M <br /> GENERAL NOTES: <br /> L <br /> FIRE ALARM SYMBOL LEGEND 1. SCOPE OF WORK: THIS PROJECT SHALL INCLUDE THE REPLACEMENT OF AN <br /> E r4 i c <br /> NOTE a MBa a7 NOT BE USED ON THIS BBaECT F•k " EXISTING SILENT KNIGHT 5207 FACP FOR A NEW POTTER AFC-1000 FACP, AND <br /> �•�� THE ADDITION OF AN AES RADIO COMMUNICATOR. ALL FIELD DEVICES SHALL REMAIN <br /> SYMBOL DESCRIPTION MANUF. & PART # MOUNTING MOUNT INQTY A` t ' ; 1 �x u' Mf THE SAME. <br /> FACP FIRE ALARM CONTROL PANEL POTTER-AFC-1000 WALL-TOP 0 66° CABINET INCLUDED 1 - +••. R - <br /> 2. THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE ARCHITECTURAL DRAWINGS Z <br /> COM FIRE ALARM COMMUNICATOR AES-AES-7707P-88-ULP-M WALL-TOP 0 66" ICABINET INCLUDED 1 - ♦ •ri Ff FOR EXACT DIMENSIONS. o <br /> ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION rAm�ss�© ty. w ° 3. INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND ALL OTHER APPLICABLE <br /> E EXISTING AWG I AMERICAN WIRE GAUGE LIS001 OR pM01 ., *� r. W CODES AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. c <br /> G WITH GUARD TWP TWISTED PAIR (L-DENOTES LOOP It" - <br /> (s a 11-oENOEES SENSOR o MODULE f) `t< " 4. WIRING DEPICTED ON THESE PLANS IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY o <br /> P PENDENT MOUNT TWSP TWISTED SHIELDED PAIR " <br /> R RESIDENTIAL 11ov FPLP I FIRE POWER LIMNED PLENUM 1-#16/2 TWP `• DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING W <br /> S SOUNDER BASE FPLR FIRE POWER LIMITED RISER �WRE YPEABBRLVAEED CONSTRUCTION CONDITIONS ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA N <br /> WP WEATHERPROOF CONDUCTOR COUNT X . . -, 'T<_; • SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS ti <br /> N flE SIZE <br /> { - F <br /> t <br /> .V .i� x <br /> EOL END OF LINE RESISTOR15r .3 +.�J LONG AS NO 110V OR HIGHER VOLTAGE CABLES ARE IN THE SAME RACEWAY. o <br /> I OF CABLES(IF OMITTED ���``` � •• <br /> EOLR END OF LINE RELAY bNLr t CABLE NEEDED) i 1: I'•a� _�: r3 r •' > c <br /> • f � rf"t 5. FIRE RATINGS SHALL BE MAINTAINED FOR ALL PENETRATIONS THROUGH FIRE-RATED > <br /> i CONSTRUCTION. w <br /> r / i �• �T, 6. POWER FOR ALL FIRE ALARM PANELS AND FIRE ALARM POWER SUPPLIES MUST BE oo <br /> PROVIDED BY A DEDICATED AC BRANCH CIRCUIT. THE LOCATION OF THE BRANCH Z <br /> co <br /> CIRCUIT BREAKER SHALL BE PERMANENTLY IDENTIFIED AT THE CONTROL UNIT, O <br /> g #1 MECHANICALLY PROTECTED, ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL AND <br /> o x SHALL BE RED AND LABELED FIRE ALARM CIRCUIT CONTROL" IN ACCORDANCE � <br /> a w z N x SBt� x ,+ WITH NFPA 72. ELECTRICAL CONTRACTOR SHALL PERFORM LOAD CALCULATIONS TO <br /> OPERATIONS a a w U w DETERMINE SIZE OF WIRING AND BREAKERS FOR ALL FIRE ALARM AC BRANCH <br /> 4 LL o z CIRCUITS BASED ON THE INFORMATION PROVIDED IN THE BATTERY CALCULATIONS <br /> MATRIX T FOR THE FIRE ALARM EQUIPMENT. u o <br /> H N — N W r <br /> ExISTING sysTEM oPERAnorls SHALL y " < " x r y- a 7. POWER-LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST REMAIN SEPARATED Z <br /> REMAIN,FIELD VERIFY ACTUAL SYSTEM o y z o y o o ,y _ _ - - _ IN CABINET. ALL POWER-LIMITED CIRCUIT WIRING MUST REMAIN AT LEAST 0.25" <br /> OPERATIONS =o = w w m w m ' -i �•. -'"'• ;x AWAY FROM ANY NONPOWER-LIMITED CIRCUIT WIRING. FURTHERMORE, ALL — w <br /> m IN � s a s � c a � F < � � Y f� � x »� � POWER-LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST ENTER AND EXIT � E- <br /> g THE CABINET THROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS. d <br /> 8. WHEN UTILIZING CLASS "A" CIRCUITS, SEPARATE OUTGOING AND RETURN (n zn <br /> FIRE ALARM INPUT � o a a a a a a a N s z 7' tiY CONDUCTORS OF CLASS "A" CIRCUITS BY A MINIMUM OF 12" WHERE RUN J <br /> VERTICALLY AND 48" WHERE RUN HORIZONTALLY. <br /> SMOKE DETECTORS • • • • • • • • • 1�- ;q .R + ^^^VVV _ Q <br /> HEAT DETECTORS • • • • • • • • utiNEar_ 9. WHEN UTILIZING SHIELDED CABLE TIE SHIELDS THROUGH AND INSULATE AT EACH <br /> KITCHEN HOOD • • • • • • • • JUNCTION BOX. INSULATE AND TAPE BACK AT END. F, <br /> PULL STATIONS • • • • • • • • VICINITY MAP 10. ALL FIRE ALARM CABLING SHALL BE ACCEPTABLE TO THE FIRE ALARM EQUIPMENT In, <br /> MANUFACTURER FOR THE INTENDED PURPOSE. CABLES USED IN VERTICAL RUNS <br /> WATERA OW SWITCHES • • • • • • • • N SCHEMATIC:NOT TO SCALE SHALL BE TYPE FPLP OR FPLR. CABLE SPLICES OR TERMINATIONS SHALL BE MADE <br /> VALVE SUPERVISORY SWITCHES • • • • IN LISTED FITTINGS, BOXES, ENCLOSURES, FIRE ALARM DEVICES, OR UTILIZATION c <br /> EQUIPMENT. WHERE INSTALLED EXPOSED, CABLES SHALL BE ADEQUATELY <br /> DUCT DETECTORS • • • • • • SUPPORTED AND INSTALLED IN SUCH A WAY THAT MAXIMUM PROTECTION AGAINST <br /> FIRE ALARM AC POWER FAIL • • • • PHYSICAL DAMAGE IS AFFORDED BY BUILDING CONSTRUCTION. WHERE LOCATED <br /> WITHIN 7 FT OF THE FLOOR, CABLES SHALL BE SECURELY FASTENED IN AN <br /> FIRE ALARM LOW BATTERY • • • • APPROVED MANNER AT INTERVALS OF NOT MORE THAN 18 IN. <br /> OPEN CIRCUIT • • • • <br /> • • • 11 DETECTORS <br /> NA <br /> SHALL NOT <br /> AND BNSTALLED UNTIL AFTER CONSTRUCTION <br /> GROUND FAULT • CLEAN-UP IS <br /> L. <br /> NAC SHORT CIRCUIT • • • • 12. LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL m <br /> LOSS OF AC TO BUILDING • • • • • DIFFUSERS. WALL-MOUNTED SMOKE DETECTORS SHALL BE LOCATED A MAXIMUM OF <br /> 12" FROM CEILING. <br /> 13. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS. <br /> PROVIDE ALL REQUIRED SYNC MODULES. PROVIDE A MULTI-SYNC MODE SLAVE <br /> CONNECTION BETWEEN ALL SYNC MODULES. = m <br /> 120 VAC FACP EXISTING INITIATING:REMAINING THE SAME 14. VERIFY ALL FIELD SELECTABLE AUDIBILITY SETTINGS OF NOTIFICATION APPLIANCES V <br /> (DEDICATED CKT.) " WITH FIRE ALARM CONTRACTOR. <br /> 0 E"Ba 15. UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING, <br /> o ._. A/C SUPPLY OR THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING OF THE ENTIRE <br /> RETURN DIFFUSER PENDANT MOUNTED-\ NOTE:MEASUREMENTS SYSTEM, PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A = p Z <br /> CEILING-MOUNTED J( AUDIBLEMNSUAL SHOWN ARE TO THE U <br /> a"MIN HEAT DETECTOR V APPLIANCES CLOSEST POINT OF FINAL FIRE ALARM SYSTEM INSPECTION. V N Q <br /> AYAYA VVYYV DETECTOR J QQ J <br /> 16. PROVIDE OFF-SITE MONITORING AS REQUIRED BY THE INTERNATIONAL FIRE CODE, <br /> NAC-1 EXISTING NOTIFICATION:REMAINING THE SAME 4"MIN 6"MIN. �36"MIN. Q J � <br /> a. <br /> 12°MAX AUDIBLE suu 12"MAX SECTION 907.6.6 AND THE LOCAL AUTHORITY HAVING JURISDICTION. <br /> M AUDIBLE-ONLY REMOTE ALARM CEILING MOUNTED CEILING MOUNTED � W <br /> ALARM HERER AND/OR VISUAL ® APPLIANCES INDICATOR SMOKE/HEAT AUDIBLE/VISUAL WALL-MOUNTED 17 NOTIFICATION CONTRACTOR <br /> NTRATORCRCUT END LINE AB(WHEN TNI ICTING DEVICES <br /> AND � Q <br /> NAC-2 EXISTING NOTIFICATION:REMAINING THE SAME HERE ONLY APPLIANCE DETECTOR APPLIANCES O �y <br /> WALL-MOUNTED <br /> NAC-3 EXISTING NOTIFICATION:REMAINING THE SAME LESS 3� 18 ROOMSMS CONTAINING CONTROLS FOR AR CONDITION NG SYSTEMS, SPRINKLER RISERS 'LJ.I m L JL <br /> U ~ Q <br /> SMOKE DETECTORLABELS W <br /> HEAT DETECTOR DOOR WIDTH <br /> AND VALVES OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL ELEMENTS <br /> MAGNETIC 0 30'MAX SHALL BE IDENTIFIED WITH PERMANENTLY MOUNTED SIGNS WITH LETTERING NOT ~ 0 W Q <br /> AES NAC-4 EXISTING NOTIFICATION:REMAINING THE SAME ESA DOOR FACP SYSTEM HOLDER AFF LESS THAN 2 INCHES TALL WITH A PRINCIPAL STROKE OF NOT LESS THAN 3/8 Z W <br /> AES-7707P-88-ULP-M RECORDS. SIDE WALL INCH. LETTERS SHALL CONTRAST WITH BACKGROUND. Lu LJ.I Lu <br /> 80"-96" 90"MIN. 10'MAX 30'MAX \\ <br /> COMMUNICATOR ® DOCUMENTS TO LOWEST WHERE CEILING AFF AFF a Z / <br /> LL <br /> PART OF LENS HEIGHT ALLOWS � 5'MAX T I 1 O W <br /> NAC-5 EXISTING NOTIFICATION:REMAINING THE SAME V <br /> 66"TO 66"TO 66"TO FROM EXIT "-FINISHED v/ <br /> 120 VAC TOP OF TOP OF TOP OFWALL <br /> (DEDICATED CU.) NAC-6 EXISTING NOTIFICATION:REMAINING THE SAME FSA FACP CABINET Q W <br /> MAPULL ®42"-48" J � <br /> FINISHED STATION v/ W <br /> 1/0-1 FLOOR <br /> 2 <br /> ................ Lj <br /> /o-2 FIRE ALARM DEVICE MOUNTING HEIGHTS p <br /> SCALE:NOT TO SCALE <br /> 1/0-3 <br /> 1/0-4 <br /> Drawings reviewed by: DRAWN CRL <br /> T Brady B.Haws SET UNICAD JOB#23276 <br /> NICET Certification CHECKED BRADY B*HAWS <br /> 0 Fire Protection Engineering Technology NICET N 138751 <br /> NO CONDUIT IN BOTTOM OF CAN Fire Alarm Systems-Level IV DATE 6/1/2023 <br /> Cert.No.138751 <br /> Exp 5/1/2025 REVISION 0 <br /> FIRE ALARM RISER DIAGRAM <br /> SCHEMATIC NOT TO SCALE .0 eaau Inc <br /> FA-1 <br />