Laserfiche WebLink
CITY OF EVERETT PUBLIC WORKS 200A SERVICE CABINET <br /> PER STANDARD DRAWING#803 <br /> "SERVICE#2" <br /> COMPONENT SCHEDULE <br /> Ol METERBASE: 200 AMP,4 JAW,MANUAL BYPASS,B-LINE U264 <br /> O PANELBOARD: 120/240 VAC,250 AMP COPPER BUS, 1 PHASE,3 WIRE, 18 CKT, <br /> SERIES RATED AT 65 KAIC AT 240 VAC <br /> MAIN BREAKER:200 AMP FRAME, 125 AMP TRIP,2 POLE,EATON PDD22GO125TFFJ <br /> BOLT-ON BRANCH BREAKERS,EATON TYPE BAB: <br /> 5 -30/2 ILLUMINATION A,B,C,D,FUTURE <br /> 1 -30/1 SIGNAL <br /> 2-20/1 SPARE <br /> 1 -20/1 GROUND FAULT RECEPTACLE <br /> 1 - 15/1 CONTROL CKT <br /> 3 -SINGLE POLE PREPARED SPACES <br /> (PLEASE VERIFY BREAKER SCHEDULE PRIOR TO RELEASE) <br /> O CONTACTOR: <br /> LIGHTING RATED,30 AMP,4 POLE, 120 VAC COIL, SQD 8910DPA34V02U1,2—REQUIRED <br /> LIGHTING RATED,30 AMP,2 POLE, 120 VAC COIL, SQD 8910DPA32V02U1, 1—REQUIRED <br /> OPHOTO ELECTRIC CELL: 1800 WATT, 120 VAC,TWIST LOCK,ALR#SST-PV-IES-UL <br /> WITH 6"x 6"x 6"WIRE MESH GUARD <br /> OPHOTO-CELL BYPASS SWITCH: <br /> HOA,30MM, SQD 9001KS43B, 1 —REQUIRED <br /> OGROUND FAULT RECEPTACLE:20 AMP, 125 VAC,DUPLEX <br /> CABINET: <br /> NEMA TYPE 3R,OUTDOOR PADMOUNT, 1/8"5052-H32 ALUMINUM WELDED SEAM <br /> CONSTRUCTION,OPEN BOTTOM FRAMED WITH 2"ANGLE,2 SCREENED AND GASKETED <br /> VENTS,CABINET GROUND WITH MINIMUM BONDING WIRE TO NEUTRAL <br /> DOORS: <br /> HEAVY-DUTY CONCEALED HINGES(LIFT-OFF TYPE), <br /> STAINLESS STEEL VAULT HANDLES WITH ROLLER RODS THAT PROVIDE 3-POINT <br /> COMPRESSION ON CLOSED CELL NEOPRENE GASKET, <br /> "BEST"LOCK ON DISTRIBUTION DOOR WITH CARD HOLDER, <br /> PADLOCKABLE METER DOOR WITH POLISHED WIRE GLASS WINDOW <br /> DEADFRONT: HINGED AND SECURED WITH QUARTER-TURN FASTENERS <br /> FINISH: MILL FINISH ALUMINUM,DEADFRONTS WHITE <br /> 1 —REQUIRED KAISER PERMANENTE <br /> CITY OF EVERETT <br /> STONEWAY P.O.#P100524133 <br /> UL LISTED PER STANDARD#508A TRANSCON <br /> "SUITABLE FOR USE AS SERVICE ENTRANCE" 4-1-22 C.S.T. S.O.#67609-R3 <br /> SKYLINE ELECTRIC & MFG. COMPANY <br /> INCORPORATED <br /> Switchboards Metal Punching..Forming..Welding <br /> \ Panelboards Industrial Control Panels <br /> Steel Cabinets 3619 7TH AVENUE SOUTH <br /> — UL Registered SEATTLE,WASHINGTON 98134 <br /> TELEPHONE(206)682-4422 FAX(206)682-0927 <br />