Laserfiche WebLink
VESDA-E VEU xtralis® <br />TECHNICAL SPECIFICATIONS <br />Specifications 3.5" Display <br />Supply Voltage <br />18-30 VDC (24 V Nominal) <br />Power Consumption C <br />VEU-A00 <br />VEU-A10 <br />24VDC <br />Aspirator Setting <br />1 <br />5 <br />10 <br />1 <br />5 <br />10 <br />Power (Quiescent) <br />7.0 W <br />8.8 W <br />14.7 W <br />8.2 W <br />10.0 W <br />15.8 W <br />Power (In Alarm) <br />7.8 W <br />9.6 W <br />15.5 W <br />10.4 W <br />11.6 W <br />16.6 W <br />Dimensions (WHD) <br />350 mm x 225 mm x 135 mm (13.8 in x 8.9 In x 5.3 in) <br />Weight <br />4.83 kg (10.6 Ids) 4.9 kg (10.8 lbs) <br />Ambient: 0°Cto 39°C (32°Fto 1020F) <br />Sampled Air: -20oC to 60°C (-4°F to 140°F) <br />Operating Conditions <br />Tested to: -20°C to 55°C (-4°F to 131°F) <br />UL -20°C to 50°C (-4°F to 122°F) <br />Humidity: 51)/oto 95% PH, non -condensing <br />Maximum area of coverage <br />6,500 m2 (69,965 sq.ft)* <br />Minimum airflow per pipe <br />15 Vm <br />1 Pipe <br />2 Pipes <br />3 Pipes <br />4 Pipes <br />Pipe lengths depending on <br />number of pipes in use <br />160 m <br />150 m <br />130 m <br />100 m <br />(524 ft) <br />(492 ft) <br />(426 ft) <br />(328 ft) <br />Maximum pipe lengths <br />Total Pipe Length (with branches): 800 m (2625 ft) <br />StaX <br />PSU, Auto Pipe Clean <br />No. of holes (A/B/C) <br />80/80/100 <br />Computer design tool <br />ASPIRE <br />Inlet: External diameter 25 mm or 1.05 in (3/4 in IPS) <br />Pipe <br />Exhaust: External diameter 25mm or 1.05 in (3/4 in IPS) via <br />adaptor <br />Relays <br />7 programmable relays (latch or non -latch states) <br />Contacts rated 2A @ 30 VDC (Resistive) <br />I rating <br />IP40 <br />Cable access <br />4 x 26 mm (1.02 in) cable entries <br />Cable termination <br />Screw Terminal blocks 0.2-2.5 sq mm (24-14 AWG) <br />Dynamic Range <br />0.0002%/m (0.00006% obs/ft) to 20% obs/m <br />(6.25 /o obs/ft) <br />Sensitivity Range <br />0.001%- 20.0% obs/m (0.0003 to 6.250/a obs/ft) <br />Alert: 0.001%-2.01% obs/m (0.00031)/o-0.625% obs/ft) <br />Threshold setting range <br />g 9 <br />Action: 0.001%-2.0% obs/m (0.0003%-0.625% obs/ft) <br />Fire1:0.001%-2.0%obs/m (0.00031)/6-0.625%obs/ft) <br />Fire2: 0.001%-20.00/o obs/m (0.00031)/o-6.25% obs/ft) <br />Event log: Up to 20,000 events <br />Smoke level, user actions, alarms and faults with time and <br />Software features <br />date stamp <br />Auto Learn: Detector learns Alarm Thresholds and Flow Fault <br />thresholds by monitoring the environment. <br />* System design and regulatory requirements may restrict the monitoring area to a lesser <br />amount. <br />Spare Parts <br />VSP-960 <br />VESDA-E Mounting Bracket <br />VSP-964-03 <br />VESDA-E Smoke Detection <br />Chamber- MK3 <br />VSP-961 <br />VESDA-E Exhaust adaptor <br />VSP-965 <br />VESDA-E Sampling Module <br />us <br />VSP-962 <br />VESDA-E Filter <br />VSP-966 <br />VESDA-E VEU-A00 Front Cover <br />VSP-962-20 <br />VESDA-E Filter- 20 Pieces <br />VSP-967 <br />VESDA-E VEU-A10 Front Cover <br />VSP-963 <br />VESDA-E Aspirator <br />VKT-800 <br />VESDA-EVEU Demo Kit <br />VSP-964 <br />VESDA-E Smoke Detection Chamber <br />e VEU-A10[Z-Nombul <br />S Zone Name <br />0.11oow. Q <br />�? <br />• �. Ko <br />1 <br />LED <br />Description <br />Fire 2 <br />® <br />Fire 1 <br />- <br />Action <br />Q <br />Alert <br />Q <br />Disabled <br />Fault <br />IPower <br />Home Page <br />Icon on Display <br />Description <br />Smoke and Alarm Threshold Levels <br />0 <br />Detector OK <br />Detector Fault <br />Aspirator Fault <br />ti <br />Airflow Fault <br />Power Fault <br />-; <br />Filter Fault <br />Smoke Chamber Fault <br />A. <br />VESDAnet Fault <br />C� <br />StaX Module Fault <br />Orderina Information <br />VEU-A00 I VESDA-E VEU with LED's,Aluminium <br />Enclosure <br />VE1J-A10 I VESDA-E VEU with 3.5" Display, Aluminium <br />Enclosure <br />Approvals Compliance <br />Please refer to the Product Guide for details <br />regarding compliant design, installation and <br />commissioning. <br />