Laserfiche WebLink
Notification Appliance Circuits can be wired as Class A or Relays <br /> Class B and support 24 VDC polarized appliances such The Main Controller Board incorporates 3 programmable <br /> as horns, strobes and bells. Strobes can be either syn- Form-C Relays and 1 Form-C Trouble relay. The Expan- <br /> chronized or non-synchronized. sion Card occupies a single slot in the Card Cage <br /> The Releasing Circuits can be wired as Class A or Class Assembly and plugs directly into the backplane. The sys- <br /> B and configured to activate agent control heads. The cir- tem can be expanded by adding Relay cards to the back- <br /> cuit-on time is configurable from 55 microseconds, 90 plane. Each Relay card provides four programmable <br /> seconds, 10 minutes, 15 minutes, or On-To-Reset, Form-C relays similar to those on the MCB. The number <br /> dependant on the release device and suppression sys- of Relay Expansion Cards in a system is limited only by <br /> tem. While the circuits are power limited, utilizing this the availability of card slots—which itself is limited to 24. <br /> option for releasing requires the use of a field In-Line Each relay is independently-driven and can be pre-pro- <br /> Release Device — separate for solenoids and actuators. grammed to change state for all states of Alarm, Trouble <br /> An NFPA-72 compliant disconnect switch provides the and Supervisory conditions. Relays are normally de- <br /> means to physically isolate the circuit from its associated energized, unless configured for Trouble. A Trouble relay <br /> field wiring. is energized upon startup and changes state for any <br /> Trouble event, including failure of the Main Controller <br /> Board. R-G-Y status LEDs are provided. Contact ratings <br /> R-NAC EXPANSION CARD SPECIFICATION are 3 A at 30 VDC or 120 VAC. <br /> Number of Cards: Subject to slot <br /> availability, max 24 per RELAY EXPANSION CARD SPECIFICATION <br /> MCB <br /> Number of Circuits Per Card: Three Number of Cards: Subject to slot <br /> Circuit Specifications: Same as R-NAC on availability, max 24 per <br /> MCB MCB <br /> Number of Relays Per Card: Four <br /> Triple Redundancy Protection Relay Specifications: Same as Relays on <br /> Unlike some generic fire alarm control units adopted for MCB <br /> releasing service, at its core the ARIES NETLink is <br /> suppression-focused. Featuring the exclusive Triple-R <br /> redundancy safeguard wherein no single component fail- City Tie Card <br /> ure or combination of abnormal operating conditions, The optional City Tie Card provides connection and oper- <br /> including main microprocessor failure, is allowed to result ation for three independently operated signaling circuits <br /> in accidental release activation, the ARIES NETLink used to connect to Municipal Tie inputs as either Local <br /> provides the same high quality, dependability and maxi- Energy output, Shunt-Type Master Box output or <br /> mum protection against inadvertent release that have Reverse Polarity output. The City Tie Card occupies a <br /> been the hallmark of Kidde suppression panels for single slot in the Card Cage Assembly and plugs directly <br /> decades. The Triple-R system requires that in order to into the backplane. The ARIES NETLink allows one City <br /> activate a release, the main microprocessor issue two Tie Card per control unit. <br /> release commands of opposite polarity via separate <br /> signaling channels and that these commands combine <br /> with a signal from the control unit's watchdog timer to CITY TIE CARD SPECIFICATION <br /> confirm the microprocessor operation. The Triple-R sys- Number of Cards: Max 1 per control unit <br /> tem ensures that electrical transients or disturbances Number of Circuits Per Card: Three <br /> such as power surges that could interfere with the opera- <br /> tion of the main microprocessor will not inadvertently Local Energy Type: VDC <br /> @ 550 mA maximum <br /> activate the connected suppression system. The result is @ <br /> a more robust and reliable suppression control unit. Shunt-Type Master Box: 24 VDC <br /> @ 5 A maximum <br /> Reverse Polarity Type: 24 VDC <br /> @ 100 mA maximum <br /> - 6 - <br />