Laserfiche WebLink
Care and <br />Maintenance <br />The TYCO Series TY-FRB, 5.6 K-factor, <br />Upright (TY313) and Pendent (TY323) <br />Sprinklers must be maintained and ser- <br />viced in accordance with this section. <br />Before closing a fire protection system <br />main control valve for maintenance <br />work on the fire protection system <br />that it controls, obtain permission to <br />shut down the affected fire protection <br />systems from the proper authorities <br />and notify all personnel who may be <br />affected by this action. <br />Absence of the outer piece of an <br />escutcheon, which is used to cover <br />a clearance hole, can delay sprinkler <br />operation in a fire situation. <br />The owner must assure that the sprin- <br />klers are not used for hanging any <br />objects and that the sprinklers are only <br />cleaned by means of gently dusting <br />with a feather duster; otherwise, non - <br />operation in the event of a fire or inad- <br />vertent operation may result. <br />Sprinklers which are found to be <br />leaking or exhibiting visible signs of <br />corrosion must be replaced. <br />Automatic sprinklers must never be <br />painted, plated, coated, or other- <br />wise altered after leaving the factory. <br />Modified sprinklers must be replaced. <br />Sprinklers that have been exposed to <br />corrosive products of combustion, but <br />have not operated, should be replaced <br />if they cannot be completely cleaned <br />by wiping the sprinkler with a cloth or <br />by brushing it with a soft bristle brush. <br />Care must be exercised to avoid <br />damage to the sprinklers before, <br />during, and after installation. Sprin- <br />klers damaged by dropping, striking, <br />wrench twist/slippage, or the like, must <br />be replaced. Also, replace any sprin- <br />kler that has a cracked bulb or that has <br />lost liquid from its bulb. (Ref. Installa- <br />tion Section.) <br />The owner is responsible for the <br />inspection, testing, and maintenance of <br />their fire protection system and devices <br />in compliance with this document, as <br />well as with the applicable standards <br />of the National Fire Protection Asso- <br />ciation (e.g., NFPA 25), in addition to <br />the standards of any other authorities <br />having jurisdiction. Contact the install- <br />ing contractor or product manufacturer <br />with any questions. <br />Automatic sprinkler systems are rec- <br />ommended to be inspected, tested, <br />and maintained by a qualified Inspec- <br />tion Service in accordance with local <br />requirements and/or national codes. <br />TFP172 <br />Page 3of4 <br />2-7/8" DIA. <br />(73,0 mm) <br />2-1/4" DIA. <br />FACE OF (57,2 mm) <br />SPRINKLER <br />FITTING 5/8" (15,9 mm) <br />FLUSH <br />3/8 5/16" _ <br />(9,5 7,9 mm) <br />MOUNTING 1/8" <br />SURFACE (3,2 mm) <br />CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm) <br />TY-FRB PLATE 3/4" (19,1 mm) <br />FIGURE 4 <br />SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323) <br />WITH TWO PIECE 518 INCH TOTAL ADJUSTMENT STYLE 15 <br />RECESSED ESCUTCHEON <br />2-7/8" DIA. _ <br />(73,0 mm) <br />FACE OF <br />SPRINKLER 2-1/4" DIA. <br />FITTING (57,2 mm) <br />5/16 1/4" 112" (12,7 mm) <br />(7,9 <br />FLUSH <br />MOUNTING 1/8" <br />SURFACE (3,2 mm) <br />CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm) <br />TY-FRB PLATE 7/8" (22,2 mm) <br />FIGURE 5 <br />SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323) <br />WITH TWO PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 <br />RECESSED ESCUTCHEON <br />Limited <br />Warranty <br />For warranty terms and conditions, visit <br />www.tyco-fire.com. <br />Ordering <br />Procedure <br />Contact your local distributor for avail- <br />ability. When placing an order, indicate <br />the full product name and Part Number <br />(P/N). <br />Sprinkler Assemblies with NPT <br />Thread Connections <br />Specify: Series TY-FRB Upright or <br />Pendent (specify) Sprinkler, SIN <br />(specify), K=5.6, Quick Response, <br />(specify) temperature rating, (specify) <br />finish, P/N (specify, refer to Table A). <br />Recessed Escutcheon <br />Specify: Style 15 Recessed Escutch- <br />eon with (specify") finish, P/N (specify") <br />Specify: Style 20 Recessed Escutch- <br />eon with (specify") finish, P/N (specify') <br />Refer to Technical Data Sheet TFP770 <br />Sprinkler Wrench <br />Specify: W-Type 6 Sprinkler Wrench, <br />P/N 56-000-6-387 <br />Specify: W-Type 7 Sprinkler Wrench, <br />P/N 56-850-4-001 <br />