Table 3. Unit MCA and MOP electrical data(standard indoor fan motor)(cooling or gas)(a) <br /> Table 3. Unit MCA and MOP electrical data(standard indoor fan motor)(cooling or gas)(a) T/YSC Volts MCA MOP <br /> T YSC Volts MCA MOP 120 575/3 22 25 <br /> 036 208-230/3 20 30 (a)For MCA/MOP of units with electric heat,refer to product catalog. <br /> 036 460/3 10 15 <br /> 036 575/3 8 15 <br /> 048 208-230/3 26 35 Table 4. Unit indoor fan data(cooling or gas) <br /> 048 460/3 11 15 T/YSC Volts Standard HP-RPM Oversize HP-RPM <br /> 048 575/3 10 15 036 208-230/3(a) 3/4-MULT 1 MULT <br /> 060 208-230/3 29 40 036 460/3(a) 3/4-MULT 1-MULT <br /> 060 460/3 13 15 036 575/3 a 3/4-MULT 1 MULT <br /> 060 575/3 10 15 048 208-230/3(a) 1-MULT 1-MULT <br /> 072 208-230/3 35 50 048 460/3(a) 1 MULT 1 MULT <br /> 072 460/3 17 25 048 575/3 a 1-MULT 1-MULT <br /> 072 575/3 13 20 060 208-230/3(a) 1-MULT 1-MULT <br /> 090 208-230/3 38 60 060 460/60/3 a 1 MULT 1 MULT <br /> 090 460/3 19 30 060 575/3(a)(b) 1-MULT 1-MULT <br /> 090 575/3 15 20 072 208-230/3 1/1750 2/1750 <br /> 092 208-230/3 39 50 072 460/3 1/1750 2/1750 <br /> 092 460/3 18 20 072 575/3 1/1750 2/1750 <br /> 092 575/3 15 20 090 208-230/3 1/1750 3/1750 <br /> 102 208-230/3 44 50 090 460/3 1/1750 3/1750 <br /> 102 460/3 21 25 090 575/3 1/1750 3/1750 <br /> 102 575/3 16 20 092 208-230/3(c) 1/1750 3/1750 <br /> 120 208-230/3 49 60 092 460/3(0 1/1750 3/1750 <br /> 120 460/3 22 25 092 575/3 1/1750 3/1750 <br /> T <br /> 4. Unit indoor fan data(cooling or gas)(continued) �T�able5. Unit dimensional data(continued) <br /> T/YSC Volts Standard HP-RPM Oversize HP-RPM C D F <br /> 102 208-230/3 2/1750 3/1750 Supply Width SW(a) 343/8 343/8 177/8 <br /> 102 460/3 2/1750(c) 3/1750 Return Length RL(a) 18 1/4 18 1/4 14 19/16 T <br /> 102 575/3 2/1750 3/1750 Return Width RW(a) 343/8 343/8 253/16 e <br /> 120 208-230/3 2.75 MULT — (a)Dimensions are for curb openings and not duct inserts. o <br /> 120 460/3 2.75-MULT — Reference the product catalog for duct insert dimensions. <br /> 120 575 a 2.75-MULT — �r <br /> (a)Direct drive motor <br /> (b)Powered through 575/230V transformer <br /> (c)Multi-speed and single zone VAVran fan option uses 2.75 MULT motor <br /> (d)Powered through 575/480V transformer qn Ingersoll Rand <br /> Table 5. Unit dimensional data Ingersoll Rand(NYSE:IR)advances the quality of life by creating comfortable,sustainable and efficient environments. <br /> C D F Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King®and Trane®—work <br /> Unit Length UL 885/8 885/8 697/8 c5 together to enhance the quality and comfort of air in homes and buildings;transport and protect food and perishables; <br /> Unit Width UW 53 1/4 53 1/4 441/4 and increase industrial productivity and efficiency.We are a global business committed to a world of sustainable <br /> Unit Height UH 407/8 467/8 407/8 C4 c3 progress and enduring results. <br /> Clearance C1 48 48 48 <br /> Clearance C2 36 36 36 Ingersoll Rand. T THERMO KING TRANE` <br /> Clearance C3 36 36 36 C1 C2 <br /> Clearance C4 36 36 36 <br /> Clearance CS 72 72 72 ingersollrand.com <br /> Curb Length CL 84 1/2 84 1/2 65 13/16 <br /> Curb Width CW 503/8 503/8 417/161 ngersol I Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. <br /> Supply Length SL(a) 18 1/2 18 1/2 163/4 <br /> �/� We are committed to using environmentally conscious print practices. <br /> a\ <br /> \T RT-PRC037AE-EN 14 Jan 2019 <br /> Supersedes RT-PRC037AD-EN(Oct 2018) 02019 Ingersoll Rand <br />