Laserfiche WebLink
SHEARWALL & HOLDOWN NOTES (U.N.O.) : <br />(1) Simpson or equal. Locate at end of shearwall u.n.o. Install <br />per manufacturer recommendations for foundation minimum end <br />distance and embedment, deepen foundation as required. <br />(2) Construct cripple wall same as shearwall (SW) above, and <br />gable -end same as shearwall (SW) below. <br />(3) Requires 3x or (2) 2x foundation sill plate <br />(4) Threaded rod and coupler as required. <br />(5) Common nails, UNO: 8d=0.131"x2'/z", 10d=0.148"x3", <br />12d=0.148"x3'/", 16d=0.162"x3'/Z", 16d sinker-0.148"x3%". <br />Install 1­11's on all trusses/rafters, A35's at 24"o/c on gables & <br />joist (or solid blkg) to top plate (sill plate at fdn) u.n.o.; When <br />cified spacing is less than 24"o/c, install A35's at roof solid <br />ing to SW top plate, and install H1 or H2.5 on all <br />;ses/rafters. LTP4, LTP5 or LS50 can be substituted for A35. <br />in. per Simpson Strong -Tie or equal. <br />Minimum 3x or dbl-2x stud lam'd w/ (2)-16d @ 6" o/c at <br />tting panel edges. <br />Anchor bolts shall be embedded at least 7" into concrete; <br />e shall be a minimum of two bolts per piece with one bolt <br />ited not more than 12" or less than seven bolt diameters from <br />h end of the piece. 2x min PT, u.n.o. <br />HOLDOWN SCHEDULE Date: 5/9/2022 <br />Job #: 1425 <br />HOLDOWN / <br />FASTENERS TO <br />FOUNDATION <br />MARK <br />STRAP *(1) <br />(2)-STUDS MIN U.N.O. <br />ANCHOR *(1)(4) <br />COMMENTS <br />T-1 <br />MSTC66 <br />(32) - 16d sinkers to each <br />N/A <br />connected element <br />T-2 <br />STHD14/14RJ <br />(38)/(30) - 16d <br />N/A <br />T-3 <br />HDU8-SDS2.5 <br />(20) - SDS 0.25x2.5 <br />SSTB28 <br />MIN. DF#2 4X POST <br />WOOD SCREWS <br />hT�oF WA <br />� N . <br />4422D pJ <br />ss/WNAL <br />U ECG <br />11 i23iZC 22_ <br />SHEARWALL SCHEDULE Date: 5/9/2022 <br />Job #: 1425 <br />MARK <br />(2) <br />SHEATHING - APPLY TO <br />2x HF STUDS @ 16"o/c <br />U.N.O. BELOW *(9) <br />SHEATHING EDGE NAILS *(5) <br />ALL EDGES BLOCKED <br />(do not penetrate past flush) <br />BASE PATE <br />NAILS * (5) <br />ROOF TO TOP PLATE, <br />FLOOR TO TOP PLATE <br />& SILL PLATE *(6) <br />SILL PLATE ANCHORS <br />3" x 3" x 1/4" WASHERS *(8(8 ) <br />SW-1 <br />7/16" OSB <br />8d @ 6" o/c (12" o/c field) <br />16d @ 12 " o/c <br />HI @ 24 " o/c <br />or A35 (& 24 " o/c <br />5/8"OxI0" AB's @ 60 " o/c <br />SW-2 <br />7/16" OSB <br />8d @ 4" o/c (12" o/c field) <br />16d @ 6 " o/c <br />A35 @ 20 " o/c <br />5/8" Ox10" AB's @ 48 " o/c <br />SW-3 <br />7/16" OSB *(7) <br />8d @ 3" o/c (12" o/c field) <br />16d @ 4 " o/c <br />A35 @ 12 " o/c <br />5/8"OxI0" AB's @ 32 " o/c <br />RSW <br />7/16" OSB *(7) <br />8d @ 3" o/c (12" o/c field) <br />SEE DETAIL 1 <br />