Permit#: FA2306-012
<br /> Site Address: 90580th St SW EVERETT evrsrrr
<br /> Applicant Seacom Cabling Inc """'"°'°"
<br /> Application Date:06/06/2023 Everett Fire Dept.Permit Review
<br /> Status:Approved
<br /> Description: Fire Alarm TI Fo r m o Fuji
<br /> Reviewed By:KBrown i8l�2
<br /> Review Status: 1st Review by City&Peer Reviewers 06/viewed3 11:45:39
<br /> Review Date: 06/07/2023 AM
<br /> Everett FireDept.Notes: ire arm yS em
<br /> (NFPA 72) General notes:
<br /> •See Attached Fire Alarm System 905 80th St SW
<br /> Acceptance Test Checklist. 1.Scope of work:This project shall include the expansion of an existing
<br /> Everett, WA 98203 addressable fire alarm system. 1242 State Ave,SuiteMB#285
<br /> 24 hour Battery Test-At the time of the Marysville,WA70
<br /> inspection/test provide proof verifying that the I 2.These drawings are diagrammatic.Refer t0 the architectural drawings for 360-939-1455
<br /> panel has been operating on secondary
<br /> power(battery)for 24 hours.No other I exact dimensions.
<br /> wwwfire-nw.com
<br /> problems shall be indicated on the panel. 3.Installation shall comply with NEC,NFPA 72 and all other applicable codes as
<br /> I Z
<br /> •NFPA 72 Report-NFPA 72 Record of I required by the local authority having jurisdiction. Z
<br /> Completion(not req'd for flow/tamper C
<br /> systems). 4.Wiring depicted on these plans is schematic,actual wire locations may differ
<br /> L_____-_-_-______.J from these plans.Wiring shall be performed as actual building construction _J (D
<br /> conditions allow and t0 minimize penetrations through area separation walls O N
<br /> Fire Alarm Wire List and fire rated walls.The use of a raceway is permitted as long as no 110 V or t^ 00.
<br /> higher voltage cables are in the same raceway. Y n E
<br /> Notification-Notification M O
<br /> V1 Wire Path Label Legend ( O
<br /> NON PLENUM RATED:FPLR S.Final ratings shall be maintained for all penetrations through fire rated \`// 0 3 0 U"j U
<br /> GENESIS CABLE) C' !`N
<br /> Chr.Position Character Purpose construction. Z N 00(V
<br /> NOM OD=0.164" #1 quantity of the same circuit 6.Power for all fire alarm panels and fire alarm power supplies must be provided > O
<br /> #2 Circuit type(see circuit legend) by a dedicated AC branch circuit.The location of the branch circuit breaker ` l \ W a < LL ro
<br /> shall be permanently identified at the control unit. Where a circuit breaker is V r tU
<br /> A 8 the disconnecting means,an approved breaker locking device shall be installed. O L N
<br /> Z
<br /> For fire alarm and/or signaling systems,the circuit disconnecting means shall Z = N f0
<br /> have a red marking. m d 00 U
<br /> E O >
<br /> Symbol Legend 7.Power limited in non-power limited circuit wiring must remain separated in v (h W M
<br /> cabinet.All power limited circuit wiring must remain at least a quarter inch
<br /> away from any non-power limited circuit wiring.Furthermore,all power limited
<br /> and non-power limited circuit wiring must enter and exit the cabinet through
<br /> SYMBOL DESCRIPTION MANUFACTURER PART Ndifferent knockouts and or separate conduits.
<br /> UMBER QUANTITY BACKBOX REQUIREMENTS d
<br /> 8.When utilizing class A circuits,separate outgoing and return conductors of
<br /> class a circuits by a minimum of 12 inches were run vertically and 48 inches
<br /> FFA;wl INTELLIKNIGHT,FACP,6-FLEXPUT,VO CIRCUITS,1.4 LOOP EXISTING SILENT KNIGHT 5820 XL 1 NA were run horizontally.
<br /> ISI 9.All fire alarm cabling shall be acceptable to the fire alarm equipment REVISION 1:
<br /> LN HORN/STROBE,2 WIRE,M-C,RED,CEILING SYSTEM SENSOR PC2R 4 4X4 DEEP manufacturer for the intended purpose. 06/05/23
<br /> c 10.Smoke detector shall not be installed until after construction cleanup is REVISION 2:
<br /> HORN/STROBE,2 WIRE,M-C,RED,WALL EXISTING SYSTEM SENSOR P2R 12 4X4 DEEP completed and final.
<br /> 11.Locate smoke detectors a minimum of 3 feet from mechanical supplies. REVISION 3:
<br /> Wall-mounted smoke detectors shall be located a minimum of 4 inches and a
<br /> �•4. K O 4.7K SILENT KNIGHT EOL-4.7 2 NA maximum of 12 inches from ceilings.
<br /> 12.Provide synchronization of all visual notification appliance circuits.
<br /> 13.Upon completion of the fire alarm system installation and programming,the
<br /> installing contractor shall perform final testing of the entire system,per all
<br /> applicable codes,and shall coordinate and perform a final fire alarm system
<br /> inspection.
<br /> 14.Provide offsite monitoring as required by the international fire code,section
<br /> Circuit Calculations Panel:FACP Card:00 907.6.6 and the local authority having jurisdiction. _
<br /> Terminal Voltage:20.4 V:DC Amperage:3.0000 A . .....
<br /> Cable:1412 SOLJKT FPLR 1M RL RED #14 16.Installing contractors show physically label all initiating devices and
<br /> Calculations based on Lump sum Length. notification appliance circuit end of lines(when wiring class B).These labels
<br /> Design Criteria:Ambient temperature:167°F Max.operating voltage drop:18% shall be in place prior to start up in testing. LL M E
<br /> Circuit Description Type Total Len P2R,116CD,207.000 mA EOL-4.7 Total Amps Gauge V Drop% V Drop Resistance Max Len }� ?y N
<br /> SIG1 Notification 41T-0 6 1 11 1242.0000 mA 1 #141 15.63 13.1876V 1 2.6 Ohms 1 481'-0 C/) (n Go
<br /> Circuit Calculations Panel:FACP Card:00 Circuit:SIG2 O N U)
<br /> Circuit Name:SIG2yam.+ E
<br /> Circuit Type:Notification Terminal Voltage:23.8 V:DC Amperage:3.0000 A CO
<br /> CD
<br /> L
<br /> Cable:14/2 SOL JKT FPLR 1M RL RED #14 E N (l3
<br /> Calculations based on Running Total Length. CO OR SMOKE DETECTOR THERMAL DETECTOR 6"FROM CEILING. O C N Q
<br /> Design Criteria:Ambient temperature:167 OF Max.operating voltage drop:18% M t j
<br /> Device Part No Appliance Desc Distance Current Voltage Voltage Drop CEILING HORN/STROBE IIa�nn
<br /> 5820 XL Panel 23.8 V WALL HORN/STROBE
<br /> 001 P2R HORN/STROBE,2 WIRE,MC,RED,WALL,116CD 77'-0 207.0000 mA 22.8213 V (0.9787 V)
<br /> 002 P2R HORN/STROBE,2 WIRE,MC,RED,WALL,115CD 801-0 207.0000 mA 21.9062 V (0.9151 V)
<br /> P02R HORN/STROBE,2 WIRE,MC,RED,CEILING,115CD 20'-0 207.0000 mA 21.7029 V (0.2034 V) FACP BPS
<br /> PC2R HORN/STROBE,2 WIRE,MC,RED,CEILING,115CD 89'-0 207.0000 mA 20.9111 V (0.7918V) FAA F❑
<br /> FIRE NAC 8D"-96"
<br /> 003 P2R HORNISTROBE,2 WIRE,MC,RED,WALL,115CD 18'-0 207.0000 mA 20.7662 V (0.1449V) ALARM POWER
<br /> 004 P2R HORN/STROBE,2 WIRE,MC,RED,WALL,115CD 88-0 207.0000 mA 20.2069 V (0.5592 V)
<br /> PC2R HORN/STROBE,2 WIRE,MC,RED,CEILING,115CD 19'-0 207.0000 mA 20.1103 V (0.0966 V) 6,p„ CONTROL 6,D., SUPPLY 5'0" 42"FRONT ACCESS
<br /> PC2R HORN/STROBE,2 WIRE,MC,RED,CEILING,115CD OW-01 207.0000 mA 19.771 V (0.3394 V) PANEL 48"SIDE ACCESS
<br /> 006 P2R HORNISTROBE,2 WIRE,MC,RED,WALL,115CD 20'1 207.0000 mA 10.7202 V (0.0608 V)
<br /> 006 P2R HORNISTROBE,2 WIRE,MC,RED,WALL,11SCD 80'-0 207.0000 mA 10.6185 V (0.1017V)
<br /> EOL�.7 EOL 4.7K 11-0 0.0000 mA 19.6185V (0 V)
<br /> 587-01 2070.0000 mA m
<br /> Total Current:2070.0000 mA Equipment Mounting Elevations
<br /> (Total VDrop Percent:17.57%) Total Voltage Drop;4.1815V
<br /> (TYPICAL) N I C E T o
<br /> Jesse
<br /> 2377.'avel
<br /> 09
<br /> Fire Ala IV
<br /> DESIGNED BY:
<br /> JH
<br /> REVIEWED BY:
<br /> Fire Alarm System J"
<br /> DATE:
<br /> 06/05/23
<br /> JOB NUMBER:
<br /> 230602-1
<br /> SHEET NUMBER:
<br /> FA-1.0