Laserfiche WebLink
n I Y <br /> SIMPSON Anchor Designer Company: Date: 10/27/2021 <br /> Engineer: MPM Page 5/5 <br /> Software Project: <br /> Version 2.7.6990.13 Address: <br /> Phone: <br /> 11.Results <br /> 11.Interaction of Tensile and Shear Forces(Sec.D.7)? <br /> Tension Factored Load,N.(lb) Design Strength,ON fib) Ratio Status <br /> Steel 600 11700 0.05 Pass <br /> Concrete breakout 600 1520 0.39 Pass(Governs) <br /> Adhesive 600 2127 0.28 Pass <br /> SET-XP w/#4 A615 Gr.60 Reber with hef=5.000 inch meets the selected design criteria. <br /> 12.Warnings <br /> -When cracked concrete is selected,concrete compressive strength used in concrete breakout strength in tension,adhesive strength in tension <br /> and concrete pryout strength in shear for SET-XP adhesive anchor is limited to 2,500 psi per ICC-ES ESR-2508 Section 5,3. <br /> -Concrete breakout strength in shear has not been evaluated against applied shear load(s)per designer option,Refer to ACl 318 Section <br /> 17.3.2.1 for conditions where calculations of the concrete breakout strength may not be required. <br /> -Per designer input,the tensile component of the strength-level earthquake force applied to anchors does not exceed 20 percent of the total <br /> factored anchor tensile force associated with the same load combination.Therefore the ductility requirements of ACI 318 17,2.3.4.2 for tension <br /> need not be satisfied—designer to verify. <br /> -Per designer input,the shear component of the strength-level earthquake force applied to anchors does not exceed 20 percent of the total <br /> factored anchor shear force associated with the same load combination.Therefore the ductility requirements of ACl 318 17.2.3.5.2 for shear <br /> need not be satisfied—designer to verify. <br /> -Designer must exercise own judgement to determine if this design is suitable. <br /> -Refer to manufacturer's product literature for hole cleaning and installation instructions. <br /> Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. <br /> , 5955 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com <br />