STRUCTURAL NOTES <br />CRITERIA <br />1. ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE <br />DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (2018 <br />EDITION). <br />2. DESIGN LOADING CRITERIA: <br />ASSEMBLY AREAS <br />FLOOR LIVE LOAD )FIXED SEATS) . . . . . . . . . . . 60 PSF <br />FLOOR LIVE LOAD )MOVABLE SEATS, PLATFORMS, LOBBIES, 6 OTHER). . 100 PER <br />OFFICES <br />FLOOR LIVE LOAD . . . . . . . . . . . . . . . . . . . . . . . . 50 PSF <br />FLUOR LIVE LOAD (CORRIDORS ABOVE FIRST FLOOR) . . . . . 80 PSF <br />FLUOR LIVE LOAD (LOBBIES AND FIRST -FLOOR CORRIDORS) . . . . . . 100 PSF <br />ROOF <br />ROOF LIVE LOAD . . . . . . . . . . . . . . . . . . . . . . . . . 25 PSF <br />MISCELLANEOUS LOADS <br />STAIR AND CORRIDOR LIVE LOAD (UNLESS OTHERWISE INDICATED) . . .100 PSF <br />DEFLECTION CRITERIA <br />LIVE LOAD DEFLECTION . . . . . . . . . . . . . . . . . . . . L/360 <br />TOTAL LOAD DEFLECTION . . . . . . . . . . . . . . . . . . . . . L/240 <br />3. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AM THE <br />METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES REQUIRED TO PERFORM THE <br />CONTRACTORS WORK. THE STRUCTURAL ENGINEER HAS NO OVERALL SUPERVISORY <br />AUTHORITY OR ACTUAL AND/OR DIRECT RESPONSIBILITY FOR THE SPECIFIC WORKING <br />CONDITIONS AT THE SITE AND/OR FOR ANY HAZARDS RESULTING FROM THE ACTIONS <br />OF ANY TRADE CONTRACTOR. THE STRUCTURAL ENGINEER HAS NO DUTY TO INSPECT, <br />SUPERVISE, NOTE, CORRECT, OR REPORT ANY HEALTH OR SAFETY DEFICIENCIES TO <br />THE OWNER, CONTRACTORS, OR OTHER ENTITIES OR PERSONS AT THE PROJECT SITE. <br />4. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR TEE STRUCTURE AND <br />STRUCTURAL COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN <br />ACCORDANCE WITH THE PLANS. CONFORM TO ASCE 37-14 "DESIGN LOADS ON <br />STRUCTURES DURING CONSTRUCTION'. <br />5. CONTRACTOR -INITIATED CHANGES SMALL BE SUBMITTED IN WRITING TO THE <br />ARCHITECT AND STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR <br />CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT SATISFY THIS <br />REQUIREMENT. <br />6. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE <br />CONDITIONS ME NOT SPECIFICALLY INDICATED BUT ARE OF SIMILAR CHARACTER TO <br />DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO <br />REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL ENGINEER. ALL <br />TYPICAL NOTES AND DETAILS SHOWN ON DRAWINGS SMALL APPLY, UNLESS NOTED <br />OTHERWISE. TYPICAL DETAILS MAY NOT NECESSARILY BE INDICATED ON THE PLANS <br />BUT SMALL STILL APPLY AS SHOWN OR DESCRIBED IN THE DETAILS. WHERE TYPICAL <br />DETAILS ARE NOTED ON THE PLANS, THE SPECIFIED TYPICAL DETAIL SHALL BE <br />USED. WHERE NO TYPICAL DETAIL IS NOTED, IT SMALL BE THE CONTRACTOR'S <br />RESPONSIBILITY TO CHOOSE THE APPROPRIATE TYPICAL DETAIL FROM THOSE <br />PROVIDED OR REQUEST ADDITIONAL INFORMATION. THE CONTRACTOR SHALL SUBMIT <br />ALL PROPOSED ALTERNATE TYPICAL DETAILS TO THOSE PROVIDED WITH RELATED <br />CALCULATIONS TO THE ENGINEER FOR APPROVAL PRIOR TO SHOP DRAWING PRODUCTION <br />AND FIELD USE. <br />T. ALL STRUCTURAL SYSTEMS, WHICH ARE TO BE COMPOSED OF COMPONENTS TO BE FIELD <br />ERECTED, SMALL BE SUPERVISED BY THE SUPPLIER DURING MANUFACTURING, <br />DELIVERY, HANDLING, STORAGE AND ERECTION IN ACCORDANCE WITH INSTRUCTIONS <br />PREPARED BY THE SUPPLIER. <br />13. REINFORCING STEEL SHALL CONFORM TO ASTM A615 (INCLUDING SUPPLEMENT SI), <br />GRADE 60, FY - 60,000 PSI. EXCEPTIONS: ANY BARS SPECIFICALLY SO NOTED ON <br />THE DRAWINGS SMALL BE GRADE 40, BY = 40,000 PSI. WELDED WIRE FABRIC SMALL <br />CONFORM TO ASTM A-185. SPIRAL REINFORCEMENT SMALL BE DEFORMED WIRE <br />CONFORMING TO ASTM A615, (SHARE 60, FY - 60,000 PSI. <br />14. DETAILING OF REINFORCING STEEL (INCLUDING NOOKS AND BENDS) SHALL BE IN <br />ACCORDANCE WITH ACT 315R-18 AND 318-14. LAP ALL CONTINUOUS REINFORCEMENT <br />45 AND SMALLER 40 BAR DIAMETERS OR 2'-0' MINIMUM. PROVIDE CORNER BARS AT <br />ALL WALL AND FOOTING INTERSECTIONS. LAP COMER BARS M5 AND SMALLER 40 BAR <br />DIAMETERS OR 2'-0" MINIMUM. LAPS OF LARGER BARS SMALL BE MADE IN <br />ACCORDANCE WITH ACI 318-14, CLASS B. LAP ADJACENT MATS OF NEEDED WIRE <br />FABRIC A MINIMUM OF B" AT SIDES AND ENDS. <br />NO BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SMALL BE FIELD BENT UNLESS <br />SPECIFICALLY SO DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER. <br />15. CONCRETE PROTECTION (COVER) FOR REINFORCING STEEL SHALL BE AS FOLLOWS: <br />FOOTINGS AND OTHER UNFORMED SURFACES CAST AGAINST AND PERMANENTLY <br />EXPOSED <br />TO EARTH . . . <br />. . . . <br />. . . . . <br />. . <br />. . . . . . . <br />. . . 3" <br />FORMED SURFACES <br />EXPOSED TO <br />EARTH OR WEATHER <br />1/6 <br />BARS OR LARGER) <br />. . 2" <br />FORMED SURFACES <br />EXPOSED TO <br />EARTH OR WEATHER <br />(i5 <br />BARS OR SMALLER). <br />. 1-1/2" <br />COLUMN TIES OR <br />SPIRALS AND <br />BEAM STIRRUPS <br />. . . . . . . <br />1-1/2' <br />SLABS AND WALLS <br />(INT. FACE). <br />. . GREATER OF <br />BAR <br />DIAMETER PLUS 1/8' <br />OR 3/4' <br />16. CONCRETE WALL REINFORCING- PROVIDE THE FOLLOWING UNLESS DETAILED <br />OTHERWISE: <br />6" <br />WALLS <br />Y4 @ <br />16 <br />HERIZ. <br />#4 @ <br />18 <br />VERTICAL <br />1 CURTAIN <br />8" <br />WALLS <br />Y4 @ <br />12 <br />HERIZ. <br />44 @ <br />18 <br />VERTICAL <br />1 CURTAIN <br />10" <br />WALLS <br />Y4 @ <br />18 <br />HORIZ. <br />44 @ <br />18 <br />VERTICAL <br />2 CURTAINS <br />12" <br />WALLS <br />Y4 @ <br />16 <br />SUITS. <br />44 @ <br />18 <br />VERTICAL <br />2 CURTAINS <br />ST. EXPANSION BOLTS INTO CONCRETE SMALL BE "STRONG -BOLT 2" WEDGE ANCHORS AS <br />MANUFACTURED BY THE SIMPSON STRONG TIE COMPANY AND INSTALLED IN STRICT <br />CONFORMANCE TO ICC-ES REPORT NUMBER ESR-3030, INCLUDING MINIMUM EMBEDMENT <br />REQUIREMENTS. BOLTS INTO CONCRETE MASONRY OR BRICK MASONRY UNITS SMALL BE <br />INTO FULLY GROUTED CELLS. PERIODIC SPECIAL INSPECTION IS REQUIRED TO <br />VERIFY ANCHOR TYPE, ANCHOR DIMENSIONS, ANCHOR LOCATION, TIGHTENING TORQUE, <br />HOLE DIMENSIONS, ANCHOR EMBEDMENT, AND ADHERENCE TO THE INSTALLATION <br />INSTRUCTIONS. <br />18. EPDXY -GROUTED ITEMS (THREADED RODS OR REINFORCING BAR) SPECIFIED ON THE <br />DRAWINGS SMALL BE INSTALLED USING 'SET-XP" HIGH STRENGTH EPDXY AS <br />MANUFACTURED BY THE SIMPSON STRONG, TIE COMPANY. INSTALL IN STRICT <br />ACCORDANCE WITH ICC-ES REPORT NO. ESR-2508. MINIMUM BASE MATERIAL <br />TEMPERATURE IS 50 DEGREES, F. RODS SMALL BE ASTM A-36 UNLESS OTHERWISE <br />NOTED. PERIODIC SPECIAL INSPECTION OF INSTALLATION IS REQUIRED TO VERIFY <br />ANCHOR OR EMBEDDED BAR TYPE AND DIMENSIONS, LOCATION, ADHESIVE <br />IDENTIFICATION AND EXPIRATION, HOLE DIMENSIONS, HOLE CLEANING PROCEDURE, <br />ANCHOR EMBEDMENT, AND ADHERENCE TO THE INSTALLATION INSTRUCTIONS. <br />CONTINUOUS SPECIAL INSPECTION IS REQUIRED FOR HORIZONTAL AND OVERHEAD <br />INSTALLATIONS. <br />19. EPDXY-GROUTEC ITEMS (THREADED RODS OR REINFORCING BAR) SPECIFIED ON THE <br />DRAWINGS SMALL BE INSTALLED USING "AT-XP" AS MANUFACTURED BY SIMPSON <br />STRONG -TIE COMPANY. INSTALL IN STRICT ACCORDANCE WITH IAMPO REPORT NO. ER- <br />0281. MINIMUM BASE MATERIAL TEMPERATURE IS 14 DEGREES, F. RODS SMALL BE <br />ASTM A-36 UNLESS OTHERWISE NOTED. PERIODIC SPECIAL INSPECTION OF <br />A. 318-14, SECTION 20.2.2.5, AND REQUIRE TESTING PER 1705.13.3 OF THE <br />INTERNATIONAL BUILDING CODE. <br />B. STRUCTURAL STEEL USED IN MOMENT FRAMES AND BRACED FAMES SMALL BE IN <br />ACCORDANCE WITH THE QUALITY ASSURANCE REQUIREMENTS OF AISC 341. <br />GEOTECHNICAL <br />8. FOUNDATION NOTES: ALLOWABLE SOIL PRESSURE AND LATERAL EARTH PRESSURE ARE <br />ASSUMED AND THEREFORE MUST BE VERIFIE➢ BY A QUALIFIED SOILS ENGINEER OR <br />APPROVED BY THE BUILDING OFFICIAL. IF SOILS ARE FOUND TO BE OTHER TEAM <br />ASSUMED, NOTIFY THE STRUCTURAL ENGINEER FOR POSSIBLE FOUNDATION REDESIGN. <br />FOOTINGS SHALL BEAR ON FIRM, UNDISTURBED EARTH AT LEAST 18" BELOW ADJACENT <br />FINISHED GRADE. UNLESS OTHERWISE NOTED, FOOTINGS SHALL BE CENTERED BELOW <br />COLUMNS OR WALLS ABOVE. <br />BACKSIDE BEHIND ALL RETAINING WALLS WITH FREE DRAINING, GRANULAR FILL AND <br />PROVIDE FOR SUBSURFACE DRAINAGE. <br />ALLOWABLE SOIL PRESSURE. <br />. . . . . <br />. . . 1500 <br />PSF <br />LATERAL EARTH PRESSURE <br />(RESTRAINED/UNRESTRAINED) . . . <br />. . . . 35 <br />PCP <br />ALLOWABLE PASSIVE EARTH <br />PRESSURE (FS OF 1.5 EXCLUDED). . . . <br />. . . 350 <br />PCF <br />COEFFICIENT OF FRICTION <br />(IS OF 1.5 EXCLUDED). . . . . . . . <br />. . . .0.45 <br />SEISMIC SURCHARGE PRESSURE <br />(UNIFORM LOAD) . . . . . . . . . <br />. . . . TH <br />PER <br />RENOVATION <br />9. DEMOLITION: CONTRACTOR SMALL VERIFY ALL EXISTING CONDITIONS BEFORE <br />COMMENCING ANY DEMOLITION. SHORING SMALL BE INSTALLED TO SUPPORT EXISTING <br />CONSTRUCTION AS REQUIRED AND IN A MANNER SUITABLE TO THE WORK SEQUENCES. <br />DEMOLITION DEBRIS SHALL NOT BE ALLOWED TO DAMAGE OR OVERLOAD THE EXISTING <br />STRUCTURE. LIMIT CONSTRUCTION LEADING (INCLUDING DEMOLITION DEBRIS) ON <br />EXISTING FLOOR SYSTEMS TO 40 PER. <br />10. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES, AND <br />CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING <br />CONSTRUCTION SHOWN ON THE DRAWINGS ARE INTENDED AS GUIDELINES ONLY AND <br />MUST BE VERIFIED. THE CONTRACTOR SMALL NOTIFY THE ARCHITECT AND STRUCTURAL <br />ENGINEER IF EXISTING CONDITIONS DETERMINED DURING WORK VARY FROM THE <br />EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS. <br />CONCRETE <br />11. CONCRETE SMALL BE MIXED, PROPORTIONED, CONVEYED AND PLACED IN ACCORDANCE <br />WITH ACI 301, INCLUDING TESTING PROCEDURES. CONCRETE SMALL ATTAIN A 28-DAY <br />STRENGTH OF f'C - 3,000 PSI AND MIX SRALL CONTAIN NOT LESS THAN 5-1/2 <br />SACKS OF CEMENT PER CUBIC YARD AND SMALL BE PROPORTIONED TO PRODUCE A <br />SLUMP OF 5" OR LESS. REQUIRED CONCRETE STRENGTH IS BASED ON THE DURABILITY <br />REQUIREMENTS OF BECTION 1904 OF SHE IBC. DEBIGN STRENGTH IS f'C 2,500 <br />PSI. <br />12. ALL CONCRETE WITH SURFACES EXPOSED TO WEATHER OR STANDING WATER SMALL BE <br />AIR -ENTRAINED WITH AN AIR -ENTRAINING AGENT CONFORMING TO ASTM C260, C494, <br />AND ISIS. TOTAL AIR CONTENT FOR FROST -RESISTANT CONCRETE SHALL BE IN <br />ACCORDANCE WITH ACI 318-14, PARIS 19.3.2.1 MODERATE EXPOSURE. F1. <br />INSTALLATION IS REQUIRED TO VERIFY ANCHOR OR EMBEDDED BAR TYPE AND <br />DIMENSIONS, LOCATION, ADHESIVE IDENTIFICATION AND EXPIRATION, HOLE <br />DIMENSIONS, HOLE CLEANING PROCEDURE, ANCHOR EMBEDMENT, AND ADHERENCE TO <br />THE INSTALLATION INSTRUCTIONS. CONTINUOUS SPECIAL INSPECTION IS REQUIRED <br />FOR HORIZONTAL AND OVERHEM INSTALLATIONS. <br />20. CONCRETE SCREW ANCHORS INTO CONCRETE AND CONCRETE MASONRY UNITS SHALL BE <br />"TITEN HD" HEAVY DUTY SCREW ANCHOR AS MANUFACTURED BY THE SIMPSON STRONG - <br />TIE COMPANY, INSTALLED IN STRICT ACCORDANCE WITH ICC-ES REPORT NO. ESR- <br />2713 (CONCRETE), NO. ESR-1056 (CMU), INCLUDING MINIMUM EMBEDMENT <br />REQUIREMENTS. SCREW ANCHORS INTO CONCRETE MASONRY UNITS SMALL BE INTO <br />FULLY GROUTED CELLS. SPECIAL INSPECTION IS REQUIRED. <br />STEEL <br />21. STRUCTURAL STEEL DESIGN, FABRICATION, AM ERECTION SHALL BE BASED ON: <br />A. AISC 360-16 AND SECTION 2205.2 OF THE INTERNATIONAL BUILDING CODE. <br />B. JUNE 15, 2016 AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND <br />BRIDGES AMENDED AS FOLLOWS: AS NOTED IN THE CONTRACI DOCUMENTS, BY THE <br />DELETION OF PARAGRAPH 4.4.1, AND REVISE REFERENCE FROM "STRUCTURAL <br />DESIGN DRAWINGS" TO "CONTRACT DOCUMENTS" IN PARAGRAPH 3.1. <br />C. SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS. <br />22. WIVE FLANGE SHAPES SHALL CONFORM TO ASTM A992, BY = 50 KSI. OTHER ROLLED <br />SHAPES INCLUDING PLATES, SHALL CONFORM TO ASTM ASS, FY = 36 ESI. STEEL <br />PIPE SHALL CONFORM TO ASTM A-53, TYPE E OR S, GRADE B, BY 35 ESI. <br />STRUCTURAL TUBING SMALL CONFORM TO ASTM MOO, GRADE Be FY - 42 KSI <br />(ROUND), FY - 46 KSI (SQUARE AND RECTANGULAR). CONNECTION BOLTS SMALL <br />CONFORM TO ASTM A307. <br />23. ALL STEEL EXPOSED TO THE WEATHER OR IN CONTACT WITH GROUND SMALL BE <br />CORROSION PROTECTED BY GALVANIZATION OR PROVIDED WITH EXTERIOR PAINT <br />SYSTEM, UNLESS OTHERWISE NOTED. <br />24. SHOP PRIME ALL STEEL EXCEPT: <br />A. STEEL ENCASED IN CONCRETE. <br />B. SURFACES TO BE WELDED. <br />C. CONTACT SURFACES AT HIGH -STRENGTH BOLTS. <br />D. MEMBERS TO BE GALVANIZED. <br />E. MEMBERS WHICH WILL BE CONCEALED BY INTERIOR FINISHES. <br />F. SURFACES TO RECEIVE SPRAYED FIREPROOFING. <br />G. SURFACES TO RECEIVE OTHER SPECIAL SHOP PRIMERS. <br />777411M <br />Property Line Retaining Wall Schedule <br />H (ff.) <br />B2 <br />is <br />H <br />Stem Reinforcing <br />Footing Reinforcing <br />Vert. Horiz. <br />Top <br />Longit. <br />4'-D" <br />V-V <br />r <br />V <br />µ 0111 <br />µ 012-m <br />µ 01rac <br />(2)04 <br />E'-r <br />4'-r <br />as <br />1r <br />µ o 12'04 <br />µ ii Dew <br />IS 01rm <br />wo <br />11/2 . clr. 0 14's k J5ds <br />2' dr. 0 16's <br />E 1 1 1 � BROTHERS <br />R <br />NOTE TO ENGINEER <br />SEISMIC SURCHARGE = IN PSF <br />SOIL DENSITY = 125 PCG <br />EQUIVALENT FLUID PRESSURE = 35 PCF <br />STRUCTURAL W <br />MINIMUM SOIL RESISTANCE = 150 PPS (WITHOUT FACTOR OF SAFETY) <br />/NGINEERING COEFFICIENT <br />CI NT OF FRI FRICTION <br />BEARING = 0.45 PSF <br />COEFFlDENi OF FRIC➢ON = 0.45 (WITHOUT FACTOR 6 SAREtt) <br />2124 Third Avenue -Suite lee Seattle, WA 98121 <br />N2o6.a,W6z¢ ssiengineers.com <br />File I Co-04-09a Scale 3/4" = 1'-0" Title Property Line Retaining Wall Boxes Two <br />ING NALL <br />1 SCALE: TUTSI x-wall-cant-retain-21 <br />SE.-" <br />Z a <br />D Z <br />Ow <br />U 0 <br />U <br />v' Q <br />seem <br />2 <br />Oa <br />2 <br />aa O <br />Ole M <br />V / w = > Q <br />�U~�Do <br />n_Q O H Q Q Y <br />U_ <br />w a�n �w <br />W - �a <br />> _. 0 <br />Uwaw <br />�!'ctL <br />JOB NUMBER: 2156 <br />DRAWN: RICH <br />CHECKED: <br />SHEET TITLE: <br />STRUCTURAL <br />NOTES & <br />DETAILS <br />PERMIT SET <br />SHEET NUMBER: <br />S100 <br />