Laserfiche WebLink
Lntertok <br />Total Quality. Assured. <br />TEST REPORT FOR WESTWOOD INVESTORS, LLC <br />Project No.: N8834.01-901-43 <br />Date:06/02/23 <br />22155 68th Avenue South <br />Kent, Washington 98032 <br />BASELINE <br />NOMINAL <br />ADJUSTED <br />BUILDING <br />BUILDING <br />NOMINAL <br />ADJUSTED <br />PRESSURE <br />PRESSURE <br />FLOW <br />FLOW <br />(Pa) <br />(Pa) <br />(cfm) <br />(cfm) <br />% ERROR <br />AVG. PRE- <br />BASELINE <br />-0.6 <br />- <br />- <br />- <br />- <br />-49.8 <br />-49.3 <br />1,483 <br />1,458 <br />0.4 <br />-55.1 <br />-54.5 <br />1,562 <br />1,535 <br />-0.2 <br />-60.0 <br />-59.4 <br />1,638 <br />1,610 <br />-0.5 <br />INDUCED TEST <br />-65.0 <br />-64.4 <br />1,728 <br />1,698 <br />0.2 <br />PRESSURES <br />-70.0 <br />-69.5 <br />1,799 <br />1,768 <br />-0.2 <br />-74.9 <br />-74.4 <br />1,883 <br />1,851 <br />0.4 <br />AVG. POST <br />BASELINE <br />-0.5 <br />- <br />- <br />- <br />- <br />AIR LEAKAGE COEFFICIENT, C <br />150.3 <br />EXPONENT, n it0.582 <br />CORRELATION COEFFICIENT, r <br />0.99911 <br />EQLA' at 10 Pa (in') <br />168.5 <br />ELA2 at 4Pa (inZ) <br />95.5 <br />AIRFLOW at 75 Pa <br />1,852 <br />AIR LEAKAGE PER ENCLOSURE AREA <br />at 75 Pa, (cfm/ftZ) <br />MEAN <br />95% CONFIDENCE INTERVAL <br />LOWER <br />UPPER <br />0.203 <br />0.202 <br />0.205 <br />1. EQLA— Equivalent Leakage Area <br />2. ELA — Effective Leakage Area <br />Page 7 of 18 <br />