BACKWARDS COMPATIBILITY TECHNICAL SPECIFICATIONS (cont'd) <br /> The AEGIS 2.0 is backwards compatible and listed for One (1)Abort Circuit <br /> use with a full range of conventional detectors and alarm -Compatible with normally open contact-closure type <br /> devices as well as suppression accessories from Kidde, devices <br /> Fenwal and Chemetron. Going forward, this will allow - Configurable as Class A or Class B <br /> legacy panels to be replaced with relative ease. - Supervised for ground faults and open circuits <br /> EASY TO INSTALL CABINET - Six (6)Abort Modes available <br /> The cabinet design allows for easy installation by fitting - Power-limited <br /> between the studs of a standard 16 inch studded wall. It Two (2) Supervisory Circuits <br /> is large enough to house two 12 VDC, 12 AH Batteries -Compatible with normally open contact-closure type <br /> and provides up to 2 inches (51 mm) of wiring and finger devices <br /> space between the circuit board and the cabinet wall. - Configurable as Class A or Class B <br /> An optional door design features a Manual Release and - Option to use SUP 1 as fourth detection circuit <br /> Abort switch for applications with space constraints. Both - Supervised for ground faults and open circuits <br /> switches incorporate guards that prevent their - Power-limited <br /> inadvertent activation. Three (3) Notification Appliance Circuits (NACs) <br /> TECHNICAL SPECIFICATIONS -Compatible with polarized 24 VDC regulated Audio- <br /> Hazards Protected Visual devices <br /> • - Rated at 1.5 Amps each <br /> - One - Up to 35 synchronized appliances <br /> • Power Supply - Configurable as Class A or Class B <br /> - 120/240 V, 50/60 Hz (90 to 264 VAC, 47 to 63 Hz) - Supervised for ground faults, shorts, and open <br /> AC Main Input circuits <br /> -5.4 Amps at 27 VDC Output - Power-limited <br /> - Battery capacity up to 68 AH @ 24 VDC - Common NAC/ARC output disable switch <br /> -Auxiliary power output rated Class B at 1 Amp at Two (2) Agent Release Circuits <br /> 18.8 - 27.6 VDC (resettable) - Each compatible with 1 or 2 control heads, or 1 <br /> • Three (3) or Four(4) Detection Circuits actuator/initiator, or 1 FM sprinkler solenoid <br /> - Compatible with ESL/Interlogix 700 Series - Circuits electrically capable of simultaneously <br /> detectors, CPD-705x, PSD-715x, and THD-705x releasing any combination of two of the above <br /> detectors, as well as Normally Open contact devices <br /> closure type devices. Refer to documents K-70-100 - Factory configured as Class B <br /> and F-70-63 for details on compatibility and the - Supervised for ground faults and open circuits <br /> maximum number of devices supported. - Default setting: Power-Limited. Each solenoid on a <br /> - Configurable as Class A or Class B power-limited ARC requires the use of an in-line <br /> - Supervised for ground faults and open circuits releasing device, P/N 06-220023-001 (order <br /> - Power limited separately, not included with panel). <br /> - DET 1 and DET 2 used for suppression - Common NAC/ARC output disable switch <br /> - DET3/WF configurable for detection or waterflow Four(4) Relays <br /> - Option to use SUP 1 circuit as DET 4 circuit* - 3 independently programmable, normally de- <br /> • One (1) Manual Release Circuit energized Form-C Relays <br /> -Compatible with normally open contact-closure type - 1 dedicated normally energized Form-C Trouble <br /> devices Relay <br /> - Configurable as Class A or Class B - Relay contacts rated 3 Amps at 30 VDC (resistive) <br /> - Supervised for ground faults and open circuits <br /> - Power limited <br /> • Only contact-closure type, non-powered devices such as <br /> switches, pull stations and alarm contacts of 4-wire detectors <br /> to be used on this Detector 4 circuit. Powered 2-wire <br /> automatic detectors must not be connected to this circuit and <br /> the circuit must not be used to power 4-wire detectors. <br /> - 4 - <br />