SCOPE RESPONSIBILITY <br />NO - MECHANICAL CONTRACTOR I EG - ELECTRICAL CONTRACTOR I PC - PLUMBING CONTRACTOR I CC - CONTROLS CONTRACTOR I GC - GENERAL CONTRACTOR I FAG - FIRE ALARM CONTRACTOR <br />COORDINATION ITEM mmmmmm <br />•V VOLTAGE TWERII180-TITr� <br />I EQUIPMENT CONDENSATE DRAIN PIPING AND P-TRAPS I YES I MC I MC I N/A I N/A I - I <br />DISCONNECT AT EQUIPMENT I YES I EXIST I EXIST I EC I EC I - <br />DONTROLS WIRING INCLUDES LOW VOLTAGE WIRING AND/OR PNEUMATIC TUBING <br />MINIMUM DUCT INSULATION REQUIREMENTS <br />(PER 2018 WSEC/SEC REQUIREMENTS SECTION C403.10.1) <br />MIN. <br />RECOMMENDED <br />SYSTEM <br />DUCT LOCATION <br />DUCT USE <br />R-VALUE <br />INSTALLED INS. <br />THICKNESS <br />UPSTREAM OF MD <br />OSA <br />CONDITIONED SPACE <br />z 2,800 CFM <br />R-16 <br />-- <br />DOWNSTREAM OF MD <br />OSA <br />CONDITIONED SPACE <br />z 2,800 CFM <br />R-8 <br />OSA <br />CONDITIONED SPACE <br /><2,800 CFM <br />R-7 <br />2" LINER, OR <br />3" WRAP <br />SA/RA <br />OUTSIDE THE BUILDING <br />ALL <br />R-8 <br />2"LINER <br />SA I RA <br />UNCONDITIONED SPACE <br />DUCT AIR NOT WITHIN 15°F OF SPACE TEMP <br />R-6 <br />1.5" LINER, OR <br />- <br />3" WRAP <br />SA I RA <br />UNCONDITIONED SPACE <br />DUCT AIR WITHIN 15"F OF SPACE TEMP <br />R-3.3 <br />1"LINER, OR <br />1.5' WRAP <br />SA / RA <br />WITHIN BUILDING ENVELOPE <br />A <br />ALL <br />R-16 <br />-- <br />ASSEMBLY <br />SA <br />CONDITIONED SPACE <br />SAT < 55OF OR > 105"F <br />R-3.3 <br />V LINER, OR <br />1.'WRAP <br />SA <br />CONDITIONED SPACE <br />55°FS SAT 5105°F <br />NONE <br />-- <br />CONDITIONED SPACE DIRECTLY <br />SA <br />SERVED BY DUCT <br />ALL <br />NONE <br />-- <br />SA (DOAS) <br />CONDITIONED SPACE <br />DOWNSTREAM OF DOAS <br />NONE <br />-- <br />RA /EXH (DOAS) <br />CONDITIONED SPACE <br />DOWNSTREAM OF DOAS <br />R$ <br />2" LINER, OR <br />UPSTREAM OF MD <br />3" WRAP <br />RELIEF / EXH <br />CONDITIONED SPACE <br />DOWNSTREAM OF MD <br />R-16 <br />-- <br />NOTES: <br />• DUCT SHALL BE WRAPPED OR LINED PER PLAN <br />• DEFAULT LINER THICKNESS = 1", UNLESS OTHERWISE NOTED ON PLANS <br />• DEFAULT WRAP THICKNESS = 1.5", UNLESS OTHERWISE NOTED ON PLANS <br />PIPING INSULATION REQUIREMENTS <br />(PER 2018 WSEC/SEC REQUIREMENTS SECTION C403.10.3) <br />FLUID <br />OPERATING <br />INSULATION CONDUCTIVITY <br />NOMINAL PIPE SIZE (IN.) <br />TEMP RANGE ff <br />CONDUCTIVITY <br />BTU'IN/(H"FT'"F) <br />MEAN RATING <br />TEMP, F <br /><1 <br />1 TO < 1 i <br />1 z TO < 4 <br />4 TO <8 <br />> 8 <br />> 350 <br />0.32 - 0.34 <br />250 <br />4.5 <br />5.0 <br />5.0 <br />5.0 <br />5.0 <br />251 - 350 <br />0.29 - 0.32 <br />200 <br />3.0 <br />4.0 <br />4.5 <br />4.5 <br />4.5 <br />201 - 250 <br />0.27 - 0.30 <br />150 <br />2.5 <br />2.5 <br />2.5 <br />3.0 <br />3.0 <br />141 - 200 <br />0.25 - 0.29 <br />125 <br />1.5 <br />1.5 <br />2.0 <br />2.0 <br />2.0 <br />105 -140 <br />0.21 - 0.28 <br />100 <br />1.0 <br />1.0 <br />1.5 <br />1.5 <br />1.5 <br />40 - 60 <br />0.21 - 0.27 <br />1 75 <br />0.5 <br />1 0.5 <br />1.0 <br />I 1.0 <br />1.0 <br />< 40 <br />0.20 - 0.26 <br />75 <br />0.5 <br />1.0 <br />1.0 <br />1.0 <br />1.5 <br />NOTES: <br />1. FOR PIPING SMALLERTHAN 1 UT AND LOCATED IN PARTITIONS WITHIN CONDITIONED SPACES, REDUCTION OF THESE THICKNESSES BY 1- SHALL BE PERMITTED BUT NOT TO <br />A THICKNESS LESS THAN 1'. <br />2. INSULATION IS NOT REQUIRED FOR CONDENSATE DRAIN PIPING FROM A DX COOLING COIL PER WSECISEC 403.10.3 EXCEPTION 3. IT IS RECOMMENDED THAT IF THE DRAIN <br />PIPING IS LOCATED WITHIN A PLENUM THAT IS NOT USED AS A RETURN AIR PATH, OR OTHER UNCONDITIONED SPACE WITH LIMITED AIRFLOW, THE DRAIN PIPE SHOULD BE <br />INSULATED WITH 0.5- THICK INSULATION TO PREVENT CONDENSATION ON THE OUTSIDE OF THE PIPE. <br />C406 EFFICIENCY PACKAGE CREDITS <br />(PER 2018 WSEC/SEC REQUIREMENTS) <br />CODE SECTION <br />OCCUPANCY <br />CREDITS <br />RESPONSIBILITY' <br />THIS PROJECT IS NOT REQUIRED TO COMPLY WITH C406 <br />-- <br />TOTAL PROJECT CREDITS: <br />0 <br />NOTES: <br />1. ACCO WILL COMPLY WITH CREDITS AS NOTED IN "RESPONSIBILITY - ACCO". <br />CREDITS NOTED AS "RESPONSIBILITY -OTHER" ARE NOT WITHIN ACCO'S SCOPE, AND ARE THE RESPONSIBILITY OF OTHER <br />DISCIPLINES. THESE ARE SHOWN FOR REFERENCE ONLY. <br />DUCT CONSTRUCTION SCHEDULE <br />(PRESSURE CLASS PER SMACNA TABLE 1-1 S) <br />DUCT SECTION/COMPONENT <br />DUCT <br />PRESSURE CLASS <br />LOW SIDE SUPPLY <br />IT <br />HVAC GENERAL NOTES <br />WASHINGTON <br />1. <br />EXCEPT AS MODIFIED BY A WRITTEN CONTRACT SIGNED BY THE DESIGN -BUILDER, THE DRAWINGS, SPECIFICATIONS, AND <br />OTHER DOCUMENTS, INCLUDING THOSE IN ELECTRONIC FORM PREPARED BY OR FOR AND/OR FURNISHED BY DESIGN -BUILDER <br />ARE "INSTRUMENTS OF SERVICE." THE DESIGN -BUILDER, DESIGN -BUILDER'S CONSULTANTS AND OTHER PROVIDERS OF <br />PROFESSIONAL SERVICES INDIVIDUALLY SHALL RETAIN A FULLY PREPAID, UNRESTRICTED, PERPETUAL LICENSE IN THE <br />INSTRUMENTS OF SERVICE AS WELL AS ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING <br />COPYRIGHT IN THOSE INSTRUMENTS OF SERVICE FURNISHED BY THEM. <br />THE INSTRUMENTS OF SERVICE FURNISHED BY DESIGN -BUILDER ARE FOR SOLE USE BY DESIGN -BUILDER IN CONSTRUCTING <br />THE SUBJECT PROJECT. THE INSTRUMENTS OF SERVICE ARE NOT SUITABLE FOR BIDDING OR CONSTRUCTING BY OTHER <br />CONTRACTORS. THEREFORE, IF DESIGN -BUILDER IS NOT RETAINED AS THE DESIGN -BUILD CONTRACTOR TO PERFORM THE <br />WORK DEPICTED IN THE INSTRUMENTS OF SERVICE, WITHOUT THE PRIOR WRITTEN CONSENT OF THE DESIGN BUILDER, THE <br />INSTRUMENTS OF SERVICE MAY NOT BE REPRODUCED OR USED FOR ANY PURPOSE EXCEPT FOR GENERAL REFERENCE. <br />DESIGN -BUILDER DISCLAIMS ALL LIABILITY FOR ANY ADAPTATION, MODIFICATION, OR INTERPRETATION OF THE INSTRUMENTS <br />OF SERVICE, OR FOR ANY OTHER UNAUTHORIZED USE OF THESE INSTRUMENTS OF SERVICE. <br />2. <br />THESE DOCUMENTS WERE PREPARED FOR CONSTRUCTION BY DESIGN -BUILDER ONLY. DESIGN -BUILDER DEVELOPED THESE <br />DOCUMENTS WITH ENGINEERING SOLUTIONS AND CONSTRUCTION MEANS AND METHODS UNIQUE TO DESIGN -BUILDER FOR <br />THE CONSTRUCTION OF THE SUBJECT PROJECT AND ARE NOT APPROPRIATE FOR OTHERS TO BID OR BUILD FROM. IN <br />ADDITION, THESE DRAWINGS WERE DEVELOPED FROM INFORMATION MADE KNOWN TO DESIGN -BUILDER AS OF THE DATE OF <br />THE DOCUMENT AND WOULD NOT INCLUDE LATER CHANGES. <br />3. <br />THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY OFFSET WHICH MAY BE REQUIRED. THE HVAC <br />CONTRACTOR IS TO COORDINATE WITH ALL OTHER TRADES AND IS TO VERIFY ALL CLEARANCES BEFORE COMMENCING WORK. <br />4. <br />MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE 2018 EDITIONS OF THE WA <br />MECHANICAL CODE, WA BUILDING CODE, WA FUEL AND GAS CODE, WA FIRE CODE, AND LOCAL CODES AND ORDINANCES. <br />5. <br />EQUIPMENT SIZING AND SELECTION TO COMPLY WITH 2O18 WSEC 403.3.1. THE OUTPUT CAPACITY FOR HEATING AND COOLING <br />EQUIPMENT SHALL BE NO GREATER THAN THAT OF THE SMALLEST AVAILABLE EQUIPMENT SIZE THAT EXCEEDS THE <br />CALCULATED LOADS. <br />6. <br />ZONE THERMOSTATIC CONTROLS SHALL BE CONFIGURED TO PROVIDE A DEADBAND OF 5'F WITHIN WHICH THE SUPPLY OF <br />HEATING AND COOLING ENERGY TO THE ZONE IS SHUT OFF OR REDUCED TO A MINIMUM PER 2018 WSEC C403.4.1.2 . <br />7. <br />AUTOMATIC CONTROLS SHALL BE CAPABLE OF STARTING AND STOPPING THE SYSTEM AS REQUIRED PER 2018 WSEC C403.4.2. <br />8. <br />VENTILATION AND MINIMUM OUTSIDE AIR VALUES CALCULATED PER 2018 WA MC CHAPTER 4. <br />9. <br />AIRSIDE ECONOMIZER TO BE PROVIDED AS NOTED IN EQUIPMENT SCHEDULES AND MEET REQUIREMENTS OF 2018 WSEC <br />C403.5. <br />10. <br />OUTSIDE AIR SUPPLY, EXHAUST OPENINGS, RETURN AIR OPENINGS USED FOR AIRSIDE ECONOMIZER OPERATION, AND <br />STAIRWAY AND SHAFT VENTS SHALL BE PROVIDED WITH CLASS I MOTORIZED DAMPERS PER 2018 WSEC C403.7.8. <br />11. <br />SELECTED FAN MOTORS SHALL BE NO LARGER THAN THE FIRST AVAILABLE MOTOR SIZE GREATER THAN THE DESIGN BHP PER <br />2018 WSEC C403.8.2. <br />12. <br />DUCT CONSTRUCTION AND HANGING SHALL COMPLY WITH SECTION 603 OF THE 2018 WA MC AND WITH CURRENT SMACNA <br />STANDARDS. EARTHQUAKE BRACE ALL DUCTS 28" DIA AND LARGER WHICH ARE SUSPENDED MORE THAN 12" BELOW <br />STRUCTURALSYSTEM. <br />13. <br />JOINTS OF MEDIUM AND HIGH VELOCITY DUCT SYSTEMS SHALL BE SEALED WITH GASKETS OR LISTED MASTIC TYPE DUCT <br />SEALANT. <br />14. <br />DUCTS SHALL BE INSULATED AS INDICATED ON PLANS. <br />A. <br />DUCT WRAP, WHERE INDICATED, SHALL BE 1.5" 0.75 LB/FT' FIBERGLASS DUCT INSULATION WITH A FACTORY APPLIED <br />REINFORCED ALUMINUM FOIL VAPOR BARRIER, UNLESS NOTED OTHERWISE <br />B. <br />SOUND LINING, WHERE INDICATED, SHALL BE 1.0" 1.5 LB/FT' FIBERGLASS DUCT LINING COATED TO PREVENT FIBER <br />EROSION AT VELOCITIES UP TO 4,000 FPM, UNLESS NOTED OTHERWISE. <br />15. <br />FLEX DUCTS SHALL CONSIST OF A REINFORCED VAPOR BARRIER, 1.5" FIBERGLASS INSULATION, AND NON -PERFORATED <br />INTERIOR LINER WITH WIRE HELIX. DUCT SHALL BE A UL 181 LISTED CLASS 1 AIR DUCT. FLEX DUCTS SHALL ONLY BE USED <br />WHERE SHOWN AND SHALL NOT EXCEED 12' IN LENGTH UNLESS NOTED OTHERWISE. <br />16. <br />PROVIDE EARTHQUAKE RESTRAINT FOR HVAC EQUIPMENT IN ACCORDANCE WITH SECTION 1613 OF THE 2018 WA BC. <br />17. <br />PROVIDE FIRE DAMPERS, SMOKE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS, AND CEILING RADIATION DAMPERS WHERE <br />INDICATED ON PLANS AND AS REQUIRED BY SECTION 607 OF THE 2015 WA MC. INSTALL IN ACCORDANCE WITH THE <br />MANUFACTURERS' INSTRUCTIONS, THE TERMS OF THEIR LISTING, AND THE REQUIREMENTS OF THE CODE. <br />18. <br />PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOORS SHALL BE SLEEVED AND FIRE STOPPED WITH LISTED MATERIALS SO <br />AS TO MAINTAIN THE INTEGRITY AND RATING OF THE FLOOR OR WALL. <br />19, <br />PROVIDE RETURN DUCT SMOKE DETECTOR AUTOMATIC SHUT DOWN OF ALL HEATING, COOLING, OR VENTILATION EQUIPMENT <br />DELIVERING IN EXCESS OF 2,000 CFM IN ACCORDANCE WITH SECTION 606 OF THE 2015 WA MC. <br />20, <br />HVAC EQUIPMENT, VALVES, AND DAMPERS SHALL BE LOCATED IN EASILY ACCESSIBLE LOCATIONS. <br />21. <br />WITHIN 90 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION TO BE <br />PROVIDED TO THE BUILDING OWNER. RECORD DRAWINGS SHALL INCLUDE AS A MINIMUM THE LOCATION AND PERFORMANCE <br />DATA ON EACH PIECE OF EQUIPMENT, GENERAL CONFIGURATION OF DUCT AND PIPE DISTRIBUTION SYSTEM INCLUDING SIZES, <br />AND THE TERMINAL AIR AND WATER DESIGN FLOW RATES. <br />22. <br />OPERATING AND MAINTENANCE MANUALS TO BE PROVIDED TO THE BUILDING OWNER THAT INCLUDE: SUBMITTAL DATA, <br />NAMES AND ADDRESSES OF AT LEAST ONE SERVICE AGENCY, HVAC CONTROLS SYSTEM MAINTENANCE AND CALIBRATION <br />INFORMATION, AND A COMPLETE OPERATIONAL NARRATIVE FOR EACH SYSTEM. <br />23. <br />A WRITTEN BALANCE REPORT SHALL BE FILED WITH THE OWNER. <br />24. <br />COMMISSIONING: COMMISSIONING FOR THE PROJECT SHALL MEET THE REQUIREMENTS OF THE 2018 WSEC, SECTION C408. <br />SYSTEM SHALL BE TESTED TO ENSURE CONTROL DEVICES, EQUIPMENT, AND SYSTEMS ARE CALIBRATED, ADJUSTED, AND <br />OPERATE IN ACCORDANCE WITH THE PLANS. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE THEY <br />OPERATE IN ACCORDANCE WITH THE PLANS. A COMPLETE REPORT OF TEST PROCEDURES AND RESULTS SHALL BE <br />PREPARED AND FILED WITH THE OWNER. <br />25. <br />FOR ALL "SEALED AIR TIGHT" SHAFTS, THE FOLLOWING MUST OCCUR: <br />A. <br />ALL VERTICAL JOINTS INSIDE THE SHAFT SHOULD BE PROVIDED WITH A CONTINUOUS SEAL FOR THE LENGTH OF THE <br />JOINT, INCLUDING THE SHAFT CORNERS (BY G.C.) <br />B. <br />TOP AND BOTTOM WALL TRACKS SHOULD BE CAULKED ALONG THEIR ENTIRE LENGTH (BY G.C.) <br />C. <br />ANY FLOOR DECKING PERPENDICULAR TO THE SHAFT SHOULD BE CAULKED. FILLING WITH ROCK WOOL IS NOT <br />ACCEPTABLE (BY G.C.) <br />D. <br />ANY PENETRATIONS OF THE SHAFT CONSTRUCTION (DUCT WORK, CONDUIT, PIPING,...) SHOULD BE SEALED ON BOTH <br />SIDES OF THE PENETRATION <br />E. <br />USE SECTION 909 OF THE 2018 IBC FOR MAXIMUM ALLOWABLE LEAKAGE AREA, FOLLOWING THE GUIDELINES FOR TIGHT <br />SHAFT CONSTRUCTION <br />LOAD CRITERIA <br />HEATING AND COOLING LOAD CALCULATIONS PERFORMED PER 2018 WSEC/SEC 403.2.1 <br />ENVELOPE VALUES <br />DESIGN TEMPERATURES <br />U-VALUE (BTUH/FT'"F) <br />"F <br />ROOF <br />N/A <br />INDOOR -COOLING <br />75 <br />WALL <br />N/A <br />INDOOR -HEATING <br />70 <br />FLOOR <br />N/A <br />OUTDOOR -COOLING <br />N/A <br />GLASS <br />N/A <br />OUTDOOR -HEATING <br />N/A <br />GLASS(SC) <br />N/A <br />INTERNAL LOADS <br />SPACE TYPE <br />MISC EQUIPMENT <br />PEOPLE DENSITY (SEAT COUNT) <br />LIGHTING(W/SOFT) <br />OFFICE <br />N/A <br />N/A <br />N/A <br />CONFERENCE <br />N/A <br />N/A <br />N/A <br />KITCHEN <br />N/A <br />N/A <br />N/A <br />SERVER ROOM <br />N/A <br />N/A <br />N/A <br />I en inewed <br />systems <br />5300 DENVER AVENUE SOUTH <br />SEATTLE, WASHINGTON 98108 <br />(206)787-8500 <br />THE PLANS AND SPECIFICATIONS HEREIN <br />ARE OWNED BYAND FOR THE SOLE USE OF <br />ACCO ENGINEERED SYSTEMS, INC. (-ACCO-), <br />AND MAY NOT BE REPRODUCED OR USED <br />BY OTHERS FOR ANY PURPOSE UNLESS <br />AUTHORIZED BYACCO IN WRITING. ACCO <br />CANNOTACCEPTANYLIABILITY, WARRANTY, OR <br />OBLIGATION IN THE EVENT OF UNAUTHORIZED USE <br />AREA OF WORK <br />KEON <br />PLAN <br />Ci. <br />9 R� inoT o 'W <br />ION.AL C <br />EXPIRES: 11-28-2024 <br />1 <br />06/30/2023 <br />PERMIT SET <br />AC <br />No. <br />Date <br />Description <br />By <br />Revisions <br />Project <br />SCHNITZER PAINE FIELD <br />SPLIT -SYSTEM HEAT PUMP <br />REPLACEMENT <br />2615 W CASINO RD <br />EVERETT, WA 98204 <br />Title <br />CONSTRUCTION <br />REQUIREMENTS <br />A. CEARNS T. TOUTONGHI <br />Designed By Checked By <br />A. CEARNS D. RISTOW <br />Drawn By Project Manager <br />70870652 1 /811=1 I.011 <br />Job Number Scale <br />M0.01 <br />