SCOPE OF WORK: ABBREVIATION LEGEND MATERIAL LIST (B.O.M.)
<br /> ABBREVIATION DESCRIPTION ABBREVIATION I DESCRIPTION ITEM SYM TOTAL PART NUMBER DESCRIPTION MANUFACTURER MOUNTING
<br /> 1. NEW INSTALLATION OF A KIDDE,NOVEC 1230 CLEAN AGENT FIRE AC ALTERNATING CURRENT MRCP MAIN RELEASING CONTROL PANEL
<br /> SUPPRESSION SYSTEM INCLUDING DETECTION AND CONTROL FOR THE AFF ABOVE FINISHED FLOOR INA MILLIAMP 1 8a-732001-sol AEGIS 2.0 RELEASING PANEL KIDDE 19" H x 14.25 W X 5" D
<br /> C
<br /> SERVER/IT ROOM WHICH IS A NORMALLY UNOCCUPIED ROOM.
<br /> AT AMP HOUR NAC NOTIFICATION APPLIANCE CIRCUIT 2 2 PS-1270 BATTERIES 12V 7 AMP HOUR POWER SONIC IN PANEL
<br /> 2. THE ALARM AND DETECTION PANEL WILL BE A CONVENTIONAL KIDDE AEGIS AHU AIR HANDLING UNIT NPT NATIONAL PIPE THREAD 3 2 711U PHOTOELECTRIC SMOKE DETECTOR ADDRESSABLE KIDDE TO DETECTOR BASE
<br /> 2.0 CONTROL PANEL. ALM ALARM NTS NOT TO SCALE 4 ® 2 701U SMOKE DETECTOR BASE 2-WIRE KIDDE 4" SO OR OCTAGON BOX
<br /> 3. BATTERY BACK-UP IS CALCULATED FOR 24 HRS STANDBY,5 MINS ALM. AWG AMERICAN WIRE GAUGE R REPLACE EXISTING DEVICE 5 ®201 1 MR-201/C/R MR RELAYS SPACE AGE 6.125" H X 3.25" W X 2.5" D � w
<br /> 4. DESIGNED FOR MAIN CLEAN AGENT CYLINDER ONLY,NO RESERVE CLEAN REAP BUILDING FIRE ALARM PANEL ROP RATE OF RISE 6 1 84-330001-001 DUAL ACTION PULL STATION w/LABELS KIDDE 1-GANG DEEP BOX
<br /> AGENT CYLINDER PROVIDED. B.O.M. BILL OF MATERIALS SHP SINGLE HAZARD PANEL ® ALEXANDER GOW
<br /> 7 1 84-100009-001 INDOOR SURFACE BACKBOX FOR ABOVE RED SGB-32S KIDDE -GANG DEEP eox
<br /> 5. THE NOVEC 1230 SYSTEM MINIMUM DESIGN CONCENTRATION IS 4.5%FOR
<br /> C CONDUCTOR sH SHIELDED FIRE EQUIPMENT CO.
<br /> CLASS A AND CLASS C ELECTRICAL FIRES AT LESS THEN 480 VOLTS. CFM CUBIC FEET PER MINUTE SLC SIGNALING LINE CIRCUIT 8 a 1 84-878752-010 PUSH BUTTON ABORT STATION KIDDE 2-GANG DEEP BOX 1436 NW 53RD STREET
<br /> 6. THE NOVEC 1230 SYSTEM IS PROVIDED WITH BOTH MANUAL AND AUTOMATIC CKT CIRCUIT SUPV SUPERVISORY 9 1 06-236881-001 BACK BOX FOR PUSH ABORT STATION KIDDE 2-GANG DEEP BOX SEATTLE WA.98107
<br /> ACTIVATION DEVICES. COM COMMON TRBL TROUBLE 10 Ds 1 76-600000-200 KEY MAINTENANCE DISCONNECT SWITCH (NOVEC 1230) KIDDE 2-GANG DEEP BOX PH:(206)632-2810
<br /> E EXISTING TW TWISTED 11 1 06-236881-001 BACK BOX FOR KEYED MAINTENANCE SWITCH KIDDE 2-GANG DEEP BOX
<br /> 7. THE SMOKE DETECTION SYSTEM IS CROSS-ZONED FOR PRE-DISCHARGE WWW.GOWFIRE.COM
<br /> ELR END OF LINE RESISTOR TYP TYPICAL
<br /> ACTIVATION. 12 1 MT-12/24-R SUPPRESSION ALARM HORN 24 VDC WHEELOCK 1-GANG DEEP BOX
<br /> 8. ALL SIGNALS WILL BE TRANSMITTED TO THE FIRE ALARM CONTROL PANEL IN FOL END OF UNE U.L. UNDERWRITER'S LABORATORY 13 2 061AVSLM243 SUPPRESSION ALARM LIGHT BLUE LENS, INCANDESCENT 24 VDC SPACE AGE 1-GANG DEEP BOX
<br /> FACP FIRE ALARM CONTROL PANEL V VOLTS
<br /> THE BUILDING. F.M. FACTORY MUTUAL INSURERS W WATT 14 F;Q 2 1GB1R SINGLE GANG BOX SPACE AGE 1-GANG DEEP BOX F �'
<br /> 9. ROOM INTEGRITY AND MIN/MAX PRESSURES WILL BE TESTED VIA RETRO-TEC GND GROUND WE, W P WEATHER PROOF 15 2 IGP1R SINGLE PLATE RED SPACE AGE COVER FOR BOX
<br /> FAN TEST SOFTWARE AND EQUIPMENT IN ACCORDANCE WITH NFPA 2001 HVAC HEATING VENTILATION & AIR CONDITIONING SCP SUPPRESSION CONTROL PANEL 16 1 85-486500-010 ELECTRIC CONTROL HEAD 24 VDC W/ CONTROL HEAD MONITOR KIDDE ON CYLINDER VALVE
<br /> ANNEX C.A MINIMUM CONCENTRATION OF 85%OF THE ADJUSTED MINIMUM cH
<br /> DESIGN CONCENTRATION SHALL BE HELD AT THE HIGHEST HEIGHT OF n 1 45-550121-001IN-LINE RELEASING clRculr DEVICE KIDDE AT ELECTRICAL ACTUATOR
<br /> PROTECTED CONTENT WITHIN THE HAZARD FOR A PERIOD OF 10 MINUTES OR 18 1 45-550201-001 NOVEC 1230 AGENT STORAGE CYLINDER 125# KIDDE FLOOR MOUNT W/WALL BRACKET
<br /> FOR A TIME PERIOD SUFFICIENT TO ALLOW FOR RESPONSE BY TRAINED 19 111 47-190000-001 NOVEC 1230 AGENT (FACTORY FILLED) KIDDE IN CYLINDER
<br /> PERSONNEL. 20 1 WK-283904-000 VALVE OUTLET ADAPTER 1-1/2" KIDDE ON CYLINDER VALVE OUTLET
<br /> 21 1 06-235432-001 CYLINDER MOUNTING BRACKET KIDDE ON CYLINDER O
<br /> 22 CO 1 45-194714-167 NOVEC 1230 DISCHARGE NOZZLE 3/4" 180 DEGREE, BRASS KIDDE ON DISCHARGE PIPING 5
<br /> 23 1 06-231866-760 WARNING SIGN "DO NOT ENTER" KIDDE ENTRANCE INTO PROTECTED SPACE 3
<br /> CLEAN AGENT FIRE SYSTEM NOTES NOVEC 1230 MECHANICAL INSTALLATION NOTES 24 1 WK-218270-000 WARNING SIGN "VACATE AT ONCE" KIDDE LOCATE NEAR HORN/LIGHT
<br /> 25 1 CUSTOM WARNING SIGN "SLOW PULSE, FAST PULSE, STEADY" KIRKLAND LOCATE AT HORN/LIGHTS
<br /> 1. DESIGN AND INSTALLATION OF THE CLEAN AGENT FIRE EXTINGUISHING 1. TANKS,BRACKETS,PIPING,NOZZLES,ETC.,ARE TO BE SURFACE MOUNTED AND EXPOSED.EXCEPTIONS ARE:
<br /> SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 2001(2018 EDITION). ABOVE"DROP-IN"FALSE CEILING TILES,WHERE SPECIFICALLY SHOWN OR LABELED ON THESE DRAWINGS.
<br /> 2. ALL PIPE DIMENSIONS ARE MEASURED FROM CENTERLINE OF FITTINGS TO CENTERLINE OF FITTINGS. -
<br /> 2. ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM APPROVED. 3. CHANGES IN PIPE DIRECTIONS,LENGTHS,SIZES,AND FITTINGS WILL CHANGE THE CALCULATED HYDRAULIC
<br /> FLOW.ANY CHANGES SHALL REQUIRE SECUREMENT OF ALEXANDER GOW FIRE EQUIPMENT APPROVAL TO INPUTS RESPONSES
<br /> 3. CLEAN AGENT EXTINGUISHING SYSTEM SHALL PROVIDE COVERAGE IN THE ASSURE PROPER NOVEC 1230 FLOW AND DISCHARGE CHARACTERISTICS.
<br /> DESIGNATED ROOM. 4. REFERENCE SHALL BE MADE TO THE MANUFACTURER'S INSTALLATION,OPERATION,AND MAINTENANCE
<br /> . y
<br /> 4. DEVICE LOCATIONS,PIPE AND CONDUIT ROUTINGS ARE CONCEPTUAL.FINAL MANUAL TO ASSURE STRICT ADHERENCE TO APPROVED INSTALLATION PRACTICESSUPPRESSION CONTROL PANEL y y o
<br /> QUANTITY AND LAYOUT SHALL BE IN ACCORDANCE WITH APPLICABLE CODES, 5. MATERIALS- MATRIX OF EVENTS
<br /> a. PIPE:BLACK OR GALVANIZED STEEL PIPE SHALL BE EITHER ASTM A 53 SEAMLESS OR ERW,GRADE A OR m m o o W n
<br /> MANUFACTURER'S RECOMMENDATIONS AND EQUIPMENT LISTINGS. B,OR ASTM A-106,GRADE A,B,OR C. m -
<br /> COORDINATE WITH MECHANICAL AND ELECTRICAL EQUIPMENT AND b. FITTINGS:MALLEABLE IRON 300 LB.CLASS SUITABLE FOR THE MATERIAL BEING USED.SCREWED 3 m
<br /> RACEWAYS. FITTINGS MAY BE OF MALLEABLE IRON 300 LB. CLASS ONLY-ASTM A-197;DUCTILE IRON 300 LB.ONLY- x=DESIRED RESPONSE o g w N
<br /> 5. MINIMUM DESIGN CONCENTRATION SHALL BE 4.50%AND THE MAXIMUM ASTM A- STEEL-ASTM
<br /> 6. THREADED CONASTM NECC TIONS-USE TEFLON
<br /> TAPE AND APPLY TO MALE THREADS ONLY. A=ABORT RESPONSE � � � o 0 0 0 4 � o p
<br /> DESIGN CONCENTRATION SHALL BE 10%.THE DESIGN TEMPERATURE IS 7. ALL GROOVED FITTINGS SHALL BE FM AND OR UL APPROVED AND HAVE A MINIMUM WORKING PRESSURE OF TD=RESPONSE AFTER TIME DELAY CHRIS SWANK
<br /> BASED ON 70oF.THE CONCENTRATION SHALL BE MAINTAINED OVER THE 468 PSIG AT 70°F. 8P., P ' - 3 Senior Enginee ng Technician,Level IV
<br /> TEMPERATURE RANGE ABOVE.. 8. ALL PIPE AND FITTINGS ARE TO BE REAMED,BLOWN CLEAR AND THOROUGHLY CLEANED WITH APPROPRIATE SYSTEM NORMAL X NICD Certification Number:108282
<br /> 6. THE MINIMUM PROTECTED HEIGHT WILL BE DETERMINED ON SITE.THESOLVENT TO REMOVE MILL VARNISH,CHIPS,AND CUTTING OIL BEFORE ASSEMBLY. TROUBLE CONDMON x x
<br /> 9. IMPORTANT:PIPING TO BE RIGIDLY SUPPORTED BY UL APPROVED HANGERS. SOPERvISOW WN-ON x x
<br /> CONCENTRATION SHALL BE MAINTAINED A MINIMUM OF 10 MINUTES. 10. CAUTION:NOVEC 1230 TANKS MUST BE LOCATED WITHIN A TEMPERATURE RANGE OF: +32°F TO+130°F.DO MANOAE 10-E-IoN X x x m x x
<br /> NOT LOCATE THE NOVEC 1230 CONTAINER WHERE IT MAY BE SUBJECT TO DAMAGE.
<br /> 7. PIPING AND FITTINGS SHALL COMPLY WITH NFPA 2001.PIPING SHALL BE POT SMOKE DETEOTSR-1ST DEFSOTOR x x x
<br /> PROVIDED WITH EARTHQUAKE PROTECTION. 11. ALL DEVICES AND EQUIPMENT SHALL BE OF THE MAKE AND TYPE LISTED BY U.L.AND/OR APPROVED BY F.M. POT MOVE - X X X TD X X TO
<br /> 12. NOVEC 1230 CYLINDER ASSEMBLIES SHALL BE OF THE MANUFACTURER'S STANDARD CAPACITY AND FILLED ABORT S TCH ErE x x A A A
<br /> LIJ
<br /> 8. FIRE PROTECTION CONTRACTOR SHALL ADVISE THE GENERAL CONTRACTOR PER REQUIREMENTS OF NFPA 2001. Novcc 1230 nNDER DISCONNECT/BY-PASS SW. X x A
<br /> TO SEAL ALL PENETRATIONS IN THE PROTECTED SPACE,INSTALL WEATHER 13. FILLING OF THE TANK ASSEMBLY SHALL BE BY A FACTORY AUTHORIZED,U.L.LISTED FILLING STATION. X X O
<br /> STRIPPING AND SWEEPS ON THE DOORS. 14. NAMEPLATES INDICATING THE MANUFACTURER'S NAME,PART NUMBER,AGENT FILL WEIGHT,TOTAL m
<br /> CHARGED WEIGHT,DATE OF INITIAL FILL,AND U.L.LISTED FILL STATION CODE SHALL BE BONDED TO EACH
<br /> 9. PROVIDE INSPECTION AND TESTS IN ACCORDANCE WITH NFPA 2001,NFPA 72 TANK.
<br /> 15. DISCHARGE NOZZLES SHALL BE AS COMPUTER CALCULATED,IF PART OF AN ENGINEERED SYSTEM,OR AS W
<br /> AND SPECIFICATION SECTION,INCLUDING A ROOM INTEGRITY TEST. z
<br /> MANUFACTURED,IF PART OF A PRE-ENGINEERED SYSTEM.THE NOZZLES WILL PRODUCE AN APPROXIMATE / ` L1J
<br /> 180 DEGREE,OR 360 DEGREE PATTERN AND MUST BE PROPERLY ORIENTED OR AIMED. v O
<br /> 16. NOZZLES MUST BE INSTALLED SO THAT THE ORIFICES ARE LOCATED 6 TO 12 INCHES BELOW THE CEILING. �
<br /> 17. 180 DEGREE NOZZLES MUST BE LOCATED+/-6INCHES FROM A WALL,WITH THE ORIFICES DIRECTED AWAY WORK AND MATERIALS NOT INCLUDED IN OUR SCOPE OF WORK _ z
<br /> FROM THE WALL. O
<br /> 18. 360 DEGREE NOZZLES MUST BE LOCATED AS CLOSE TO THE CENTER OF THE ENCLOSURE AS POSSIBLE. CLEAN AGENT FIRE SUPPRESSION INTERFACE REQUIREMENTS. I„u O
<br /> DRY CONTACTS WILL BE PROVIDED BY ALEXANDER GOW FOR THE FOLLOWING INTERFACES. z
<br /> 1. H.VAC. SYSTEM SHUT-DOWNS Z N O Q O
<br /> 2. CLOSURE OF DAMPERS. (DAMPERS SUPPLIED BY OTHERS) J Q
<br /> FIRE SPRINKLER SYSTEM NOTES 3. CONNECTIONS TO EPO SWITCHES (EPO SWITCHES SUPPLIED BY OTHERS) FQ �
<br /> THE SERVER/IT ROOM CURRENTLY HAS A WET FIRE SPRINKLER SYSTEM INSTALLED. UPON COMPLETION OF THE INSTALLATION OF 4. CONNECTIONS TO BUILDING FIRE ALARM SYSTEM FOR MONITORING OF ALARM, TROUBLE AND SUPERVISORY SIGNALS z O
<br /> THE NOVEC 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEM AND THE FIRE FINAL INSPECTION, THIS WET FIRE SPRINKLER SYSTEM CLEAN AGENT FIRE SUPPRESSION SYSTEM REQUIREMENTS
<br /> WILL BE CAPPED OFF OUTSIDE OF THE SERVER/IT ROOM. MAKING THE SERVER/IT ROOM NO LONGER PROTECT BE THE FIRE 1. SEALING OF THE CLEAN AGENT FIRE SUPPRESSION ENCLOSURE. Q 7-- CD
<br /> SPRINKLER SYSTEM. MIKE WISLER ASSISTANT FIRE MARSHALL WITH EVERETT FIRE PREVENTION HAS APPROVED OF CAPPING OF THE W W
<br /> FIRE SPRINKLER SYSTEM FOR THE SERVER/IT ROOM. w
<br /> w cn v
<br /> FMOUNT AGENT RELEASE L>LJ (n W
<br /> LIGHT ABOVE ENTRY DOOR.
<br /> O LiJ Z �
<br /> ROOM SEALING NOTES: Q
<br /> REQUIREMENTS FOR SEALING ROOMS THAT ARE PROTECTED BY AGENT. O W w
<br /> SIGNFig
<br /> a_
<br /> (---
<br /> DOOR PROBLEM SOLUTION U CD
<br /> OUTSIDE W
<br /> OF ROOM EE POROUS CONCRETE PAINT WITH SEALANT !1 Q
<br /> 88 ELECTRICAL PANELS 1-HOUR RATED DUPONT TYPE SEALER `J <
<br /> 6'-0.. OPEN CONDUIT DUCT SEALER W w
<br /> WALL PENETRATIONS 1-HOUR RATED DUPONT TYPE SEALER
<br /> 0^ O �_ z
<br /> 4._0..
<br /> CRACKS IN CONCRETE CAULKING O
<br /> DAMPERS SMOKE DAMPERS ONLY, NO FIRE DAMPERS
<br /> JUNCTION AT WALL & FLOOR CAULKING (INSIDE OF ROOM) DRAWN BY: JOE SHELDON
<br /> PLENUM LIGHT FIXTURES COMPLETELY WEATHER-STRIPPED
<br /> cREORRDex: CHRIS swANN
<br /> DOORS WEATHER-STRIPPING, BOTTOM SWEEPS,
<br /> AND DOOR CLOSERS ARE REQUIRED. PLOT DATE: 5/12/23
<br /> EQUIPMENT MOUNTING DETAILe HOLDERS REQ'D. IF DOORS ARE TO BE OPEN. PROJECT NUMBER: 21835
<br /> SCALE: NTS
<br /> THIS IS NOT A COMPLETE LIST. THE ROOM MUST BE SEALED SO AS NICET CERTIFICATION
<br /> NOTES:
<br /> 1. DETAIL NOT INTENDED TO SHOW SPATIAL RELATIONSHIP OF DEVICES. TO BE VIRTUALLY AIR-TIGHT. ALEXANDER GOW IS NOT CHRIS SWANN F S O 1
<br /> CERTIFIED ENGINEERING TECHNICIAN
<br /> REFERENCE FLOOR PLANS FOR ACTUAL LOCATIONS. RESPONSIBLE FOR THE SEALING AND INTEGRITY OF THE ROOM. NICET CERTIFICATION NO.:108282
<br /> EXPIRATION DATE:05/01/2024
<br /> FIRE ALARM SYSTEMS LEVEL N
<br /> SPECIAL HAZARDS SUPPRESSION SYSTEMS LEVEL IV SHEET NUMBF.I: