Laserfiche WebLink
AWARNING <br />ELECTRICAL SHOCK HAZARD <br />TERMINALS ON LINE AND LOAD <br />SIDES MAY BE ENERGIZED IN <br />THE OPEN POSITION <br />INVERTER(S), AC DISCONNECT(S), AC <br />COMBINER PANEL (IF APPLICABLE). <br />PER CODE(S): NEC 2020: NEC 706.15 <br />(C)(4) & NEC 690.13(B) <br />LABEL LOCATION: <br />AC DISCONNECT <br />NEC 690.13(B) <br />A WARNING DUAL POWER SOURCE <br />SECOND SOURCE IS PHOTOVOLTAIC SYSTEM <br />i A-1 i ---- <br />POINT OF INTERCONNECTION <br />PRODUCTION METER <br />NEC 705.12(B)(3)(3) & NEC 690.59) <br />SERVICE PANEL IF SUM OF <br />BREAKERS EXCEEDS PANEL RATING <br />NEC 705.12 (b)(3)(2) <br />NOTES AND SPECIFICATIONS: <br />• SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE <br />2020 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS <br />ARE REQUIRED BY SECTION 690, OR IF REQUESTED BY THE <br />LOCAL AHJ. <br />• SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS <br />USING EFFECTIVE WORDS, COLORS AND SYMBOLS. <br />• LABELS SHALL BE PERMANENTLY AFFIXED TO THE <br />EQUIPMENT OR WIRING METHOD AND SHALL NOT BE HAND <br />WRITTEN. <br />• LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND <br />THE ENVIRONMENT INVOLVED. <br />• SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, <br />PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISE <br />SPECIFIED. <br />• DO NOT COVER EXISTING MANUFACTURER LABELS. <br />LABEL LOCATION: <br />AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF <br />INTERCONNECTION. <br />PER CODE(S): NEC 2020: 690.54 <br />LABEL LOCATION: <br />EMT/CONDUIT RACEWAYS <br />(PER CODE: NEC690.31(D)(2) <br />LABEL LOCATION: <br />MAIN SERVICE DISCONNECT / UTILITY METER <br />(PER CODE: NEC 690.13(B)) <br />A WARNING <br />THIS EQUIPMENT FED BY <br />MULTIPLE SOURCES TOTAL <br />RATING OF ALL OVERCURRENT <br />DEVICES EXCLUDING MAIN POWER <br />SUPPLY SHALL NOT EXCEED <br />AMPACITY OF BUSBAR <br />LABEL LOCATION: <br />POINTS OF CONNECTION/BREAKER <br />CODE: NEC 705.12(b)(3)(2) <br />A CAUTION <br />PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED <br />LABEL LOCATION: <br />MSP (PER CODE: NEC 705.12(D) & NEC <br />690.59 <br />LABEL LOCATION: <br />UTILITY SERVICE ENTRANCE/METER, INVERTER/DC <br />DISCONNECT IF REQUIRED BY LOCAL AHJ, OR <br />OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ. <br />PER CODE(S): NEC 2020: 690.56(C)(2) <br />AWARNING <br />THE DISCONNECTION OF THE <br />GROUNDED CONDUCTOR(S) <br />MAY RESULT IN OVERVOLTAGE <br />ON THE EQUIPMENT <br />i A-1 i ­nT­ <br />I I V V C R I C R <br />PER CODE: NEC 690.31(E) <br />co <br />4„ <br />SOLAR PV SYSTEM EQUIPPED <br />WITH RAPID SHUTDOWN <br />TURN RAPID SHUTDOWN <br />SWITCH TO THE "OFF" <br />POSITION TO SHUT DOWN <br />PV SYSTEM AND REDUCE <br />SHOCK HAZARD IN THE <br />ARRAY. <br />LABEL LOCATION: <br />ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE DISCONNECTING <br />MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED. <br />PER CODE(S): NEC 2020: IFC 690.56(C) <br />CAUTION ! <br />MULTIPLE SOURCES OF POWER <br />POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE <br />FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN <br />6027 DEXTER AVE <br />(N) PV MODULES <br />(E) UTILITY METER <br />(N) 200A MAIN SERVICE PANEL <br />WITH (N) 200A MAIN BREAKER <br />(N) 30A NON -FUSED AC DISCONNECT <br />(N) PRODUCTION METER <br />(N) ENPHASE IQ COMBINER BOX 4 <br />Lumio * <br />VERSION <br />I DESCRIPTION DATE REV <br />I INITIAL RELEASE 106/15/2023 I LIR <br />PROJECT NAME <br />Q <br />0 <br />. <br />uj <br />6 <br />CO <br />ti <br />o <br />>Mo=�� <br />a <br />N <br />C) U) W <br />W <br />zW <br />Cy) <br />O- <br />o0W <br />w <br />W��O <br />2 <br />z <br />o cn != <br />z <br />Q cV <br />W <br />U <br />0- ~ <br />W <br />> <br />Q Q <br />W <br />�l <br />W <br />ry <br />0— <br />SHEET NAME <br />WARNING LABELS & <br />PLACARD <br />SHEET SIZE <br />ANSI B <br />11" X 17" <br />SHEET NUMBER <br />PV-5 <br />