Laserfiche WebLink
ASPIRE2 Installation Data Pack <br />Page 1 of 3 <br />VE S DA" <br />Installation Data Pack for 787-8 <br />Pipe Type <br />America <br />Date <br />1 /30/07 <br />Installer <br />SEATRONICS <br />Units <br />US <br />Altitude <br />0' <br />Designed with Hole Sizes 5/64"3/32";1/8" <br />Detector : 787-8 <br />Type <br />VESDALaserPLUS <br />Endcap Usage <br />Create a Balanced Design <br />Application <br />Default <br />Aspirator Speed <br />4200rpm <br />Fire Threshold <br />0.062%/ft <br />Temperature <br />68.0°F <br />Absolute Pressure <br />1013.5hPa <br />System Flowrate <br />33.51/min <br />Manifold Pressure <br />369Pa <br />Total Pipe Length <br />402' 1" <br />Number Of Sample Points 12 <br />Maximum Transport Time 90sec <br />Minimum Hole Flow Rate 2.01/min <br />Inverted Detector <br />No <br />file: //C:AProgram Files\Vision Fire and Security\ASPIRE2\bin\IDP.html 2/l/2007 <br />