Laserfiche WebLink
Table 7. Unit Wei hts <br /> Unit Size <br /> Model 030 045 060 075 100 125 1 150 `1 175 200 225 250 300` 350 400 <br /> Pounds(kg) <br /> UBX 84 89102 108 168 171 300 320 320 385 400 458 494 506 <br /> (38 40) (46) (49) 76 78 136 145 145 175 (181) (208) 224 230 <br /> UBZ 85 90 103 i09 169 172 301 321 321 386 401 459 495 507 <br /> 39) 41 47 (49 (77 78 (137) (146) (146) (175 182 208 (225) (230 <br /> UDX 57 62 71 76 101 106 178 193 193 211 223 277 303 316 <br /> 26 (28) (32) (34 46A8 81 88 88 (96) (101) (1 26J.. 137 143 <br /> UDZ 58 63 71 77 102 107 179 194 194 212 224 278 304 317 <br /> 26 29 (32 (35) (46) (49) (81) 1 (88) (88 96 102 126 138 144 <br /> Combustion Air Requirements <br /> 0 WARNING <br /> • Do not install a unit in a confined space without providing wall openings leading to and from <br /> the space. <br /> • Unit heater models UBX and UDX are designed to take combustion air from the space in which <br /> the unit is installed and are not designed for connection to outside combustion air intake ducts. <br /> Connecting outside air ducts voids the warranty and could cause hazardous operation. <br /> • For UBZ and UDZ models, refer to the combustion air requirements in the venting instructions listed in 'Cable 1. <br /> • UBX and UDX models must be supplied with the air that enters into the combustion process and is then vented <br /> to the outdoors. Sufficient air must enter the equipment location to replace that which is exhausted through the <br /> heater vent system. <br /> • In the past,the infiltration of outside air assumed in heat loss calculations(one air change per hour)was assumed <br /> to be sufficient.However,current construction methods,which use more insulation,vapor barriers,tighter fitting and <br /> gasketed doors and windows,weather-stripping,and/or mechanical exhaust fans,may now require the introduction <br /> of outside air through wall openings or ducts. <br /> • Under all conditions, enough air must be provided to ensure there will not be a negative pressure condition within <br /> the equipment room or space. <br /> • Requirements for combustion air and ventilation air depend upon whether the unit is located in a confined or <br /> unconfined space. A confinedspace is defined as a space whose volume is<50 cubic feet per 1,000 BTUh of the <br /> installed appliance input rating. An unconfined space is defined as a space whose volume is>50 cubic feet per <br /> 1,000 BTUh of the installed appliance input rating. <br /> • For confined space installation of UBX and UDX models (including those with CV option), provide openings <br /> (depending on the combustion air source)near the floor and ceiling for ventilation and air for combustion,as shown <br /> in Figure 4 and as listed in Table 8. <br /> NOTE: For further details on supplying combustion air to a confined space, refer to the National <br /> Fuel Gas Code ANSI 2223.1 a (latest edition). <br /> C A ` --___B-__ _ ` <br /> CONFINER <br /> SPACE <br /> C A B_ __ \ <br /> blmnmimmm <br /> Figure 4. Confined Space Combustion Air Openings(Refer to Table 8) <br /> 1-UBX-UBZ-UDX-UDZ(04-21)1034344-0 11 <br />