Laserfiche WebLink
1. The project appears to have significant modifications that are not being currently shown as <br />"new" construction. All ch a nges from the origina l building layout, including those that were <br />performed by a previous owner without permits, must be shown as new work. This includes any <br />building modifications that are physically present but were not performed with permit. <br />2. Unpermitted modifications to the building may have altered and compromised the structural <br />system(s) for the building. Complete structura l framing plans should be included in the drawing <br />set and submitted for review. The framing plans should show all roof and floor framing, and <br />vertical framing (walls, posts, etc.) providing a complete load path from the roof to the <br />foundations. <br />3. Conti nu in g with the previous com me nt, the rear 30-40% of the building is not origina l(i.e., <br />portion containingthe kitchen and stairway, and possibly part ofthe rear bedroom). While this <br />portion may have been added with a permit, this is unclear. Futhermore, it appears possible <br />that the addition involved demolition to part of the rear load -bearing wall. While complete <br />justification of the addition is not being requested, the structural plans should verify that the <br />load path was modified appropriately. Since the existing stairway does not appear original, it <br />appears likely that a pre-existing stairway was demolished and floor openings infilled. Old infill <br />construction should be verified to not compromise the load path of the modified building load <br />paths. Modifications to the existing exterior wall to add, enlarge, infill, or otherwise change the <br />openings require modified structural framing. <br />4. Sections should be provided through the building clarifying the construction, minimum one in <br />each direction. Reflected ceiling plans should be included indicating the ceiling heights and <br />sloped surfaces, particularly at the basement and attic levels. <br />5. The basement level is not permitted as habitable space, and is documented as unfinished space <br />per the County Assessors records. Therefore, all improvements to the basement level must be <br />shown as new construction and are required to comply with the requirements for new <br />construction. Head heights may comply with exceptions for existing basements, but are <br />required to comply throughout the convert space. <br />6. The original garage door opening at the basement level is now an exterior wall. The wall is <br />required to comply with the requirements for new construction. <br />7. The details indicated that the new headers have been provided for the egress windows at the <br />basement bedrooms. Headers do not appearto be shown in the plans as indicated. <br />8. The plan dimensions, are not consistent for all levels. Based on a review of building <br />photography, the exterior walls should generally stack from the attic level to the <br />basement. Additional attic and crawl spaces should be shown. Access to these areas should be <br />provided. <br />9. The exteriorframing appears to have been exposed (i.e., original wall finishes replaced or <br />finishes added to previously unfinished framing). The building envelope is required to comply <br />with the insulation requirements of the energy code. <br />10. It appears the stairway is not original and is therefore required to comply with the code <br />requirements for new construction. The rise, run, and width of the stairs and landing should be <br />stated. Sections through the stairs showing the head clearances should be included. Handrails <br />are required. The barn door in the kitchen providing stair access to the attic level may not <br />comply with landing requirements and need to be modified or removed; at a minimum, the <br />door appears to require safety glazing. <br />