Bldg 101 Panel <br /> Forest Park <br /> 205 Park Rd Bldg <br /> 130 Everett, WA <br /> 98203 <br /> PANEL Bldg 101 FEEDER <br /> FED FROM MAIN SWITCHBOARD NUMBER OF CONDUITS 1 <br /> #CIRCUITS 20 FEEDER CONDUIT 1 1/4" <br /> HI VOLTAGE 240 WIRE SIZE L1 #1 <br /> LOW VOLTAGE 120 WIRE SIZE L2 #1 <br /> PHASE 1 <br /> DESIGN LOAD AMPS 126 WIRE SIZE NEUTRAL #1 <br /> NEUTRAL BUS YES WIRE SIZE GROUND #6 <br /> GROUND BUS YES <br /> AVAILABLE FAULT CURRENT AT THIS PANEL 11,033 <br /> MAIN BREAKER SIZE AMPS 150 <br /> # BKR CIRCUIT DESCRIPTION I VA VA I CIRCUIT DESCRIPTION BKR # <br /> 1 20 NW office lights&plugs D 360 L1 5,000 G Furnace 60A-2P 2 <br /> 3 20 SE office recep D 360 L2 5,000 G 1 1 4 <br /> 5 20 NW office recep D 360 L1 360 D Receps 20 6 <br /> 7 20 Recep D 360 L2 100 C Hall Lights 20 8- <br /> 9 20 Recep D 360 L1 200 C Office lights 20 10 <br /> 11 20 Recep D 360 L2 360 D Receps 20 12 <br /> 13 20 Lights C 200 L1 200 D Alarm 20 14 <br /> 15 igh s cc: 0 2 G <br /> 17 40A-2P EVSE G 3,840 L1 3,840 G EVSE 40A-2P 18 <br /> 19 1 G 3,840 L2 3,840 G 1 1 20 <br /> NEW <br />