N <br /> r � <br /> N <br /> U GENERA NOTEs: FIRE ALARM SYMBOL LEGEND 3 J <br /> Mathew Buntin L3 1. THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE ARCHITECTURAL DRAWINGS FOR NOTE ALL SYMBOUS MAY NOT BE USED ON THIS eR01Ecr ti <br /> er " NICET#144348 0 EXACT DIMENSIONS. SYMBOL DESCRIPTION QTY MOUNTING LLI p o <br /> CERTIFIED Fire Alarmz o 2. INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND ALL OTHER APPLICABLE CODES FACP FIRE ALARM CONTROL PANEL EXISTING 1 WALL-TOP @ 66' v) 00 <br /> Systems Level III AS REQUIRED BY THE LOCAAUTHORITY HAVING JURISDICTION. LLI _� W <br /> o QL Ato 2 <br /> OPERATIONS o r - [T] TAMPER SWITCH 3 FIELD VERIFY Q L w '_ <br /> MATRIX J o - a _ 3. WIRING DEPICTED ON THESE PLANS IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY © MANUAL PULL STATION EXISTING l0 WALL @ 48" <br /> DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING th in <br /> - ¢ o CONSTRUCTION CONDITIONS ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA wF WATER Flow SWITCH 3 FIELD VERIFY c W M <br /> ® z - _ SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS CEILING MOUNT STROBE EXISTING 9 FIELD VERIFY N Q CD o <br /> S2CUflty Solutions CD m _ m - = LONG AS NO 11 OV OR HIGHER VOLTAGE CABLES ARE IN THE SAME RACEWAY. v _1 00 a <br /> ® STROBE EXISTING 26 WALL 80"-96" <br /> a 4. FIRE RATINGS SHALL BE MAINTAINED FOR ALL PENETRATIONS THROUGH FIRE-RATED <br /> > < o CONSTRUCTION USING APPROVED LISTED FIRESTOP SYSTEM. ABBREVIATION DESCRIPTION Ep q p o� <br /> lr� <br /> � o E EXISTING wA7AGESS �CANDEELA�1tN TT/lFIRE ALARM INPUT i < < 5. POWER FOR ALL FIRE ALARM PANELS AND FIRE ALARM POWER SUPPLIES MUST BE (w) vs 3o W(.CAiW ¢ �' " PROVIDED BY A DEDICATED AC BRANCH CIRCUIT. THE LOCATION OF THE BRANCH G WITH NT M J No.laasaa vnuomw o3ro uzozs SMOKE DETECTORS SPOT OR BEAM • • ¢ • • • • • • P PENDENT MOUNT L <br /> ( ) CIRCUIT BREAKER SHALL BE PERMANENTLY IDENTIFIED AT THE CONTROL UNIT AND R RESIDENTIAL 11oV 2 DEVICE ADDRESS-,,Q >, <br /> DUCT DETECTORS • • • • • SHALL HAVE A RED MARKING IN ACCORDANCE WITH NFPA 72. S SOUNDER BASE LlDO01 OR D01 Q <br /> PULL STATIONS • • • • • • • <br /> WE WEATHER PROOF (D or M-(DENOTES DETECTOR oR-DENOTES LOOP <br /> )MODULE q) d <br /> 6. POWER-LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST REMAIN SEPARATED EOL END OF LINE RESISTOR <br /> MONITORING SERVICE PROVIDED BY: WATERFLOW SWITCHES • • • • • • • IN CABINET. ALL POWER-LIMITED CIRCUIT WIRING MUST REMAIN AT LEAST 0.25" AWAY EOLR END OF LINE RELAY <br /> FROM ANY NONPOWER-LIMITED CIRCUIT WIRING. FURTHERMORE, ALL POWER-LIMITED AWG AMERICAN E GAUGE -#1s 2 WP <br /> WIR <br /> ALARM CENTER, INC. VALVE SUPERVISORY SWITCHES • • • -_ WIRE 111E A1111TA1ED <br /> AND NONPOWER-LIMITED CIRCUIT WIRING MUST ENTER AND EXIT THE CABINET TWP TWISTED PAIR WIRECORTH1oR DOUNt <br /> PO BOX 3407 FIRE ALARM AC POWER FAIL • • • THROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS. TWSP TWISTED SHIELDED PAIR WIRE SIZE <br /> FPLP FIRE POWER LIMITED PLENUM N DE CABLES IF OM17ED <br /> LACEY,WA 98509-3407 FIRE ALARM LOW BATTERY • • • 7. WHEN UTILIZING CLASS "A" CIRCUITS, SEPARATE OUTGOING AND RETURN CONDUCTORSONLY l CABLE NEEDED) <br /> FPLR FIRE POWER LIMITED RISER <br /> PHONE:(800)238-9I 2G OPEN CIRCUIT • • • OF CLASS A" CIRCUITS BY A MINIMUM OF 12" WHERE RUN VERTICALLY AND 48" <br /> FAX:(3GO 438-4244 GROUND FAULT • • • WHERE RUN HORIZONTALLY. <br /> NAC SHORT CIRCUIT • • • 8. WHEN UTILIZING SHIELDED CABLE TIE SHIELDS THROUGH AND INSULATE AT EACH <br /> LOSS OF AC To BUILDING • • • • JUNCTION BOX. INSULATE AND TAPE BACK AT END. o <br /> .Q <br /> BUILDING DATA Note FIRE AARM coNTROL PANEL Is EXISTING To REMAIN.THE INPUTS SHOWN AeovE 9. ALL FIRE ALARM CABLING SHALL BE ACCEPTABLE TO THE FIRE ALARM EQUIPMENT <br /> MANUFACTURER FOR THE INTENDED PURPOSE. w <br /> ARE FOR THE INITIATING EQUIPMENT BEING ADDED AND/OR MODIFIED AND MAY d <br /> NOT REFLECT ALL EXISTING INITIATING INPUTS OR OUTPUTS CONNECTED To THE C3 <br /> 80th St.SW 10. SMOKE DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER CONSTRUCTION CLEAN-UP <br /> ADDRESS: Everett,WA 98203-7002 EXISTING FACE. CONTRACTOR SHALL FIELD VERIFYEXISTING EQUIPMENT IF REQUIRED. IS COMPLETED AND FINAL. <br /> PARCEL#: 01130400010000 11. LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL <br /> AREA: I G,GG3 PT2/2,G33PT2 DIFFUSERS. WALL-MOUNTED SMOKE DETECTORS SHALL BE LOCATED A MINIMUM OF m <br /> TYPE Of CON5T: Ma5onary Horn Tones and Sound Output Data 4" AND A MAXIMUM OF 12" FROM CEILING. <br /> Horn and Horn Strobe Output(dSA) <br /> OCCUPANCY: G37 Warehou5ing#Storage Service 8-175 16-33 24-Volt Nominal 12. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS. Q <br /> Switch volts volts Reverberant Anechoic PROVIDE ALL REQUIRED SYNC MODULES. PROVIDE A MULTI-SYNC MODE SLAVE <br /> Position sound pattern dB Dc FWR Dc FWR Dc FWR Dc FWR CONNECTION BETWEEN ALL SYNC MODULES. <br /> 1 Temporal High 78 78 84 84 88 88 99 98 <br /> 2 Temporal Medium 74 74 80 80 86 86 96 96 13. VERIFY ALL FIELD SELECTABLE AUDIBILITY SETTINGS OF NOTIFICATION APPLIANCES <br /> KEY MAP 3 Temporal Low 71 73 76 76 83 80 94 89 WITH FIRE ALARM CONTRACTOR. <br /> 4 Non-Temporal High 82 82 88 88 93 92 100 100 <br /> QMahalIndian Cmafne 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 14. UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING, <br /> Snohomish County PUD 6 Non-Temporal Low 75 75 81 81 88 84 96 92 <br /> Q oderatronsCenter �. s p THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING OF THE ENTIRE SYSTEM, <br /> _ 7r Coded High 82 82 88 88 93 92 101 101 PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A FINAL FIRE N N <br /> Br Coded Medium 76 78 85 85 90 90 97 98 N N <br /> ALARM SYSTEM INSPECTION. <br /> 9t Coded Low 75 75 81 81 88 85 96 92 r C r N <br /> t6ettings 7,8,and 9 are not available on 2-wire horn strobes. 0 N <br /> 15. PROVIDE OFF-SITE MONITORING AS REQUIRED BY THE INTERNATIONAL FIRE CODE, rn <br /> Achilles USA9 . % :, SECTION 907.6.5 AND THE LOCAL AUTHORITY HAVING JURISDICTION. a a a <br /> u`r FJV 16. INSTALLING CONTRACTOR SHALL, PHYSICALLY, LABEL ALL INITIATING DEVICES AND > a > <br /> United States© TABL.EA.18.4.3 Awmge Ambient Sound Level Acco tiling NOTIFICATION APPLIANCE CIRCUIT END OF LINE (WHEN WIRING CLASS "B"). THESE z° t- p z° 4 <br /> PustalSerVice to Location LABELS SHALL BE IN PLACE PRIOR TO START-UP AND TESTING. <br /> gpeln9F., Crystal Springs r <br /> Arco Apanments Aivmge Ambient m s ra c <br /> ✓i` ® Lorxrtion Sourrd L-1fdI O 2 <br /> J Gsvro atl ` WCeslno ad v Mrs cats U2021 N 3 in <br /> Business occupancies 55 p� p` y ' iy p d j <br /> 1111 80th St SW Educational occupancies 45 <br /> Everett,WA 98203 Dvections Industrial occupancies 80 <br /> Institutional occupancies 50 <br /> Mercantile occupancies 40 <br /> Mechanical moms 85 <br /> Piers and water-suarounded structures 40 SCOPE OF WORK <br /> VICINITY MAP PI aces of assembly 55 THE SCOPE OF WORK SHALL INCLUDE THE INSTALLATION OF THREE NEW WATER FLOW SWITCHES AND <br /> Residential occupancies 35 3 NEW TAMPER SWITCHES TO THE EXISTING ALARM SYSTEM. UPON COMPLETION OF THE <br /> Storage occupancies 30 INTERCONNECTION A TEST WILL BE PERFORMED TO ENSURE THAT THE FIRE ALARM PANEL <br /> Thoroughfares,high-density urban 70 AS-WELL-AS THE MONITORING CENTER ARE RECEIVING SIGNALS. THE EXISTING NOTIFICATION AND <br /> Thoroughfares,rnedium-density urban 55 SIGNALING APPLIANCE ARE SHOWN. <br /> i / • Thoroughfares,rural and suburban 40 <br /> _ t Tower occupancies 35 N o <br /> r Underground strucnsres and 40 <br /> ' windowless buildings = o <br /> ' Vehicles and vesse is 50 o <br /> M � <br /> ,r C Cl) 00 � <br /> ZI c ,cam > °' M <br /> ' � tnQt- <br /> po <br /> U o m m <br /> as � <br /> Q > ca <br /> r LU d <br /> d <br /> E <br /> A <br /> z <br /> v <br /> v <br /> 'o <br /> a` <br /> Sheet Number <br /> TITLE <br /> 1 of 3 <br />