Laserfiche WebLink
NEUDORFER r - <br /> NE�B:B <br /> ENGINEERS <br /> WWW.NEUDDRFERENGINEERS,COM <br /> AN �tegra COMPANY <br /> Energy Recovery Unit <br /> PROJECT: Mountain Pacific Bank Office TI DATE: 8/3/2023 <br /> LOCATION: Everett,WA CONTACT: Tony Amort <br /> PROJECT#: 2023-0783 AUTHOR: <br /> ERV-01 Supply Outlet Summary <br /> System/Unit Area Served Type of Outlet Size LxW/D AK Design Prelim Final Final% Remarks <br /> Reading Type Airflow Airflow Airflow <br /> Outlet-01 Office 105 Flowhood CD-1 4" 1.00 11 40 18 164 <br /> Outlet-02 Office 106 Flowhood CD-1 4" 1.00 11 30 18 164 <br /> Outlet-03 Open Office Flowhood CD-2 6" 1.00 68 70 100 147 <br /> 113 <br /> Outlet-04 Office 101 Flowhood CD-1 4" 1.00 11 20 17 155 <br /> Outlet-05 Office 102 Flowhood CD-1 4" 1.00 11 20 18 164 <br /> Outlet-06 Office 103 Flowhood CD-1 4" 1.00 11 35 18 164 <br /> Outlet-07 Office 104 Flowhood CD-1 4" 1.00 11 15 18 164 <br /> Outlet-08 Facilities 110 Flowhood CD-1 4" 1.00 11 40 25 227 (2) <br /> Outlet-09 IT/Server 107 Flowhood CD-2 1 6" 1.00 68 1 70 1 95 1 140 (1) <br /> Totals: - - - - 213 340 327 154 <br /> ERV-01 Exhaust Inlet Summary <br /> System/Unit Area Served Type of Inlet Size LxW/D AK Design Prelim Final Final% Remarks <br /> Reading Type Airflow Airflow Airflow <br /> Inlet-01 IT/Server 107 Flowhood EG-1 8" 1.00 200 330 180 90 (1) <br /> Inlet-02 Open Office Flowhood EG-1 6" 1.00 58 115 60 103 <br /> 113 <br /> Inlet-03 Restroom 108 Flowhood EG-1 6" 1.00 50 100 55 110 <br /> Totals: - 308 545 295 96 - <br /> Neudorfer Engineers <br />