A I B C D E F G I H <br /> LOAD CALCS-TOTAL AMPS AVAILABLE <br /> MAX AC OPERATING CURRENT CALCS <br /> BUS RATING 120% TOTAL MAIN BREAKER MAX BREAKER SIZE <br /> 200A X 1.2 - 240 200A = 40A #OF MICROINVERTERS MAX OUTPUT CURRENT MAX AC OPERATING CURRENT <br /> 10 x 1.25 = 12.50A <br /> COMBINER BOX PANEL SIZE CALCS <br /> CIRCUIT# <br /> NUMBER OF NUMBER OF NOMINAL OUTPUT TOTAL 125% BREAKER SIZE TOTAL BREAKER SIZE CALCS <br /> � MODULES MICROINVERTERS CURRENT IN AMPS AMPS � <br /> CIRCUIT 1 10 10 x 1.25 = 12.50 x 1.25 = 15.63 = 20A MAX AC OPERATING CURRENT 125% TOTAL BREAKER SIZE <br /> 12.50A x 1.25 x 15.63A = 20A <br /> NOTES: UTILITY METER(E) <br /> 1. 200A UTILITY METER GLOBE ONLY.(EXISTING) <br /> N 2. 200A LOAD CENTER INSTALLED WITH SURGE N <br /> PROTECTION.(NEW) <br /> 3. 60A RATED NON-FUSED LOCKABLE AC DISCONNECT. TO UTILITY <br /> (NEW) 1 GRID(E) <br /> 4. 125A RATED COMBINER PANEL.(NEW) <br /> ZI <br /> ALL CONDUIT SIZES ARE MINIMUM SIZES <br /> ALL WIRE SIZES ARE FOR COPPER WIRE <br /> (2)8 AWG (2)8 AWG2 VERIFY WIRE <br /> (1)8 AWG EGC (1)8 AWG EGC SIZE AIN SERVICE PANEL(N) <br /> co W <br /> T <br /> q <br /> I I <br /> 4 <br /> 200A <br /> MAIN SERVICE <br /> DISCONNECT(E) <br /> CIRCUIT#1 - 10 ZNSHINE ZXM6-60-320/B <br /> MODULES <br /> WITH HOYMILES MI-300 MICRO INVERTERS <br /> U o (2)8 AWG <br /> (1)8 AWG EGC <br /> a3 <br /> `1O� . . . `2J `1J "= 3 <br /> 20A LOAD-SIDE _j <br /> (2)12 AWG SOLAR OCPD <br /> t (1)8 AWG EGC (Opposite end of the main disconnect <br /> on the busbar-NEC 705.12(B)(3) <br /> LO cn <br /> DRAWN BY: DRAWING SCALE: <br /> CONFIDENTIAL-THE INFORMATION CONTAINED ARM NOT TO SCALE <br /> IN THIS PACKET AND SUBSEQUENT CUTSHEETS Dale Hamilton DATE: DESIGN <br /> SHALL NOT BE USED FOR THE BENEFIT OF SOLGEN POWER <br /> SO LG E N <br /> ANYONE OUTSIDE SOLGEN POWER. NEITHER 5100 ELM RD, 7/9/2021 <br /> SHALL IT BE DISCLOSED TO OTHERS OUTSIDE PASCO, WA 99301 1 <br /> P O W E R THE RECIPIENT'S ORGANIZATION, EXCEPT IN PAGE# <br /> CONNECTION WITH THE SALE AND USE OF THE P: 509-931-1663 1915 - 122nd PL SE, Everett, WA 98208 <br /> RESPECTIVE EQUIPMENT, WITHOUT WRITTEN PV <br /> CONSENT FROM SOLGEN POWER. <br />