Laserfiche WebLink
Permit#: FA2307-011 A <br /> Site Address: 2331 Hoyt Ave EVERETT <br /> Applicant: ETG-Fire LEVERETT LC .,�n .or► <br /> Application Date: 07/25/2023 Everett Fire Dept. Permit Review <br /> Description: Everett HS Commercial Building FACP Status: Approved <br /> Replacement Reviewed By: KBrown <br /> 07/25/2023 10:52:42 <br /> F1" <br /> Review Status: 1st Review by City& Peer Reviewers 8223 Broadway AM __J G <br /> RE I Review Date: 07/25/2023 Everett, WA 98203 <br /> SPECIAL HAZARDS FIRE PROTECTION (206) 557-3660 <br /> Date: 7/24/2023 Fire Alarm System Product Submittals <br /> Project: Everett High School / Commercial Building <br /> Fire Alarm Control Panel Replacement <br /> Customer: Everett Public Schools <br /> Site Address: 2416 Colby Ave. Everett Pages: 8 <br /> Everett, WA 98201 <br /> Material List of Data Sheets <br /> Item Manufacturer Model # Description <br /> 1 Notifier N16 Intelligent Fire Alarm Control Panel <br /> (END) <br /> r-—-—-—-—-—-—-—-—-—-I <br /> IEverett Fire Dept. Notes: A <br /> (NFPA 72) I <br /> I EVERETT <br /> -See Attached Fire Alarm System ' <br /> IAcceptance Test Checklist. <br /> I •24 hour Battery Test -At the time of the ' <br /> inspection/test provide proof verifying that the ' <br /> Ipanel has been operating on secondary power I <br /> (battery) for 24 hours. No other problems <br /> Ishall be indicated on the panel. I <br /> ' •Record of Completion - For all new ' <br /> systems, a Record of Completion is required I <br /> ' to be entered into The Compliance Engine I <br /> prior to permit final. <br /> i (www.thecomplianceengine.com) I <br /> 1------------------J <br />