MODULE SPECIFICATIONS QCeIIS Q.PEAK DUO BLK ML-G10+395 DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS
<br /> RATED POWER(STC) 395 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP;, MICROI NVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 9.7 A AC
<br /> MODULE VOC 45.3 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 12.1 A AC
<br /> MODULE VMP 36,9 V DC CITY Everett; CONDUCTOR(TC-ER,COPPER(90'C))= 12 AWG
<br /> BLUE RAVE N
<br /> MODULE IMP 10.7 A DC WEATHER STATION SNOHOMISHCOl CONDUCTOR RATING= 30 A
<br /> MODULE ISC 11.1 A DC ASHRAE EXTREME LOW TEMP('C) -Si AMB.TEMP,AMP.CORRECTION= 1
<br /> VOC CORRECTION •0.27 %/'C ASHRAE 2%AVG.HIGH TEMP('C) 30' ADJUSTED AMP.= 30 > 12.1 1403 N. Research Way
<br /> 84097
<br /> VMP CORRECTION .0.34 %/'C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 9.7 A AC Orem, U7.
<br /> 800.377.4480480
<br /> SERIES FUSE RATING 20 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 12.1 A AC WWW.BLUERAVENSOLAR.COM
<br /> ADJ. MODULE VOC @ ASHRAE LOW TEMP 48.9 V DC NUMBER OF MODULES PER MPPT 8 7 CONDUCTOR(UFB,COPPER(60°C))= 10 AWG CONFIDENTIAL-THE INFORMATION
<br /> ADI MODULE VMP @ ASHRAE 2°�G AVG. HIGH TEMP 32.2 V DC DC POWER RATING PER CIRCUIT(STC) 3160 2765 CONDUCTOR RATING= 30 A HEREIN CONTAINED SHALL NOT BE
<br /> USED FOR THE BENEFIT OF ANYONE
<br /> TOTAL MODULE NUMBER 15 CONDUIT FILL DERATE= 1 EXCEPT BLUE RAVEN SOLAR NOR
<br /> SHALL IT BE DISCLOSED IN WHOLE OR
<br /> MICROINVERTER SPECIFICATIONS Enphase IQ8+Mlcroinverters STC RATING OF ARRAY 5925 AMB.TEMP.AMP.CORRECTION= 1 IN PART TO OTHERS OUTSIDE
<br /> POWER POINT TRACKING(MPPT)MIN/MAX 30 - 58 V DC AC CURRENT @ MAX POWER POINT(IMP 9.7 8.5 ADJUSTED AMP. = 30 > 12.1 RECIPIENTS ORGANIZATION,EXCEPT
<br /> IN CONNECTION WITH THE SALE AND
<br /> MAXIMUM INPUT VOLTAGE 60 V DC MAX.CURRENT(IMP X 1.25) 12.1 10.5875 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 9.7 A AC USE OF THE RESPECTIVE EQUIPMENT,
<br /> WITHOUT THE WRITTEN PERMISSION
<br /> MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 12.1 A AC OF BLUE RAVEN SOLAR LLC.
<br /> MAXIMUM USABLE DC INPUT POWER 440 W MAX.COMB.ARRAY AC CURRENT(IMP) 18.2 CONDUCTOR(UF-B,COPPER(60'C))= 10 AWG
<br /> MAXIMUM OUTPUT CURRENT 1.21 A AC MAX.ARRAY AC POWER 435OW AC CONDUCTOR RATING= 30 A NABCEP
<br /> AC OVERCURRENT PROTECTION 20A CONDUIT FILL DERATE= 0.8
<br /> MAXIMUM OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. JRISE(V) VEND(V) %VRISE AMB-TEMP.AMP.CORRECTION= 1 CERTIFIED
<br /> CEC WEIGHTED EFFICIENCY 97 % VRISE SEC. 1(MICRO TO 1BOX) 28.8 12 Cu. 0.93 240.93 0.39% ADJUSTED AMP.= 24 > 12.1 PV INSTALLATION
<br /> VRISE SEC. 2(JBOX TO COMBINER BOX) S5 lOCu. 1.35 24135 0.56% COMBINER BOX TO INVERTER RATED AMPS= 18.2 A AC PROFESSIONAL
<br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC. 3(COMBINER BOX TO P01) 5 10 Cu. 0.23 240.23 0.10% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 22.69 A AC Scott Gurney
<br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 2.51 242.51 1.05% CONDUCTOR(THWN-2,COPPER(75'C TERM.))= 10 AWG #PV-011719-015866
<br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 35 A CONTRACTOR:
<br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILL DERATE= 1 BRS FIELD OPS
<br /> MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 18.2 A AC AMB.TEMP,AMP.CORRECTION= 1 800-377-4480
<br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP = 35 > 22.7
<br /> U U
<br /> GROUNDING NOTES WIRING &CONDUIT NOTES Z
<br /> a �
<br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1. ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE 0 �: Y
<br /> PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. O lie
<br /> L0
<br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE (V ol
<br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). CC pQ
<br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE C 0) L!7
<br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED
<br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF O W W
<br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. LL NN
<br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE y F
<br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. Z C
<br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND w (10 L 2 C
<br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS E c
<br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.461. REQUIRED. CWC >% LU LU
<br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE G J
<br /> 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. O
<br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE y '
<br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE V) U)
<br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(13)(3)(C)]. !✓
<br /> 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90°C RATED,WET AND UV RESISTANT,AND UL = Cu > V V
<br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP U cr) W Q
<br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES.
<br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED,
<br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY:
<br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND
<br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Prem I U m CAD
<br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION
<br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE:
<br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC
<br /> GREEN IF 4 AWG OR LARGER).
<br /> PO
<br /> CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE PIOGREY)
<br /> POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED
<br /> 3.ALL December 19, 2022
<br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK)
<br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.661, DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, PROJECT NUMBER:
<br /> ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY
<br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE 675781
<br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] "USE-2 IS AVAILABLE AS UV WHITE
<br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES.
<br /> 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, SHEET NAME:
<br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING
<br /> MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.151. ELEC CALCS
<br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC
<br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)].
<br /> REVISION: PAGE NUMBER:
<br /> 0 PV6