STRUCTURAL NOTES <br />C K=A <br />(THESE NOTES ARE TYPICAL UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS) <br />CODE <br />ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, <br />SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (IBC), 201S EDITION. SPECIFICATIONS AND STANDARDS <br />WHERE REFERENCED ON THE DRAWINGS ARE TO BE THE LATEST EDITION. <br />DESIGN LOADS <br />DEAD LOADS: <br />ROOF <br />12 PSF <br />FLOOR <br />12 PSF <br />DECK <br />8 PSF <br />LIVE LOADS: <br />ROOF (SNOW LOAD) <br />25 PSF <br />DECK <br />60 PSF <br />(LIVE LOADS ARE REDUCED WHERE PERMISSIBLE PER IBC SECTION 1607.10). <br />EARTHQUAKE LOADS: <br />EQUIVALENT LATERAL FORCE PROCEDURE PER ASCE 7-10 SECTION 12.8. <br />SITE CLASS (ASSUMED) <br />D <br />SHORT PERIOD SPECTRAL RESPONSE ACCEL (SS) <br />1.343 <br />ONE SECOND SPECTRAL RESPONSE ACCEL (Si) <br />0.510 <br />SHORT PERIOD DESIGN SPECTRAL RESPONSE ACCEL (Sps) <br />0.895 <br />ONE SECOND DESIGN SPECTRAL RESPONSE ACCEL (SDI) <br />0.510 <br />RISK CATEGORY <br />II <br />SEISMIC IMPORTANCE FACTOR (IE) <br />1.0 <br />SEISMIC DESIGN CATEGORY <br />D <br />BASIC SEISMIC FORCE -RESISTING -SYSTEM <br />CANTILEVER TIMBER COLUMNS <br />RESPONSE MODIFICATION FACTOR, (R) <br />1.5 <br />REDUNDANCY FACTOR (p) <br />1.0 <br />SEISMIC RESPONSE COEFFICIENT (Cs) <br />0.597 <br />W = TOTAL SEISMIC DEAD LOAD AS DEFINED PER ASCE 7-10 SECTION 12.7.2 <br />BASE SHEAR (V), V=CSW= W <br />WIND LOADS: <br />BASIC WIND SPEED (3 SECOND GUST) 110 MPH <br />EXPOSURE B <br />Kn 1.00 <br />SEE PLANS FOR ADDITIONAL DESIGN LOADS. <br />STATEMENT OF SPECIAL INSPECTIONS <br />STRUCTURAL OBSERVATION OF THE STRUCTURAL SYSTEM BY THE ENGINEER IS NOT REQUIRED. <br />SOILS REPORT: NOT AVAILABLE AT TIME OF DESIGN <br />ALLOWABLE SOIL PRESSURE: 1500 PSF (ASSUMED) <br />LATERAL EARTH PRESSURE: <br />UNRESTRAINED: 35 PCF+ ANY APPLICABLE SURCHARGE <br />RESTRAINED: 50 PCF + ANY APPLICABLE SURCHARGE <br />PASSIVE: 300 PCF <br />COEFFICIENT OF FRICTION: 0.35 <br />FOOTINGS SHALL BEAR ON FIRM UNDISTURBED EARTH OR 12" OF COMPACTED STRUCTURAL FILL AS REQUIRED AND <br />AT LEAST 18" BELOW ADJACENT EXTERIOR GRADE. ANY FOOTING ELEVATIONS SHOWN IN THE DRAWINGS <br />REPRESENT MINIMUM DEPTHS AND ARE FOR BIDDING ONLY. ACTUAL FOOTING ELEVATIONS ARE SUBJECT TO SITE <br />CONDITIONS AND MUST THEREFORE BE ESTABLISHED BY THE CONTRACTOR. FOOTINGS SHALL BE CENTERED BELOW <br />COLUMNS OR WALLS ABOVE, UNLESS NOTED OTHERWISE. <br />IMPORTED STRUCTURAL FILL AND BACKFILL MATERIAL SHOULD CONSIST OF CLEAN, WELL GRADED GRANULAR <br />MATERIAL FREE OF DEBRIS OR ORGANICS WITH A MAXIMUM PARTICLE DIAMETER OF THREE INCHES AND NO MORE <br />THAN 10% FINES (PASSING THE #200 SIEVE). <br />FILL AND BACKFILL MATERIAL SHOULD BE PLACED IN LEVEL LIFTS NOT EXCEEDING TWELVE (12") INCHES IN LOOSE <br />THICKNESS AND COMPACTED TO A MINIMUM OF 95% OF ITS MAXIMUM DRY DENSITY AS DETERMINED BY ASTM <br />TEST METHOD D1557-00. <br />BACKFILL BEHIND ALL RETAINING WALLS WITH WELL -DRAINING, GRANULAR FILL AND PROVIDE FOR SUBSURFACE <br />DRAINAGE. PROVIDE DAMPPROOFING AT EXTERIOR FACE OF ALL FOUNDATION WALLS EXPOSED TO EARTH PER <br />ARCHITECTURAL SPECIFICATIONS. <br />CONCRETE <br />ALL CONCRETE SHALL BE MIXED, PROPORTIONED, CONVEYED, AND PLACED IN ACCORDANCE WITH SECTION <br />CHAPTER 5 OF ACI 318 AND THE AMERICAN CONCRETE INSTITUTE'S SPECIFICATIONS FOR STRUCTURAL CONCRETE <br />FOR BUILDINGS (ACI 301). <br />ALL CONCRETE SHALL BE STONE -AGGREGATE CONCRETE HAVING A UNIT WEIGHT OF APPROXIMATELY 150 POUNDS <br />PER CUBIC FOOT. <br />CONCRETE STRENGTHS AT 28 DAYS (f'c) AND MIX CRITERIASHALL BE AS FOLLOWS: <br />MAXIMUM <br />MIN CEMENT <br />TYPE OF CONSTRUCTION <br />Pc <br />WATER/CEMENT <br />CONTENT PER NBA[ <br />MAXIMUM <br />SHRINKAGE STRAIN <br />RATIO <br />YARD <br />FOOTINGS • <br />3000 PSI <br />0.55 <br />51/2 SACK <br />N/A <br />THE MINIMUM AMOUNT OF CEMENT LISTED ABOVE MAY BE CHANGED IF A CONCRETE PERFORMANCE MIX IS <br />SUBMITTED TO THE ENGINEER AND THE BUILDING DEPARTMENT FOR APPROVAL TWO WEEKS PRIOR TO PLACING <br />ANY CONCRETE. THE PERFORMANCE MIX SHALL INCLUDE THE AMOUNTS OF CEMENT, FINE AND COARSE <br />AGGREGATE, WATER, AND ADMIXTURES AS WELL AS THE WATER -CEMENT RATIO, SLUMP, CONCRETE YIELD, AND <br />SUBSTANTIATING STRENGTH DATA IN ACCORDANCE WITH CHAPTER 5 OF ACI 318. <br />ALL CONCRETE EXPOSED TO WEATHER OR TO FREEZING TEMPERATURES SHALL BE AIR -ENTRAINED IN ACCORDANCE <br />WITH ACI 318 TABLE 4.2.1 FOR MODERATE EXPOSURE CONDITION. <br />" PROVIDE 3000 PSI FOR DURABILITY REQUIREMENTS. 2,500 PSI F'c CONCRETE MEETS STRENGTH REQUIREMENTS <br />FOR DESIGNED FOOTINGS, THEREFORE SPECIAL INSPECTION IS NOT REQUIRED. <br />UNLESS OTHERWISE NOTED, REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS SHALL BE AS TABULATED <br />BELOW: <br />fc = 30DO PSI <br />DEVELOPMENT LENGTH <br />LAP SPLICE <br />BAR <br />TENSION <br />COMPRESSION <br />TENSION <br />COMPRESSION <br />SIZE <br />TOP BARS <br />BARS <br />ALL BARS <br />TOP BARS <br />B� <br />ALL BARS <br />#3 <br />22 <br />17 <br />9 <br />28 <br />22 <br />12 <br />#4 <br />29 <br />22 <br />11 <br />37 <br />29 <br />15 <br />#5 <br />36 <br />28 <br />14 <br />47 <br />36 <br />19 <br />#6 <br />43 <br />3-117 <br />56 <br />43 <br />23 <br />#7 <br />63 <br />48 <br />20 <br />81 <br />63 <br />27 <br />#8 <br />72 <br />1 55 <br />1 22 <br />93 <br />1 72 <br />1 30 <br />NOTE: <br />1. ALL LENGTHS ARE IN INCHES. <br />2. ALL LAP SPLICES ARE CLASS B. <br />3. "TOP BARS" ARE HORIZONTAL REINFORCEMENT PLACED SUCH THAT MORE THAN 12 INCHES OF <br />CONCRETE IS CAST IN THE MEMBER BELOW THE BAR. <br />CONCRETE COVER ON REINFORCING <br />CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: <br />3" <br />CONCRETE EXPOSED TO EARTH AND WEATHER: <br />#6 BARS AND LARGER <br />2" <br />#5 BARS AND SMALLER <br />11/2" <br />CONCRETE NOT EXPOSED TO EARTH OR WEATHER: <br />SLABS, WALLS AND JOISTS <br />3/4" <br />COLUMN TIES OR SPIRALS AND BEAM STIRRUPS <br />11/2" <br />CONCRETE GENERAL NOTES <br />VERTICAL BARS SHALL START FROM TOP OF FOOTING. HORIZONTAL BARS SHALL START A DISTANCE OF 1/2 THE <br />NORMAL BAR SPACING FROM TOP OF FOOTING AND TOP OF FRAMED SLABS. IN ADDITION, THERE SHALL BE A <br />HORIZONTAL BAR AT A MAXIMUM OF 3" FROM TOP OF WALL AND BOTTOM OF FRAMED SLABS. <br />PROVIDE CORNER BARS TO MATCH THE HORIZONTAL REINFORCING WITH TENSION LAP SPLICE AT EACH SIDE PER <br />TABLE, OR BEND ONE SIDE OVER TO PROVIDE TENSION LAP. <br />SEE ARCHITECTURAL DRAWINGS AND MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND DIMENSIONS OF <br />OPENINGS IN CONCRETE WALLS, FLOORS AND ROOF. UNLESS INDICATED OTHERWISE, REINFORCE AROUND <br />OPENINGS GREATER THAN 12" IN EITHER DIRECTION WITH (2) #5 EACH SIDE AND (1) #S x 4'-0" DIAGONAL AT EACH <br />CORNER. EXTEND BARS 2'-0" BEYOND EDGE OF OPENING. IF T-O" IS UNAVAILABLE, EXTEND AS FAR AS POSSIBLE <br />AND HOOK. HOOK ALL REINFORCING INTERRUPTED BY OPENINGS. <br />BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL NOT BE FIELD BENT UNLESS SO DETAILED OR <br />APPROVED BY THE STRUCTURAL ENGINEER. <br />SEE ARCHITECTURAL DRAWINGS FOR ALL GROOVES, NOTCHES, CHAMFERS, FEATURE STRIPS, COLOR, TEXTURE AND <br />OTHER FINISH DETAILS AT ALL EXPOSED CONCRETE SURFACES. PROVIDE 3/4" CHAMFER AT ALL CORNERS EXCEPT AS <br />NOTED. <br />LUMBER <br />ALL GRADES SPECIFIED ARE MINIMUM GRADES REQUIRED. ALL LUMBER SHALL BE IN ACCORDANCE WITH W WPA <br />GRADING RULES, KILN -DRIED TO MC 19 AND OF THE FOLLOWING MINIMUM STANDARDS: <br />SIZE CLASSIFICATION <br />SPECIES <br />GRADE <br />Fb (PSI) <br />Fc (PSI) <br />SLEEPERS <br />DOUG-FIR <br />STUD <br />700 <br />- <br />LIGHT FRAMING (STUDS) <br />HEM -FIR <br />STUD <br />675 <br />B00 <br />2x JOISTS AND PLANKS <br />HEM -FIR <br />#2 <br />850 <br />- <br />PLATESANDBLOCKING <br />HEM -FIR <br />#2 <br />850 <br />- <br />6xANDLARGERBEAMSAND <br />STRINGERS <br />DOUG-FIR <br />#2 <br />875 <br />- <br />41 AND SMALLER BEAMS AND <br />STRINGERS <br />HEM -FIR <br />#2 <br />850 <br />- <br />ALL POSTSANDTIMBERS <br />DOUG-FIR <br />#1 <br />1200 <br />1000 <br />REFER TO PLAN NOTES, SCHEDULES, AND DETAILS FOR MORE SPECIFIC LUMBER SIZE AND GRADE REQUIREMENTS. <br />UNLESS NOTED OTHERWISE IN THE PLANS, ALL WOOD AND WOOD -BASED MEMBERS EXPOSED TO WEATHER OR IN <br />CONTACT WITH CONCRETE, MASONRY, OR WITHIN 8" OF SOIL SHALL BE PRESERVATIVE -TREATED BY <br />VACUUM -PRESSURE IMPREGNATION IN ACCORDANCE WITH AWPA STANDARD Ul. <br />NAILS, BOLTS, AND METAL CONNECTORS FOR WOOD <br />ALL NAILS SHALL CONFORM TO THE STANDARDS SET FORTH BY THE NATIONAL DESIGN STANDARDS (NOS) FOR <br />WOOD CONSTRUCTION, LATEST EDITION. NAILING NOT SPECIFIED SHALL BE PER IBC TABLE 2304.9.1 NAILING <br />SCHEDULE. ALL NAILS CALLED OUT ON PLANS SHALL BE COMMON NAILS UNLESS NOTED OTHERWISE AND SHALL <br />NAIL <br />SHANK 0 <br />MIN LENGTH <br />8d OOMMON <br />0.1310 <br />2 1/2" SHANK <br />10d COMMON <br />0.1480 <br />3" SHANK <br />12d COMMON <br />0.1480 <br />3 1/4" SHANK <br />16d COMMON <br />0.1620 <br />3 1/2" SHANK <br />101 BOX NAILS MAY BE SUBSTITUTED FOR 8d COMMON NAILS WITH NO CHANGE IN NAILSPACING. FRAMING <br />MEMBERS MAY BE NAILED WITH 16d SINKERS (0.148"0 x 31/4"), BUT ONLY 16d COMMON NAILS SHALL BE USED <br />WHERE 16d NAILS ARE INDICATED IN THIS DRAWING SET. ENGINEER MAY APPROVE OTHER NAILS IF NAIL LABELS <br />ARE SUBMITTED TO ENGINEER PRIOR TO START OF CONSTRUCTION. <br />ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS <br />OF ALL BOLTS AND LAG SCREWS BEARING ON WOOD. LEAD HOLES FOR LAG BOLTS SHALL BE BORED FOR THE <br />SHANK AND THREADED PORTIONS PER NDS 11.1.3. <br />CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE" BY SIMPSON COMPANY, CATALOG <br />TO BE THE LATEST EDITION, OR ENGINEER APPROVED EQUAL. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE <br />WITH THE MANUFACTURER'S RECOMMENDATIONS AND WITH THE NUMBER AND SIZE OF FASTENERS AS SPECIFIED <br />BY THE MANUFACTURER. WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS, <br />SCREWS, OR BOLTS IN EACH MEMBER. <br />INSTALL SOLID BLOCKING AT ALL BEARING POINTS. ALL SHIMS SHALL BE SEASONED, DRIED, AND THE SAME GRADE <br />(MINIMUM) AS MEMBERS CONNECTED. <br />GALVANIZATION <br />UNLESS NOTED OTHERWISE, STEEL CONNECTORS IN CONTACT WITH TREATED WOOD SHALL BE GALVANIZED <br />ACCORDING TO THE FOLLOWING TABLE: <br />GALVANIZATION <br />UNTREATED <br />WOOD <br />CCA-C <br />SBX <br />ACQ-C <br />ACQ-D <br />CBA-A <br />CA-B <br />OTHER <br />BORATE <br />ACZA <br />OTHER PT <br />WOOD <br />G90 <br />X <br />x <br />X <br />G185 <br />X <br />X <br />X <br />X <br />X <br />X <br />HOG <br />X <br />X <br />X <br />X <br />X <br />X <br />STT300 <br />x <br />x <br />X <br />X <br />X <br />X <br />X <br />X <br />G90 = 0.90 OZ. OF ZINC PER SQUARE FOOT OF AREA <br />G185 = 1.85 OZ. OF ZINC PER SQUARE FOOT OF AREA <br />HOG = HOT DIP GALVANIZED <br />SST300 = TYPE 316L STAINLESS STEEL <br />RATED SHEATHING <br />RATED SHEATHING SHALL BE GRADE C-D INT-APA WITH EXTERIOR GLUE OR OSS SHEATHING WITH EXTERIOR GLUE <br />IN CONFORMANCE WITH IBC STANDARD 2303.1.4. <br />EXISTING BUILDING <br />CONTRACTOR SHALL VERIFY ALL DIMENSIONS, MEMBER SIZES AND CONDITIONS OF THE EXISTING BUILDING <br />DEPICTED IN THE DRAWINGS, AND NOTIFY THE STRUCTURAL ENGINEER OF ANY DISCREPANCIES FOR POSSIBLE <br />REDESIGN. <br />CONTRACTOR RESPONSIBLE FOR COMPLETELY SEALING ALL AREAS WHERE EXISTING ROOF MATERIAL IS <br />PENETRATED OR REMOVED. PROVIDE WATER PROOFING AS REQUIRED BY THE ARCH. <br />GENERAL <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL, CIVIL, ELECTRICAL, AND <br />MECHANICAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND <br />CONDITIONS FOR COMPATIBILITY BEFORE PROCEEDING. ANY DISCREPANCIES SHALL BE BROUGHT TO THE <br />ATTENTION OF THE ARCHITECT BEFORE PROCEEDING. <br />CONTRACTOR TO SEE ARCHITECTURAL, CIVIL, ELECTRICAL AND MECHANICAL DRAWINGS FOR SIZE AND LOCATION <br />OF PIPE, VENT, DUCT AND OTHER OPENINGS AND DETAILS NOTSHOWN ON THESE DRAWINGS. <br />CONTRACTOR SHALL BE RESPONSIBLE FOR ERECTION STABILITY AND TEMPORARY SHORING AS NECESSARY UNTIL <br />PERMANENT SUPPORT AND STIFFENING ARE INSTALLED. <br />CONTRACTORANITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND STRUCTURAL <br />ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS <br />ONLY WILL NOT SATISFY THIS REQUIREMENT. <br />DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT <br />SPECIFICALLY INDICATED BUT ARE OF A SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF <br />CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL <br />ENGINEER. <br />LEGEND <br />DEFINITION <br />SYMBOL DEFINITION <br />SYMBOL <br />DIRECTION OF <br />NATIVE SOIL <br />FRAMING <br />P, <br />EXTENT OF <br />GRANULAR FILL <br />FRAMING <br />COLUMNS <br />STRUCTURAL STEEL <br />COLUMN BEARING <br />RATED SHEATHING <br />ON BEAM <br />BEAM CONTINUOUS <br />SHEAR WALL <br />SWX <br />OVER SUPPORT <br />(SEE SCHEDULE) <br />COLUMN MARK <br />G <br />CONCRETE WALL <br />(SEE SCHEDULE) <br />/ <br />BEARING STUD <br />FOOTING MARK <br />WALL <br />(SEE SCHEDULE) <br />O <br />NON -BEARING <br />HOLDOWN MARK <br />STUD WALL <br />(SEE SCHEDULE) <br />BEARING STUD <br />{ <br />HANGER MARK <br />SHEAR WALL <br />(SEE SCHEDULE) <br />OK <br />NON -BEARING( <br />FLAG NOTE <br />STUD SHEAR WALL <br />(SEE PLAN NOTES) <br />CMU WALL <br />STEEL MOMENT <br />FRAME CON.. <br />ABBREVIATIONS <br />(A) <br />ABOVE <br />GLB <br />GLUE -LAMINATED BEAM <br />AB <br />ANCHOR BOLT <br />HORIZ <br />HORIZONTAL <br />ALT <br />ALTERNATE <br />KP <br />KING POST <br />ARCH <br />ARCHITECT <br />KSI <br />KIPS PER SQUARE INCH <br />(B) <br />BELOW <br />L <br />ANGLE <br />BD <br />BAR DIAMETER <br />MECH <br />MECHANICAL <br />BLKG <br />BLOCKING <br />MF <br />MOMENTFRAME <br />BM <br />BEAM <br />MTL <br />METAL <br />BOT <br />BOTTOM <br />NS <br />NEAR SIDE <br />BRNG <br />BEARING <br />OC <br />ON CENTER <br />BTWN <br />BETWEEN <br />OPP <br />OPPOSITE <br />UP <br />COMPLETE JOINT PENETRATION <br />PL <br />PLATE <br />CUR <br />CLEAR <br />PLCS <br />PLACES <br />CIVIL) <br />CONCRETE MASONRY UNIT <br />PSI <br />POUNDS PER SQUARE INCH <br />COL <br />COLUMN <br />PSF <br />POUNDS PER SQUARE FOOT <br />CONC <br />CONCRETE <br />P/T <br />POST TENSIONED <br />CONN <br />CONNECTION <br />PT <br />PRESSURE TREATED <br />CONT <br />CONTINUOUS <br />REINF <br />REINFORCING <br />COORD <br />COORDINATE <br />REQ'D <br />REQUIRED <br />DBL <br />DOUBLE <br />SCHED <br />SCHEDULE <br />DET <br />DETAIL <br />SIM <br />SIMILAR <br />CIA <br />DIAMETER <br />SOG <br />SLAB ON GRADE <br />DIM <br />DIMENSION <br />STD <br />STANDARD <br />DIR <br />DIRECTION <br />STIFF <br />STIFFENER <br />EA <br />EACH <br />STL <br />STEEL <br />ELEV <br />ELEVATION <br />SYMM <br />SYMMETRICAL <br />ES <br />EACH SIDE <br />SW <br />SHEARWALL <br />EX <br />EXISTING <br />TOC <br />TOP OF CONCRETE <br />EXP <br />EXPANSION <br />TOS <br />TOP OF STEEL <br />FLR <br />FLOOR <br />TOW <br />TOP OF WALL <br />FON <br />FOUNDATION <br />TYP <br />TYPICAL <br />FTG <br />FOOTING <br />LINO <br />UNLESS NOTED OTHERWISE <br />FS <br />FAR SIDE <br />VERT <br />VERTICAL <br />GC <br />GENERAL CONTRACTOR <br />WF <br />WIDE FLANGE <br />ENGINEERING <br />250 4TH AVE. S., SUITE 200 <br />EDMONDS, WASHINGTON 98020 <br />PHONE (425) 778-8500 <br />FAX (425) 778-5536 <br />G. Ce,. <br />oy dT aa9q� <br />h <br />L <br />rOJVAL 4A' <br />01 / 08/ 2020 <br />DESIGN: CGP <br />DRAWN: <br />JCP <br />CHECK: <br />JGG <br />JOB NO: <br />19128.10 <br />DATE: <br />04/23/19 <br />Y <br />U <br />U) <br />W <br />W <br />W w <br />U M O <br />O <br />Z <br />W V) 00 <br />a rn <br />Q <br />w a a <br />� V) <br />V)z <br />U <br />w W <br />W Q) Q <br />D <br />x Pr)W <br />(n <br />SHEET <br />S1.1 <br />CITY OF EVERETT <br />REVIEWED FOR PERMIT <br />