROM BATCH TIME TO TIME OF PLACEMENT UNLESS APPROVED BY THE ENGINEER OF RECORD. <br />TEMPERATURE OF CONCRETE SHALL NOT EXCEED 90`f AT TIME OF PLACEMENT. <br />4. CONCRETE EXPOSED TO FREEZE -THAW CYCLES SHALL CONTAIN AIR ENTRAINING ADMIXTURES. AMOUNT OF AIR ENTRAINMENT TO BE <br />BASED ON SIZE OF AGGREGATE AND F3 CLASS EXPOSURE (VERY SEVERE). CEMENT USED TO BE TYPE II PORTLAND CEMENT WITH A <br />MAXIMUM WATER -TO -CEMENT RATIO (W/C) OF 0.45. <br />5. ALL STEEL REINFORCING SHALL CONFORM TO ASTM A615. ALL WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM A185. ALL <br />SPLICES SHALL BE CLASS "B" TENSION SPLICES, UNLESS NOTED OTHERWISE. ALL HOOKS SHALL BE STANDARD 90 DEGREE HOOKS, <br />UNLESS NOTED OTHERWISE. YIELD STRENGTH (Fy) OF STANDARD DEFORMED BARS ARE AS FOLLOWS: <br />#4 BARS AND SMALLER 40 ksi <br />#5 BARS AND LARGER 60 ksi <br />6. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE ON <br />DRAWINGS: <br />• CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3" <br />• CONCRETE EXPOSED TO EARTH OR WEATHER: <br />• #6 BARS AND LARGER 2" <br />• #5 BARS AND SMALLER 1-1/2" <br />• CONCRETE NOT EXPOSED TO EARTH OR WEATHER: <br />• SLAB AND WALLS 3/4" <br />• BEAMS AND COLUMNS 1-1/2" <br />7. A TOOLED EDGE OR A 3/4" CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE, UNLESS NOTED OTHERWISE, <br />IN ACCORDANCE WITH ACI 301 SECTION 4.2.4. <br />ELECTRICAL INSTALLATION NOTES: <br />ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, NEC AND ALL APPLICABLE <br />FEDERAL, STATE, AND LOCAL CODES/ORDINANCES. <br />2. CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT IS NOT BLOCKED <br />AND TRIP HAZARDS ARE ELIMINATED. <br />3. WIRING, RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC. <br />4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC. <br />4.1. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF APPROVAL, AND SHALL CONFORM TO REQUIREMENT OF <br />THE NATIONAL ELECTRICAL CODE. <br />4.2. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN THE SHORT CIRCUIT <br />CURRENT TO WHICH THEY ARE SUBJECTED, 22,000 AIC MINIMUM. VERIFY AVAILABLE SHORT CIRCUIT CURRENT DOES NOT EXCEED THE <br />RATING OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE 110.24 NEC OR THE MOST CURRENT ADOPTED CODE PRE THE <br />GOVERNING JURISDICTION. <br />5. EACH END OF EVERY POWER PHASE CONDUCTOR, GROUNDING CONDUCTOR, AND TELCO CONDUCTOR OR CABLE SHALL BE <br />LABELED WITH COLOR -CODED INSULATION OR ELECTRICAL TAPE (3M BRAND, 1/2" PLASTIC ELECTRICAL TAPE WITH UV PROTECTION, OR <br />EQUAL). THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA. <br />6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE, PHASE <br />CONFIGURATION, WIRE CONFIGURATION, POWER OR AMPACITY RATING AND BRANCH CIRCUIT ID NUMBERS (i.e. PANEL BOARD AND CIRCUIT <br />ID'S). <br />7. PANEL BOARDS (ID NUMBERS) SHALL BE CLEARLY LABELED WITH PLASTIC LABELS. <br />8. TIE WRAPS ARE NOT ALLOWED. <br />9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR (#14 OR LARGER) <br />WITH TYPE THHW. THWN. THWN-2. XHHW. XHHW-2. THW. THW-2. RHW. OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED. <br />10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOR (#6 OR LARGER) WITH <br />TYPE THHW, THWN, THWN-2, XHHW, XHILI THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED. <br />11. POWER AND CONTROL WIRING IN FLEXIBLE CORD SHALL BE MULTI -CONDUCTOR, TYPE SCOW CORD (#14 OR LARGER) UNLESS <br />OTHERWISE SPECIFIED. <br />12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL BE MULTI -CONDUCTOR, TYPE TC CABLE (#14 OR LARGER), WITH <br />TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED. <br />13. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP -STYLE, COMPRESSION WIRE LUGS AND WIRE NUTS BY THOMAS AND <br />BETTS (OR EQUAL). LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION NOT LESS THAN 75. C (90` C IF AVAILABLE). <br />14. RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, ILL, ANSI/IEEE AND <br />NEC. <br />15. ELECTRICAL METALLIC TUBING (EMT), INTERMEDIATE METAL CONDUIT (IMC), OR RIGID METAL CONDUIT (RMC) SHALL BE USED FOR <br />EXPOSED INDOOR LOCATIONS. <br />16. ELECTRICAL METALLIC TUBING (EMT) OR METAL -CLAD CABLE (MC) SHALL BE USED FOR CONCEALED INDOOR LOCATIONS. <br />17. SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL ELBOWS/90s AND ALL APPROVED ABOVE <br />GRADE PVC CONDUIT. <br />18. LIQUID -TIGHT FLEXIBLE METALLIC CONDUIT (LIQUID-TITE FLEX) SHALL BE USED INDOORS AND OUTDOORS, WHERE VIBRATION <br />OCCURS OR FLEXIBILITY IS NEEDED. <br />19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION -TYPE AND APPROVED FOR THE LOCATION USED. SET <br />SCREW FITTINGS ARE NOT ACCEPTABLE. <br />20. CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE AND THE <br />NEC. <br />21. WIREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER, DESIGNED TO SWING OPEN DOWNWARDS <br />(WIREMOLD SPECMATE WIREWAY). <br />22. SLOTTED WIRING DUCT SHALL BE PVC AND INCLUDE COVER (PANDUIT TYPE E OR EQUAL). <br />23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON -PERFORATED STRAPS AND HANGERS. EXPLOSIVE <br />DEVICES (i.e. POWDER -ACTUATED) FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED. CLOSELY FOLLOW THE LINES OF <br />THE STRUCTURE, MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES. CHANGES IN DIRECTION TO <br />ROUTE AROUND OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BODIES. CONDUIT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE <br />MANNER. PARALLEL AND PERPENDICULAR TO STRUCTURE WALL AND CEILING LINES. ALL CONDUIT SHALL BE FISHED TO CLEAR <br />OBSTRUCTIONS. ENDS OF CONDUITS SHALL BE TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO PREVENT CONCRETE, PLASTER OR DIRT <br />FROM ENTERING. CONDUITS SHALL BE RIGIDLY CLAMPED TO BOXES BY GALVANIZED MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED <br />MALLEABLE IRON LOCKNUT ON OUTSIDE AND INSIDE. <br />24. EQUIPMENT CABINETS, TERMINAL BOXES, JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR EPDXY -COATED SHEET <br />STEEL. SHALL MEET OR EXCEED UL 50 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND NEMA 3 (OR BETTER) FOR <br />EXTERIOR LOCATIONS. <br />25. METAL RECEPTACLE, SWITCH AND DEVICE BOXES SHALL BE GALVANIZED, EPDXY -COATED OR NON -CORRODING; SHALL MEET OR <br />EXCEED UL 514A AND NEMA OS 1 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WE OR <br />BETTER) FOR EXTERIOR LOCATIONS. <br />26. NONMETALLIC RECEPTACLE, SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2 (NEWEST REVISION) AND BE RATED <br />NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR BETTER) FOR EXTERIOR LOCATIONS. <br />27. THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR DISH WIRELESS, L.L.C., AND <br />TOWER OWNER BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS. <br />28. THE CONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS, CABLES AND DISTRIBUTION PANELS IN ACCORDANCE <br />WITH THE APPLICABLE CODES AND STANDARDS TO SAFEGUARD LIFE AND PROPERTY. <br />29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW "DISH WIRELESS, L.L.C." <br />30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED <br />d....sh_ <br />5701 SOUTH SANTA FIE DRIVE <br />LITTLETON, CO 80120 <br />I <br />TOWER IN P OFESSIONALS <br />326 0 D. A IGH, NC <br />27603 0 I (9 ) 61-6351 <br />M. <br />�2 N <br />Co <br />50257 <br />.� �'fiGIST�s� <br />' 0 <br />NAL <br />March 8, 2022 <br />IT IS A VIOLATION OF LAW FOR ANY PERSON, <br />UNLESS THEY ARE ACTING UNDER THE <br />DIRECTION OF A LICENSED PROFESSIONAL <br />ENGINEER, TO ALTER THIS DOCUMENT. <br />DRAWN BY: <br />CHECKED BY:APPROVED <br />BY: <br />CDK I <br />CP <br />I CP <br />REDS REV #: TBD <br />CONSTRUCTION <br />DOCUMENTS <br />SUBMITTALS <br />REV <br />DATE <br />DESCRIPTION <br />,1 <br />08-05-21 <br />PRELIMINARY <br />B <br />12-21-21 <br />PRELIMINARY <br />C <br />01-18-22 <br />PRELIMINARY <br />0 <br />03-08-22 <br />CONSTRUCTION <br />A&E PROJECT NUMBER <br />147003 <br />DISH WIRELESS, L.L.C. <br />PROJECT INFORMATION <br />SESEA00361C <br />9610 19TH AVENUE SE <br />EVERETT, WA 98208 <br />SHEET TITLE <br />GENERAL NOTES <br />SHEET NUMBER <br />GN-4 <br />