Laserfiche WebLink
EXHAUST FAN SCHEDULF <br /> STATIC VFD OPERATING WEIGHT <br /> ENOOIP LOCATION SERVICE BMAINUFFACTS OF DURERN DESIGNSSEERIES TYPE OF VOLUME PRESSURE DRIVE TYPE FAN MOTOR YES NO (LBS) REMARKS <br /> CFM INCHES W.G. RPM HE FLA RPM V/PH/HZ <br /> FF-02 SIDEWALL FUME HOOD GREENHECK 300HP CENTRIFUGAL 6800 1.5" BELT 874 3 3.6 1725 460/3/60 Y 223 1,2,3,4 <br /> EF-03 MAIN FLOOR VEHICLE EXHAUST CAR-MON CMB-14 INLINE 1800 5" BELT 3023 3 3.8 3600 460/3/60 NO 200 1,2,4 <br /> REMARKS: <br /> 1. INSTALL AS PER MANUFACTURER'S RECOMMENDATIONS <br /> 2. ELECTRICAL TO PROVIDE DISCONNECT SWITCH. <br /> 3. PROVIDE SPARK PROOF FAN (SPARK B). <br /> 4. PROVIDE 120V SHUTOFF DAMPER AT BUILDING EXTERIOR WALL TO MEET ENERGY CODE. <br /> DUCT CONSTRUCTION SCHEDULE <br /> U MIN SMACNA DUCT <br /> DUCT LOCATION DUCT TYPE DUCT SERVICE CLASS SEAL CLASS MATERIAL <br /> N <br /> FUME HOOD EXHAUST -2 C SS <br /> EXHAUST <br /> VEHICLE EXHAUST MINUS 4-5" A GA <br /> SAZAN <br /> G R O U P <br /> 600 Stewart St., Ste 1400 <br /> Seattle,Washington 98101 <br /> 100% SUBMITTAL Tel 206.267.1700 <br /> 03.06.23 fp Fax 206.267.1701 <br /> SAZAN#678-23085 <br /> DRAWN DATE <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE C({M ACCEPTABILITY SUBTITLE CURRENT REVISION SYMBOL DATE <br /> 4�oF K`HI J THIS DESIGN AND/OR CHECKED SCHEDULES 22-30461 03.06.23 0 <br /> 40-10 EXHAUST EXTRACTION 22-30461 SAZAN 03.06.23 aGL SPECIFICATION IS APPROVED SHEET m <br /> -ABOE/NG® APPROVED BY DEPT DATE N IN E 40-10 EXHAUST EXTRACTION n 2d \ <br /> C <br /> A 3` \Y/I <br /> HECKED I L <br /> 848 APPROVED BUILDING 40-10 JOB N0. COMP N0. <br /> "O I <br /> 03/06/2023 APPROVED MECHANICAL MASTER EVERETT, WA DWG No. 40-010-M2d <br />