Laserfiche WebLink
76:5/41/6/20�2Am' * Page <br /> City of Everett <br /> INSPECTION ACTIVITY REPORT <br /> 9/28/2021 9/28/2021 ELEC 06-ROUGH SKB PARTIAL APPR see notes (9/28/2021 10:15 AM SKB) <br /> IN Install AFCI breakers so that we can tell if <br /> there are enough circuits and that all <br /> required AFCI and GFCI protection devices <br /> are installed. <br /> 11/23/2021 11/23/2021 ELEC 06-ROUGH SKB NO ACCESS (11/23/2021 2:25 PM SKB) <br /> IN 2 pm <br /> 11/30/2021 11/30/2021 ELEC 06-ROUGH SKB APPROVAL as noted for final (11/30/2021 11:34 AM SKB) <br /> IN OK lower level from kitchen west Rough in <br /> verify number of circuits in downstairs <br /> • kitchen at final. <br /> 12/13/2021 12/13/2021 ELEC 09-FINAL SKB CANCELLED (12/13/2021 7:48 AM SKB) <br /> Owner called and asked for his inspection <br /> to be moved to next day. <br /> 12/14/2021 12/14/2021 ELEC 09-FINAL SKB OTHER (12/14/2021 11:12 AM SKB) <br /> Nothing to inspect at this time. <br /> 6/29/2022 6/29/2022 ELEC 10-FINAL SKB CORRECTION Mebet Tadege(206)288-3564 <br /> mebettadege@yahoo.com <br /> (6/29/2022 12:06 PM SKB) <br /> Receptacles must be tamper resistant type <br /> in the new room change areas. All <br /> receptacles must be GFCI protected in the <br /> laundry area.The dryer receptacle must be a <br /> four wire and GFCI protected at the <br /> breaker. Blank off the junction box next to <br /> the furnace. <br /> 7/5/2022 7/5/2022 ELEC 10-FINAL MCB APPRVD-PERN Mebet Tadege(206)288-3564 <br /> mebettadege@yahoo.com <br /> INSP12 <br /> ?III <br />