INITIATING WIRING RECORD DRAWINGS
<br /> = convergjnt'
<br /> AS-BUILT/RECORD DRAWING REQUIREMENTS: u O p
<br /> F
<br /> SIGNATURE LOOP WIRING LIMITATIONS: a F a N N a
<br /> THE FOLLOWING INFORMATION SHOULD BE RECORDED ON A SEPARATE SET OF a
<br /> SIGNATURE DUAL DRIVER CONTROLLER MODULES SUPPORTS UP TO 250 DRAWINGS FOR EACH PROJECT: a o a o a o z
<br /> INTELLIGENT SIGNATURE DETECTORS AND 250 INTELLIGENT SIGNATURE > 450 Shattuck AVenue South,Renton,Washington 98057
<br /> MODULES 1. ANY CHANGES IN THE LOCATION OF ANY ASSOCIATED FIRE ALARM OR z u_ m u_ z u_ u u z o Phone:425-272-2250 Fax;425-251-0949
<br /> WIRE LENGTH LIMITATIONS: INTERFACE EQUIPMENT.CONTROL PANELS,ANNUNCIATORS,DETECTORS, T o 0 0 ,., o O ~o O
<br /> CONTROL RELAYS,INPUT AND OUTPUT MODULES,TERMINAL CABINETS, z z z m
<br /> NON-TWISTED,NON-SHIELDED WIRE ETC. SEQUENCE OF 5 m m m k > This locums-- tlthe infoimeb.n/depicb.ns mnWinedl.hoWn
<br /> 16AWG-20pf/FT&4.02 OHMS/1000 FEET 2. ANY CHANGES TO CIRCUIT WIRING.THIS INCLUDES DELETION OR Q o w o o g •8 is the exclusive pmperry m Converging Technologies LLC end shell
<br /> 18AWG-20pfIFT&6.38 OHMS/000 FEET ADDITIONAL WIRING RUNS.ANY RE-ROUTING OF CIRCUIT WIRING.ANY a N a a m be handled as prepdetary end wnfld.ntial information and must be
<br /> DETECTORS ONLY i6AWG-125 DETECTORS-9,275' ADDITIONS OR DELETIONS TO THE NUMBER,LOCATION,AND ORDER OF OPERATIONS s u o retu..d upon request.This dowmenl cannot be reproduced by any
<br /> O ¢ F Q ] ens without the then euthodutlon of Convergint Technologies LLC.
<br /> MODULES ONLY 16AWG-125 MODULES-7,921' DEVICE WIRING ON A CIRCUIT. u K Q
<br /> DETECTORS AND MODULES i6AWG-125 OF EACH-3,608' 3. ADDRESSES AND/OR LABELS FOR ALL ADDRESSABLE DEVICES. o a a a a z
<br /> DETECTORS ONLY 18AWG-125 DETECTORS-5,839' 4. CANDELA SETTINGS OF ALL VISUAL NOTIFICATION DEVICES. o 0 0 o O o z I,m z
<br /> MODULES ONLY 18AWG-125 MODULES-4,986' 5. WATTAGE TAP SETTINGS OF ALL SPEAKER NOTIFICATION DEVICES. o ,n
<br /> DETECTORS AND MODULES 18AWG-125 OF EACH-2,271' > Fj
<br /> ANY CHANGES SHALL BE DISCUSSED WITH CONVERGINT PROJECT MANAGER G > 3Lp m
<br /> TWISTED PAIR,NON-SHIELDED WIRE TO ENSURE SYSTEM AND CODE PARAMETERS ARE MET.CONVERGINT SHALL a G a a > o
<br /> 16AWG-36pf/FT&4.02 OHMS/1000 FEET NOT BE HELD ACCOUNTABLE FOR CHANGES MADE WITHOUT APPROVAL. Q
<br /> 18AWG-25pf/FT&6.38 OHMS/1000 FEET
<br /> DETECTORS ONLY 16AWG-125 DETECTORS-9,275' THIS INFORMATION SHALL BE NEAT AND LEGIBLE WHEN PRESENTED TO THE
<br /> MODULES ONLY 16AWG-125 MODULES-7,921' TECHNICIAN AT THE CONCLUSION OF THE PROJECT.PLEASE NOTE CONTACT
<br /> DETECTORS AND MODULES 16AWG-125 OF EACH-3,608' INFORMATION ON DRAWINGS FOR INDIVIDUALS WITH FAMILIARITY OF SMOKE DETECTOR X X X
<br /> DETECTORS ONLY 18AWG-BAWG_1125 DETECTORS-5,839' INSTALLATION IN THE EVENT QUESTIONS ARISE DURING THE CLOSEOUT
<br /> MODULES ONLY 1DETECTORS AND MODULES 18AWG-125 OF EACH-2,27125 MODULES- 6 PROCESS.
<br /> MANUAL PULL STATIONX y X y
<br /> X
<br /> TWISTED PAIR,SHIELDED WIRE
<br /> 16AWG-82pf/FT&4.02 OHMS/1000 FEET NETWORK WIRING GENERALTROUBLE CONDITION X X
<br /> 18AWG-58pf/FT&6.38 OHMS/1000 FEET
<br /> DETECTORS ONLY i6AWG-125 DETECTORS-6,098' DATA NETWORK SPECIFICATIONS: GENERAL SUPERVISORY CONDITION X X
<br /> MODULES ONLY 16AWG-125 MODULES-6,098'
<br /> DETECTORS ONDETECTORS LY
<br /> MODULES 18AWG-125 DETECTORS 605,839' MAXIMUM ALLOWED VALUES BETWEEN ANY THREE NODES OF A NETWORK. HEAT DEFECTOR X X X
<br /> MODULES ONLY 18AWG-125 MODULES-4,986' • RESISTANCE:90 OHMS
<br /> DETECTORS AND MODULES 18AWG-125 OF EACH-2,271' • CAPACITANCE:0.3 MICROFARADS
<br /> • DISTANCE:5,000 FEET
<br /> SlG0-LOOP WIRING c-ASS E 0- SIGNATURE DATA LOOP.C-ASS 3 ONLY THE FOLLOWING TABLE LISTS THE MAXIMUM CUMULATIVE CAPACITANCE FOR FACP-LOSS OF PRIMARY POWER X X
<br /> THE ENTIRE DATA NETWORK GIVEN VARIOUS WIRE SIZES AND TRANSMISSION
<br /> "I-WAT ILI IATA RATES.MAXIMUM CUMULATIVE CAPACITANCE IS THE TOTAL CAPACITANCE OF
<br /> aoa,x n o of LaoP�h a ::rev ALL INSTALLED COPPER WIRE USED IN THE DATA NETWORK.
<br /> MAXIMUM CUMULATIVE CAPACITANCE IN MICROFARADS
<br /> • em • em
<br /> i BAWG_'l
<br /> @ 38.4K BAUD/2.8 @ 19.2K BAUD
<br /> i 6AWG-1.8 @ 38.4K BAUD/2.1 @ 19.2K BAUD
<br /> US JNACCEPTAISUE 14AWG-2.1 @ 38.4K BAUD/4.2 @ 19.2K BAUD
<br /> CABLE PROPERTIES
<br /> DATA AND AUDIO NETWORKS IN AN EST3 SYSTEM DO NOT REQUIRE THE USE OF
<br /> SHIELDED CABLE,AND NETWORKS DESIGNED WITH TWISTED-PAIR CAN BE
<br /> ABOUT TWICE AS LONG AS THOSE DESIGNED WITH SHIELDED CABLE.THE
<br /> GE- MAXIMUM LENGTH OF A DATA NETWORK VARIES WITH THE PROPERTIES OF THE
<br /> WIRE USED.WIRE MANUFACTURERS TYPICALLY PROVIDE SPECIFICATIONS FOR
<br /> m
<br /> WIRE RESISTANCE AND CAPACITANCE.
<br /> T-TAPPING.ACCEPTABLE elof-TAPP,h-RAC-SLE SURVIVABILITY WIRING
<br /> PATHWAY SURVIVABILITY LEVELS
<br /> PATHWAY SURVIVABILITY MUST MEET THE REQUIREMENTS OF NFPA 72;SECTION
<br /> 12.4 FOR THE CORRESPONDING LEVEL OF SURVIVABILITY REQUIRED BY NFPA 72,
<br /> NOTIFICATION WIRING
<br /> CHAPTER 24.THE FOLLOWING IS A CONDENSED DESCRIPTION OF THE
<br /> SURVIVABILITY LEVELS.
<br /> SPEAKER CIRCUIT WIRING LIMITATIONS: PATHWAY SURVIVABILITY LEVEL 0.LEVEL 0 PATHWAY SHALL NOT BE REQUIRED TO
<br /> WIRE LENGTH LIMITATIONS: HAVE ANY PROVISIONS FOR PATHWAY SURVIVABILITY.
<br /> THE MAXIMUM ALLOWABLE WIRE LENGTH IS THE FARTHEST DISTANCE THAT A PATHWAY SURVIVABILITY LEVEL 1.PATHWAY INSTALLED IN FULLY SPRINKLED
<br /> SPEAKER CIRCUIT CAN EXTEND FROM THE AMPLIFIER TO THE LAST SPEAKER BUILDING MEETING THE REQUIREMENTS OF NFPA 13 WITH ANY INTERCONNECTING
<br /> WITHOUT LOSING 0.5 dB OF SIGNAL.THE FOLLOWING ARE MAXIMUM DISTANCE CONDUCTORS,CABLES OR OTHER PHYSICAL PATHWAYS INSTALLED IN METAL
<br /> BASED ON APPROXIMATE WATTAGE OF THE SPEAKER CIRCUIT.CIRCUIT LENGTHS RACEWAYS.
<br /> ARE FURTHER BASED ON ORIGINATION OF A CIRCUIT FROM EITHER THE PATHWAY SURVIVABILITY LEVEL 2.PATHWAY SURVIVABILITY LEVEL 2 SHALL
<br /> AMPLIFIER OR FROM THE CCI MODULE. CONSIST OF ONE OR MORE OF THE FOLLOWING:
<br /> ALLOWABLE LENGTH AT 25 Vrms,WITH 0.5 dB LOSS (1) 2-HOUR FIRE-RATED CIRCUIT INTEGRITY(CI)CABLE
<br /> 16AWG-20 WATTS-231' (2) 2-HOUR FIRE-RATED CABLE SYSTEM[ELECTRICAL CIRCUIT PROTECTIVE
<br /> 1
<br /> 6AWG-30 WATTS-154' SYSTEM(S)]
<br /> 16AWG-40 WATTS-116' (3) 2-HOUR FIRE RATED ENCLOSURE OR PROTECTED AREA
<br /> (4) 2-HOUR PERFORMANCE ALTERNATIVES APPROVED BY THE AUTHORITY
<br /> ALLOWABLE LENGTH AT 70 Vrms,WITH 0.5 dB LOSS HAVING JURISDICTION
<br /> 16AWG-20 WATTS-
<br /> 1815' ppTHWAY SURVIVABILITY LEVEL 3.SAME AS LEVEL 2 WITH ADDITION OF BEING IN A
<br /> 1
<br /> 6AWG-30 WATTS-1210' FULLY SPRINKLED BUILDING MEETING THE REQUIREMENTS OF NFPA 13.
<br /> 16.-40 WATTS-907'
<br /> NAC CIRCUIT(HORN,STROBE)WIRING LIMITATIONS: CIRCUITS REQUIRING SURVIVABILITY BY NFPA 72
<br /> FOR 24VDC SYSTEMS,MINIMUM DEVICE OPERATING VOLTAGE IS 16VDC. THE FOLLOWING CIRCUIT TYPES,WHEN USED ARE REQUIRED TO BE SURVIVABLE
<br /> VOLTAGE DROP CALCULATIONS ARE BASED ON 16VDC AND POWER SUPPLY AS DESCRIBED BELOW.REFER TO NFPA 72,CHAPTER 24 FOR ADDITIONAL
<br /> DE-RATED AND ON DEPLETED BATTERY BACKUP PER THE PRESCRIBED PERIOD INFORMATION REGARDING CIRCUIT TYPES.THIS IS NOT A COMPLETE LIST AND IS
<br /> OF STANDBY AND ALARM RING TIME.THE VOLTAGE DROP WILL LIMIT THE MEANT TO SUPPLEMENT ANY NOTES PROVIDED ELSEWHERE IN OUR DRAWING
<br /> CIRCUITS CAPACITY IN ALMOST ALL CASES AND CURRENT CANNOT BE USED AS PACKAGE.PLEASE CONTACT CONVERGINT ENGINEERING DEPARTMENT WITH ANY
<br /> THE ONLY CIRCUIT WIRING LIMITATION.ALTERATIONS TO CIRCUIT LENGTH QUESTIONS ON THE APPLICATION OF SURVIVABILITY.
<br /> DESIGNER OF RECORD
<br /> FROM THOSE CALCULATED MAY CAUSE CIRCUITS TO BE OUT OF THE
<br /> TOLERANCES GRANTED BY THE FIRE ALARM CODE.CHANGES TO DEVICE IN-BUILDING FIRE EMERGENCY VOICE/ALARM COMMUNICATIONS SHALL BE JACOB USHER
<br /> LOCATION OR CIRCUIT LENGTH SHALL BE COMMUNICATED TO THE CONVERGINT SURVIVABLE BASED ON ONE OF TWO CATEGORIES(24.3.6.4) NICET III
<br /> TEAM. •• FOR SYSTEMS EMPLOYING RELOCATION OR PARTIAL EVACUATION,A LEVEL FIRE ALARM SYSTEMS
<br /> 2 OR 3 PATHWAY SURVIVABILITY SHALL BE REQUIRED(24.3.6.4.1).
<br /> NAC CIRCUIT WIRING AND ROUTING MUST NOT EXCEED WHAT IS SHOWN ON THE •• FOR SYSTEMS THAT DO NOT EMPLOY RELOCATION OR PARTIAL #+^e+ep
<br /> DESIGN DRAWINGS AND CALCULATIONS.A VOLTAGE DROP TEST IS PART OF EVACUATION,A LEVEL 0,LEVEL 1,LEVEL 2 OR LEVEL 3 PATHWAY =EIDATE l it o-Noss
<br /> FORVERIFICA
<br /> MOST FIRE FINALS AND IS REQUIRED BY NFPA.A FAILED FIRE FINAL MAY SURVIVABILITY SHALL BE REQUIRED(24.3.6.4.2). PLEASE VISIT SNVWNICETORG
<br /> REQUIRE REWIRING OF THE FAILED CIRCUITS.
<br /> TWO-WAY IN-BUILDING WIRED EMERGENCY COMMUNICATIONS SYSTEMS SHALL U/dXN//lam
<br /> WIRE RESISTANCE RATINGS USED FOR CALCULATIONS: HAVE A PATHWAY SURVIVABILITY OF LEVEL 2 OR LEVEL 3(24.3.6.7).THIS
<br /> 18AWG-13 OHMS PER 1000' APPLIES TO FIREMAN'S PHONE SYSTEMS,STAIRWELL RE-ENTRY INTERCOM
<br /> 18AWG
<br /> -8 OHMS PER 1000' AND ELEVATOR LOBBY TWO-WAY AS REQUIRED BY INTERNATIONAL BUILDING
<br /> 14AWG-:OHMS
<br /> PER 1000' CODE(IBC),SECTIONS,403 AND 1009.8.
<br /> EXAMPLE: 1.0 AMP CIRCUIT LOAD USING#14 WIRE=409 FEET MAXIMUM. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS(DAS)SHALL
<br /> COMPLY WITH 24.3.6.8.1 THROUGH 24.3.6.8.4.DAB IS NOT A COMPONENT OF
<br /> THE FIRE ALARM DESIGN AND IS PROVIDED FOR INFORMATIONAL PURPOSES
<br /> ONLY.
<br /> CLASS A OR B NOTIFICATION WIRING • AREA OF REFUGE EMERGENCY COMMUNICATIONS SYSTEMS SHALL HAVE
<br /> PATHWAY SURVIVABILITY OF LEVEL 2 OR LEVEL 3(24.3.6.9.1).
<br /> CIRCUITS INTENDED TO TRANSMIT OFF-PREMISES SHALL HAVE A PATHWAY
<br /> SURVIVABILITY OF LEVEL 0,LEVEL 1,LEVEL 2 OR LEVEL 3(24.3.6.9.2).
<br /> EOL
<br /> FOR SMOKE CONTROL SPECIFIC SURVIVABILITY REQUIREMENTS,REFER TO THE
<br /> FACP SMOKE CONTROL SECTION OF OUR NOTES.UPON REQUEST,CONVERGINT WILL
<br /> OR EOL RESISTOR ON PROVIDE EQUIVALENT SUBSTITUTIONS FOR ANY SPECIFIED CABLE.ANY CABLE
<br /> NAC NON ADDRESSABLE SUBSTITUTED MUST HAVE EQUAL TO OR BETTER PROPERTIES TO THE CABLE
<br /> CIRCUITS SPECIFIED IN OUR WIRE LEGEND.
<br /> DEVICE DEVICE SMOKE CONTROL
<br /> CLASS B,STYLE 4 WIRING AS A FIRE ALARM VENDOR,CONVERGINT TECHNOLOGIES HAS REVIEWED AND
<br /> PROVIDED A DRAWING PACKAGE THAT REFLECTS THE REQUIRED INTERFACES TO
<br /> THIRD PARTY EQUIPMENT AND SYSTEMS.CONVERGINT IS NOT THE DESIGNER OF
<br /> RECORD FOR THE SMOKE CONTROL SYSTEM AND DEFERS TO THE REGISTERED
<br /> FIRE PROTECTION ENGINEER FOR THIS SPECIFIC PROJECT AS IT RELATES TO THE
<br /> FIRE ALARM/SMOKE CONTROL INITIATION AND CONTROL DESIGN PARAMETERS.
<br /> ANY PROVIDED SMOKE CONTROL NARRATIVE(S)OR REPORTS HAVE BEEN REV Joao-pescRIPnoN onrE
<br /> FACP INCORPORATED INTO OUR DESIGN APPROACH UNLESS INFORMED OTHERWISE.
<br /> OR ADDITIONALLY,WE HAVE REVIEWED THE REQUIREMENTS OF 909.12 IN IT'S
<br /> NAC ENTIRETY AS IT RELATES TO THE FIRE ALARM DESIGN AND INCORPORATED THE
<br /> NECESSARY ELEMENTS.THE INSTALLER OF THIS SYSTEM IS ALSO REQUIRED TO
<br /> MEET THE APPLICABLE REQUIREMENTS.
<br /> IT2 WIRING ASSOCIATED WITH SMOKE CONTROL MUST MEET THE REQUIREMENTS OF
<br /> DEVICE DEVICE THE AMENDED CODE FOR THIS PROJECT.THIS VARIES FROM JURISDICTION TO
<br /> y JURISDICTION.AS SUCH,THESE NOTES ARE INTENDED TO COVER THE GENERAL
<br /> d NATURE OF THIS WIRING.IN ADDITION TO THE SURVIVABILITY REQUIREMENTS
<br /> O LISTED BELOW,ALL WIRE REGARDLESS OF VOLTAGE SHALL BE FULLY ENCLOSED IN rAnxaLUH
<br /> CONTINUOUS RACEWAY AS INDICATED IN,IBC,909.12.2. PRaecT bEewNER: Ac EU.
<br /> D �PROUISCT-ERI H.
<br /> 111 ANYWIREASSOCIATEDWITHTHECONTROLOFANYASPECTOFSMOKE POWER REQUIREMENTS
<br /> J CLASS A.STYLE 6 WIRING
<br /> U CONTROL SHALL HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN TWO S_CAE_77 AN- DATE: 08-23
<br /> HOURS.THIS INCLUDES THE ADDRESSABLE DATA(SLC)CIRCUIT(S)USED TO
<br /> Q CONNECT ADDRESSABLE RELAYS AND MONITOR MODULES. EACH MAIN FIRE ALARM PANEL REQUIRES(1)120VAC,20AMP DEDICATED
<br /> < SEPARATION OF CLASS A CIRCUITS-INSTALLATION EXCEPTIONS: CIRCUIT. WSDOT
<br /> THE CONTROL PORTION ANY SMOKE CONTROL COMPONENT THAT FAILS TO FIRE ALARM
<br /> H CLASS A OUTGOING AND RETURN CONDUCTORS,EXITING AND RETURNING THE SMOKE CONTROL STATE,GENERALLY ISN'T REQUIRED TO BE TWO HOUR EACH NAC BOOSTER PANEL REQUIRES(1)120VAC,15AMP DEDICATED CIRCUIT.
<br /> TO THE CONTROL PANEL,ARE TO BE ROUTED SEPARATELY.THE MINIMUM RATED.ANY REQUIRED PROOFING PORTION OF THESE INTERFACES SHALL 709 N BROADWAY
<br /> v RECOMMENDED SEPARATION IS 1 FT.VERTICALLY AND 4 FT. HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN TWO HOURS. IN BUILDINGS EMPLOYING EMERGENCY STANDBY POWER SYSTEMS,THE FIRE EVERETT,WA 98201
<br /> x HORIZONTALLY.THE FOLLOWING EXCEPTIONS STILL DO NOT ELIMINATE ALARM SHALL BE SUPPLIED WITH EMERGENCY POWER.THIS IS REQUIRED IN
<br /> o THE 2ND PAIR OF WIRES.THEY ALLOW YOU TO USE A SINGLE RACEWAY THE INITIATION PORTION OF SMOKE CONTROL GENERALLY ISN'T REQUIRED TO HIGH-RISE AND SMOKE CONTROL APPLICATIONS.ALL OTHER APPLICATIONS
<br /> M AND ELIMINATE THE SEPARATION FOR THESE CONDITIONS. BE TWO HOUR RATED UNLESS SUPERCEDED BY PROJECT OR LOCAL ARE SUBJECT TO LOCAL BUILDING AND ELECTRICAL CODES.
<br /> H- REQUIREMENTS;HOWEVER CERTAIN JURISDICTIONS DO REQUIRE THESE NOTES
<br /> O 1. WHEN MAXIMUM CABLE,ENCLOSURE,OR RACEWAY IS LESS THAN 10 ELEMENTS TO BE ENCLOSED IN METAL RACEWAY.REFER TO LOCAL WHERE THE FIRE ALARM SYSTEM IS CONNECTED TO EMERGENCY
<br /> Z FEET.NO LIMIT TO NUMBER OF DEVICES. AMENDMENTS FOR SPECIFIC REQUIREMENTS. POWER,THE FIRE ALARM SYSTEM MONITORS THE GENERATOR FOR
<br /> 2. UNLIMITED CONDUIT OR RACEWAY DROP TO AN INDIVIDUAL DEVICE. RUNNING,FUEL LOW AND TROUBLE STATES.
<br /> (� 3. UNLIMITED CONDUIT OR RACEWAY DROP TO A ROOM NOT FOR WIRING METHODS,PLEASE REFER TO THE SURVIVABILITY WIRING SECTION OF FIRE ALARM SYSTEM
<br /> Z EXCEEDING 1000 SO,FT.NO LIMIT TO THE NUMBER OF DEVICES. OUR NOTES.LEVEL 2 AND LEVEL 3 WIRING GENERALLY MEETS THE REQUIREMENTS FOR ADDITIONAL DETAILS,REFER TO NFPA 72,CHAPTER 10.
<br /> OF THE INTERNATIONAL BUILDING CODE,CHAPTER 909.
<br /> wlNc.
<br /> o FA-0-2