SUPV.-1 CKT. ABORT MANUAL RELEASE <br /> END-OF-LINE RESISTOR END-OF-LINE RESISTOR END-OF-LINE RESISTOR <br /> 5.1 K+/-5%,O.5W 5.1 K+/-5%,0.5W 5.1 K+/-5%,0.5W i <br /> ELECTRICAL SUPERVISION <br /> 1.A SHORT CIRCUIT FROM ANY FIELD-WIRING TERMINAL(EXCEPT AC POWER INPUT TERMINALS AND <br /> BLUE WHITE ABORT SWITCH MANUAL RELEASE FORM-C RELAY TERMINALS)TO EARTH GROUND WILL CREATE A'GROUND FAULT'TROUBLE CONDITION <br /> 2.AN OPEN CIRCUIT IN THE PARING FOR THE INPUTS(SUPERVISORY CIRCUITS,ABORT,MANUAL <br /> RELEASE,DETECTOR CIRCUITS).THE OUTPUTS(NACS AND RELEASE CIRCUITS).AND THE BATTERY <br /> CONTROL HEAD MONITOR CHARGING CIRCUIT HILL CREATE AN'OPEN'TROUBLE CONDITION. <br /> 3.A SHORT CIRCUIT BETWEEN CONDUCTORS IN THE WIRING FOR THE OUTPUTS(NACS AND RELEASE <br /> DETECTOR CIRCUIT CIRCUITS),AND THE BATTERY CHARGING CIRCUIT WILL CREATE A'SHORT*TROUBLE. 4mw <br /> BLUE WHITE A (CROSS ZONE CONFIGURATION) 4.IMPEDANCE VALUES FOR OPEN CIRCUIT AND SHORT CIRCUIT CONDITIONS ARE;OPEN CIRCUIT:INFINITE ALEXANDER GOW <br /> OHMS SHORT CIRCUIT:ZERO(0)OHMS. <br /> FIRE EQUIPMENT CO. <br /> A A (-) 2 , (-) 1436 NW 53RD STREET <br /> , END-OF-LINE RESISTOR INPUT CIRCUITS(TYPICAL FOR ALL CIRCUITS) <br /> 5.1 K+/-57 0.5 W CLASS B SEATTLE WA.98107 <br /> I*) SEE INSTALLATION,OPERATION&MAINTENANCE MANUAL PH:(206)632-2810 <br /> I+) P/N 06-236716-001,FOR WIRING IMPEDANCE LIMITATIONS. WWW.GOWFIRE.COM <br /> TO MAINTENANCE A <br /> BY-PASS SWITCH 28 VDC MAX. <br /> A 100 MA MAX. <br /> DETECTOR CIRCUIT GENERAL NOTES F <br /> CONNECTIONS BY (CROSS ZONE CONFIGURATION) 1.WIRE SIZES FOR ALL TERMINAL BLOCKS IS 12-18 AWG. <br /> ®® ®® ® e (®® 000 0® 2.EARTH GROUND OFFSET VOLTAGE IS 6.6 VDC(NOM.)RELATIVE TO SYSTEM COMMON(E.G.TB16 <br /> BLDG. FIRE ALARM wa2 wR1 ABORT xax El s ETJ DET2 <br /> CONTRACTOR R5_P34 -2 I+ 1 2 ++ )� i ewe <br /> 1-2 z++ 1-2 2 1+ 1 z +1+ (-) (_) 3.ROUTE NON-POWER LIMITED WIRING AT LEAST Y4INCH AWAY FROM ALL POWER-LIMITED WIRING. <br /> 0 iE Tab i 1 T35 Teo Tea Tee 2 3 4.DO NOT ATTACH POWER LIMITED AND NON-POWER LIMITED WIRING TO THE SAME TERMINAL BLOCK. <br /> TROUBLE � supervisory 2 supernsory 1 ( ) Abort Manual WaterBaw/ Detector 2 A END-OF-LINE RESISTOR <br /> ®� w Release Detector 3 5.1 K+/-5%0.5 W 5.END-OF-LINE RESISTOR,5.1K+/-55 0.5W IS P/N 06-129025-002 <br /> TO MAIN BUILDING FIRE ALARM ®, � f=® (*) BATTERY CIRCUIT <br /> ALARM PANEL L _ SEALED,LEAD-ACID BATTERIES ONLY.MAXIMUM 68AH. z <br /> ®„ a REPLACE EVERY 3 YEARS OR AS RECOMMENDED BY BATTERY MANUFACTURER. C <br /> SUPERVISORY ®e 0 Na. 0 s;�„�o O,__. � CHARGING CIRCUIT VOLTAGE:270(NOM.) <br /> P ® O ea- � CHARGING CIRCUIT CURRENT:6.OA(MAX.) 5 <br /> 0 PasT-maria <br /> FF ®`n O a<N O wu SEE INSrALLATION,OPERATION&MAINTENANCE MANUAL,P/N 06-236716-001,FOR SUITABLE 3 <br /> O % O � O+ +� BATTERY TYPES AND STANDBY OPERATING TIMES. <br /> T612 O/"�37 O/%M31 O >aO S.STrN.uN S B S NOTIFICATION APPLIANCE CIRCUITS <br /> ° la.Sa <br /> 1 ®� O O ar ,ai O Srs,EN re` lsaa) <br /> O saaop,NT O SaoNT�rex O O PSus,TNa �❑�❑�❑�❑ <br /> (TYNPGIC:CALLASFSOR AL <br /> L CIRCUITS) <br /> REGULATED 24VDC <br /> O O O WIRIO <br /> A,STYLE Z OR CLASS B,STYLE Y <br /> 'a Batt Oat0 Supt O SUPS Td O NM rex p c+owTeL <br /> WIRING SHOWN IN SOLID LINES.ADDITIONAL WIRING FOR CLASS A,STYLE Z SHOWN IN DASHED LINES <br /> c c c (EOL DEVICE AT TERMINAL BLOCK). <br /> MOUNT RELAYSUITABLE FOR SYNCHRONIZED AND NON-SYNCHRONIZED NOTIFICATION APPLIANCES.USE POLARIZED <br /> Kidde AEGIS 2.0 Control Panel END-OF-LINE RESISTOR NOTIFICATION APPLIANCES ONLY. <br /> SCP IN 3'-0' OF 5.1 K+/-57 0.5 W MAXIMUM SINGLE NOTIFICATION APPLIANCE CURRENT:I.5A <br /> ® ® SEE INSTALLATION,OPERATION&MAINTENANCE MANUAL,P/N 06-237463-001,FOR WIRING IMPEDANCE <br /> UU F.N <br /> + _ _ + NOTIFICATION- LIMITATIONS. <br /> APPLIANCE CIRCUIT <br /> ffi BLUE OGHT BLUE 11CJIT <br /> appySent Switc ( ) r ® RELEASE CIRCUITS <br /> AC SlSm <br /> h56 <br /> _ N1-1 111-2 N1-3 (TYPICAL FOR ALL CIRCUITS) <br /> TB16 Auxiliary OutputX19 15CD 15CD VOLTAGE-24VDC(NOM.) <br /> Regulated 24 VDC CURRENT:2.4A(MAX.) <br /> White Current:1.0(max.) USE THE FOLLOWING RELEASING DEVICES ONLY: <br /> 120 VAC, 5060 HZ, 3.2 A Block -_ 2allo/,esase 1 Release 2 Aux 24 INC NAC 3 ® DEVICE TYPE MODEL NOS. CHRIS SWANN <br /> BY SITE ELECTRICAL CONTR. 120 ^a^�- ten- ++-- t++ 1- + INITIATOR 83-131025-001 Senior En neerin Technician,Level IV <br /> Green TBI3 n aRa m aacz" z rete CONTROL HEADS 890181,895630,899175,897494,48650001,81-100000-001, 9' a <br /> rrE T814 ®® 7816 ®® 161 7617 ®® ® NICE[Certii¢alian Number:108282 <br /> 06-118329-001 (FM ONLY)06-118384-001 (UL ONLY),87-120099-001,90-487100-001, <br /> 38-509837-001,38-509834-001 <br /> TO EARTH-GROUND STUD = PRE-ACTION/DELUGE FM GROUPS A B,D,E,G,I,J AND K VALVES FOR POWER LIMITED,USE <br /> 51 K 57%, <br /> ON SIDE OF BACK BOX END-OF-LINE 0RESISTOR IN-UNE RELEASING DEVICE P/N 06-220023-001 (REFER TO SINGLE SOLENOID CIRCUIT FOR WIRING). <br /> P . +/-5 .5 w(TVP) CONTROL HEAD P/N 83-100034-001 AND MICRO SWITCH P/N 87-120039-001 <br /> IN-LINE RELEASING DEVICE,P/N 06-220023-001 <br /> (MUST BE CLOSE NIPPLED TO ACTUATOR ENCLOSURE) RELAY-CONTACT RATING Uj <br /> UBLK RED BLK O 3.OA 0 1320 AC (((RESISTIVE) <br /> INSTALL CIRCUIT BREAKER HANDLE CLAMP - <br /> ON CIRCUIT BREAKER DEDICATED TO THE z <br /> + <br /> CONTROL PANEL. PER FIRE MARSHAL. RED <br /> A ELECT.ACTUATOR Z <br /> SUPV-2 ON AGENT CYLINDER <br /> INPUT CKT. <br /> Kidde � � 12-V 7ah 12-V 7ah ~ <br /> A9narw KLA 01721 Battery Battery NO _ z Q <br /> Fire Systems CD <br /> Y Phore:(SOB)8B 1-2000 �A�N 10K OHMS W 6F777 <br /> J <br /> /2 W N <br /> O� Q Q <br /> Battery Calculation <br /> NO 0-) J U <br /> (.AEGIS 2.0 and AEGIS-XLT) C Al Q Q (-D <br /> Version 1.1,20171 _ <br /> rater Distributorintormabon: KIDDE AEGIS 2.0 RELEASING PANEL (j) <br /> Name:Alexander G..Fre E of Ment SCALE: NTS NO z <br /> Project Name:PUGET SOUND KIDNEY CENTER C <br /> Service Request#:21875 &NO <br /> Prepared By:Chris Swann C R Q Description:SERVER.9T ROOM <br /> NO FLAG NOTES: W W <br /> C <br /> + NO GN z LTJ <br /> mee m.�y„aea �rwa �awo�..na see "amx raw. x 0 THESE (3) KNOCK-OUTS RESERVED FOR NON-POWER W <br /> ,:.a�.vo,nwm.san.a as nmax.e:a,a n�HruA aaaledaLiJ (D <br /> Power Su I and Batts Sire CaICUlatian - LIMITED WIRING ONLY, INCLUDING 120VAC POWER. � � <br /> A Tau sleld-a CunnH .5 t< 0.131A.I. 24VDC POWERZ (� <br /> B TOIalAiermGuroM ews tem: , CYLINDER DISCONNECT SWITCH Q THIS KNOCK-OUT RESERVED FOR CONNECTIONS TO A O w <br /> PART#76-600000-200 <br /> C EMerSLrq-B Hwn: z H- BATTERY BOX ONLY, WHEN USED. Q Z <br /> 0 Er4w Alarm Tine: 5 1Fnele U) U <br /> E Aem eae Hou P alaied BAC"'Dll: 32 AH <br /> F TOLL Amp Abu ReNerire IDewaLg Faaa 121: 4.00 AH RIOM{tick to Update.Prim arq <br /> U �LJ <br /> G 8a6e Slee 'red stem R2 bean i:e keel[ AH CRe/B&w y Cekr4aean. L- LLJ <br /> W <br /> LLJ <br /> Q <br /> WIRE TAG DESCRIPTION <br /> TAG ID CABLE TYPE WIRE DESCRIPTION FUNCTION W <br /> A TEN BLK/ORG 2 CONDUCTOR, 16 AWG- TEN ZONEUnit Unit Unit Unit <br /> O <br /> B TEN BLK/ORG 4 CONDUCTOR, 16 AWG- TEN ZONE LOOPft.. Enter Curaent Current Current Cuirrewt <br /> LL Z LL <br /> C THHN RED/BLUE 2 CONDUCTOR, 14 AWG- THHN HORN/STROBE <br /> 1 Corm�l Umi 11 .100 0.100 0240 0.24 D THHN RED/BLUE 4 CONDUCTOR, 14 AWG- THHN HORN/STROBE LOOP DRAWN BY: JOE SHELDON <br /> 2 Pm9ramnraDle Relay •t 0.000 0.000 OA20 0.08 <br /> 3 De1eCLln Ceatil#1 1 0.007 0.0 OA70 0.07 E THHN BRN/YL 2 CONDUCTOR, 14 AWG- FPLP DOOR CONTROL CHECKEDBY: CHRIS SWANN <br /> 4 Detect=Gast#2 1 0.000 OA 0.070 0.07 F THHN ORG 2 CONDUCTOR, 14 AWG- FPLP FAN SHUTDOWN <br /> 5 Detect=C-Al#41 Su use #1 1 0.070 OA00 OD70 0.07 PLOT DATE: 5/12/23 <br /> 6 Sdp-y Ckaat 02 1 0.000 oA 0.010 0.01 N TWISTED`PLP RED/BLK 2 CONDUCTOR, 16 AWG- FPLP NETWORK COMMUNICATION <br /> 7 Manual Release CGcu4#1 1 0.000 OAOD 0.010 0.01 P FPLP RED/BLK 2 CONDUCTOR, 14 AWG- FPLP 24VDC POWER PROJECT NUMBER: 21835 <br /> 8 Abat Cffwd#1 1 0.009 OA 0.010 0.01 <br /> 9 Pt1aa11ectnc Smoke Detects 2NAre,711U 2 OA'.0 0.020 OD00 0.00 U FPLP RED/BLK 2 CONDUCTOR, 14 AWG- FPLP SUPPRESSION RELEASE N�CET CERTIFICATION nTo^I <br /> 10 NAC Ciraal#1 AEGIS-XLT can be ARC#3 1 0.000 OA 0230 0.23 V L CLI\I I CAI I V <br /> 11 Releal Grcu##1 1 E_.g OR 0240 0.24 <br /> 12 MR 201 Relay 1 0.000 OA 0.035 0.03 CHRIS SWANN <br /> 13 Blue - is 0.000 OA OD96 0.19 CERTIFIED ENGINEERING TECHNICIAN F 04 <br /> 14 M724 Flan / 0.000 OA 0.036 0.03 NICET CERTIFICATION NO.:108282 <br /> 024 <br /> 15 ManeD-nnea SrM n 1 0.011 OA11 OD11 0.011 EXPIRATION DATE:OS/01/2Mane- <br /> FIRE ALARM SYSTEMS LEVEL N <br /> SPECIAL HAZARDS SUPPRESSION SYSTEMS LEVEL IV SHEET NUMBER: <br />