Laserfiche WebLink
NEUDORFER r - <br /> NE�B:B <br /> ENGINEERS <br /> WWW.NEUDDRFERENGINEERS,COM <br /> AN Integra COMPANY <br /> Fan Unit <br /> PROJECT: Boeing Bldg.40-10 Exhaust Extraction DATE: 8/21/2023 <br /> LOCATION: Everett, CONTACT: Moon Kim <br /> PROJECT#: 2023-0913 AUTHOR: <br /> SYSTEM/UNIT: EF-02 Tested By: Moon Kim <br /> Date: 8/9/2023 <br /> Unit Data Motor Data <br /> Fan Manufacturer Greenheck Motor Manufacturer Baldor <br /> Fan Model Number CUBE-300-30-1-40-X-SW Motor Frame 182T <br /> Fan Serial Number 22364320 Motor HP 3 HP <br /> Fan Rotation Clockwise Motor RPM 1760 RPM <br /> Fan Discharge Up Blast Motor Rated Volts 230/460 Volts <br /> Drive Type Belt Drive Motor Phase 3 <br /> Motor Hertz 60 Hz <br /> Test Data Motor Full Load Amps 8.4/4.2 Amps <br /> Total Design Flow 6800 CFM Motor Service Factor 1.15 <br /> Total Actual Flow 7295 CFM Nominal Efficiency 89.50% <br /> Fan RPM Actual 682 RPM Power Factor 75.00 <br /> Motor RPM Actual 1788 RPM <br /> Motor Volts T1-T2 482 Volts Sheave Data <br /> Motor Volts T2-T3 482 Volts Motor Sheave MFG Not Legible <br /> Motor Volts T1-T3 481 Volts Motor Sheave Model VP56 <br /> Motor Amps T1 3.30 Amps Motor Sheave Bore 1 1/8 in. <br /> Motor Amps T2 3.40 Amps Motor Sheave Type Adjustable <br /> Motor Amps T3 3.40 Amps Adj Mtr Sheave Pos Minimum <br /> Fan Sheave MFG Not Legible <br /> Fan Sheave Model AK114 <br /> Fan Sheave Bore 1 in. <br /> Number of Belts 1 <br /> Belt Size A47 <br /> Sheave Center Line 11 5/8 in. <br /> Motor to Extend 1.50 in. <br /> Motor to Retract 1.00 in. <br /> Test Pressures <br /> Fan Suction SP -0.69 in.we <br /> Fan Discharge SP Atmosphere in.we <br /> Actual Total SP 0.69 in.we <br /> Neudorfer Engineers 9 <br />