Laserfiche WebLink
VERETT <br />0 <br />Permit Inspections <br />City of Everett <br />1/12/2023 <br />1/12/2023 <br />ELEC06-ROUGH IN <br />STEVE BANKS <br />CORRECTION <br />REQUIRED <br />Notes: <br />Ground all metal boxes. Get rid of unused wires. Add receptacles in the kitchen for two foot and 4 foot rule. Add receptacles to meet the 6'12 foot in <br />especially the master bedroom. Add a switch at each store that opens out for the outside light. Properly secure and support all wires. Make up all <br />boxes, including the closet re -identify any white conductors that are used as current carrying conductor. Refeed the water heater properly. Check all <br />overcurrent to be proper size for the wire, and the circuit it serves. <br />1/23/2023 <br />1/23/2023 <br />ELEC 06-ROUGH IN <br />STEVE BANKS <br />PARTIAL <br />see notes <br />APPROVAL <br />Notes: <br />1/19/2023 1:49 PM ShuChuan Chang <br />Contact Name: ShuChuan Chang <br />Site Address: 2817 MEDORA WAY <br />Phone:6262269678 <br />e-Mail: shuchuanl112@gmail.com <br />Check kitchen pop up box at final and junction boxes in attic must be above the insulation in the attic and KO seals in garage junction box.Do not install <br />insulation tonight attic. <br />1/23/2023 <br />1/23/2023 <br />ELEC06-ROUGH IN <br />STEVE BANKS <br />CORRECTION <br />REQUIRED <br />Notes: <br />Raise junction boxes above 16 inches in the attic for insulation. <br />1/26/2023 <br />1/26/2023 <br />ELEC 06-ROUGH IN <br />STEVE BANKS <br />APPROVAL <br />as noted <br />Notes: <br />1/24/2023 4:06 PM ShuChuan Chang <br />Contact Name: ShuChuan Chang <br />Site Address: 2817 MEDORA WAY <br />Phone:6262269678 <br />e-Mail: shuchuan1112@gmail.com <br />Install junction box covers in attic check at final. <br />4/21/2023 <br />4/21/2023 <br />ELEC 10-FINAL <br />STEVE BANKS <br />CORRECTION <br />eTRAKiT Inspection Request <br />REQUIRED <br />Notes: <br />4/18/2023 9:27 PM ShuChuan Chang <br />Contact Name: ShuChuan Chang <br />Site Address: 2817 MEDORA WAY <br />Phone:6262269678 <br />e-Mail: shuchuan1112@gmail.com <br />Provide GFCI protection for the dryer. There's reverse polarity in the downstairs bedroom. The new receptacle out the closet downstairs has no power <br />for testing. The bathroom and laundry room the GFCI's appear to be non-functioning, rewire and Replace. The front outside receptacle has no power for <br />testing provider receptacle at the back patio. <br />I <br />Printed: Thursday, 27 April, 2023 2 of 3 rk <br />SUPERION <br />